ITC-XX Isolated Terminal Signal Conditioner/Converter

Brand: Pribusin, Inc

The ITC-XX provides high isolation from Input to Output to Power in a small, easy to install package. The universal DIN rail mount often makes it possible to install the ITC-XX right next to the instrument that is to be isolated.

The many different input and output configurations allow it to be used is a great variety of applications ranging from PLC front end conditioning to adding an extra loop with lots of drive to an existing almost fully loaded, loop.

The high output drive (100 Ohms @ 4-20 mA) allows the ITC-XX to drive several other instruments directly from its output. The standard two wire supply allows the ITC-XX to be used with two wire field transmitters such as differential pressure transducers, temperature sensors, etc.
Features
  • High Input-Output-Power Isolation (1500Vac Test).
  • Small Size - Fits on Terminal Block Rail.
  • Industry Standard Inputs: 4-20 mA, 1-5 Vdc, and more.
  • Industry Standard Outputs: 4-20 mA, 1-5 Vdc, more.
  • High Output Drive on Current Outputs (1000 Ohms for 4-20mA output).
  • Power: 24 Vdc, 80 mA.
  • Two Wire Supply Output for Two Wire Transmitters.
  • High Noise Rejection.
  • CSA and NRTL Approved (LR 51078).

Specifications

Accuracy, Linearity

  • ± 0.1 % Max., ± 0.05 % Typical

Change Effects

  • -0.03 % Per 100 ohms Change (4-20 mA Only) Calibrated at 250 ohms

Common Mode Rejection

  • at 60 Hz = 120 dB

Coupling Capacitance

  • Input-Output-Power = 20 PF

Drift at 25° C

  • ± 0.1 %

Input Impedance

  • 50 ohms

Isolation

  • 1500 Vac Input to Output to Power (Test)

Operating Temperature

  • -40° to +50° C

Power

  • 24 Vdc (19-29 Vdc) @ 80 mA (160 mA is Two Wire Supply is Used)

Response Time

  • 50 milliseconds to 63 % of Final Value, 250 milliseconds to 99 % of Final Value

Temperature Effects

  • ± 0.5 % Max., ± 0.2 % Typical for 40° C Change
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more