Yodify Product Library
Add the RM140W Overfill Protection Rack Monitor to your store or catalog  
Book Your Demo and See How
or create your store

RM140W Overfill Protection Rack Monitor

Brand: Civacon Corporate

Overfill protection and grounding monitor for truck or rail loading in petro-chemical applications.

Built to function with all probes designed to the API code: API RP 1004 and the EU Standard EN13922, the RM140W Series is the world’s most flexible and adaptable monitor.

The RM140W provides a fail-safe, state-of-the-art overfill protection and grounding monitoring system that is compatible with all commonly used overfill protection and grounding systems.
Features
  • Automatic Sensing of 2-Wire/Thermistor or 5-Wire Overfill Systems, No Manual Switching or Inspection Required
  •  Supports Up to 8 2-Wire/Thermistor Probes and Up to 12 5-Wire Probes
  • High-output Display Visible in Direct Sunlight, Provides Flexibility for Indoor/Outdoor Use
  • Coded Wireless By-pass Key for Secure and Reliable Operation
  • Self-test at Start Up/Continuous Self-monitoring, Ensures Safety Throughout the Loading Process
  • Separate Grounding and Overfill Control Outputs
  • Compact and Functional Design is Easy to Install, Perfect for Tight Spaces or Crowded Work Areas
  • Global Electronic Compatibility, Able to Operate on Almost Any Electric Service
  • RM100 is Directly Compatible with PD100 Probe Doctor as a “Plug-in Replacement”

1 - 11 of 11 Part Numbers
5542
5542
Fuse 5A at 250VAC Anti-surge
6983
6983
RM140W Bypass Fob
6985
6985
RM100 Safety Ground Harness
6987
6987
Fuse 400mA, 250VAC Anti-surge, 1500A Breaking Capacity
7100
7100
Civacon Optic Plug
7300
7300
Civacon 6-Channel Thermistor Plug
7500
7500
Civacon Junction Box
7720
7720
Civacon Earth Clamp with Straight Cable
RM100-3 
RM100-3 
RM100 Aluminium Safety Barrier
RM100-4 
RM100-4 
RM100 Polycarbonate Terminal Cover
RM100-5K
RM100-5K
RM100 PCB Assembly Complete Kit: RM100-5 + 6959 Display
1 - 11 of 11 Part Numbers

Specifications

Power

  • 240 V Operation
  • 110 V Operation

Minimum Input Voltage

  • 185 Vac
  • 85 Vac

Maximum Input Voltage

  • 275 Vac
  • 135 Vac

In-rush Current

  • 2.2A
  • 2.3A

Maximum Current

  • 400 mA

Normal Power Consumption

  • 8.6W - No probe
  • 20W - 8x 2-wire probes

Mains Power Fuse Rating

  • 250 V, 400 mA anti-surge 1500 A Breaking Capacity

Nominal Voltage

  • 10.5 V
  • 13.02 V Max.

Nominal Current

  • 116 mA
  • 121 mA Max.

Relay Outputs

  • Overfill Monitoring Relay

Relay Contacts

  • Common
  • Normally Open
  • Normally Closed

Maximum Contact Voltage

  • 250 Vac

Maximum Contact Load

  • 5A - resistive
  • 2.5A - inductive

Relay Fuse Rating

  • 250 V at 5A anti-surge

Width

  • 12.8"
  • 324 mm

Height

  • 13.4"
  • 340 mm

Depth

  • 13.4"
  • 170 mm

Weight

  • 36.37 lb
  • 16.5 kg

Material

  • Aluminium Housing Base and Cover
  • Laminated Glass Window

Type of Protection

  • Explosion-proof enclosure for Group II, Zone 1, Ex d [ia]

IEC Certificate Marking

  • IECEx TSA 05.0049X Ex d [ia] IIB T6 (Tamb=60° C) IP66

ATEX Certificate Marking

  • DEMKO 06 ATEX 140833X 0518 II 2 (1) G EEx d [ia] IIB T6 Ta = -20° to 60° C

EU Directives

  • 73/23/EEC & 93/68/EEC (Low Voltage) 94/9/EC (ATEX) 89/336/EEC (EMC) 2002/95/EC (RoHS) Compatible with EN 13922

FM Approval Marking

  • FM Approved for US and Canada. Explosionproof with I.S. Outputs Intrinsically Safe Sécurité Intrinsèque Exia Class I, Div. 1, Group C & D, T6 Ta = -25° to 60° C
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team