SEM1750 Signal Conditioner
Brand: Status InstrumentsThe SEM1750 is a cost effective dual channel signal conditioner that accepts a bipolar voltage or current signal and isolates to provide ranged industrial process output signals such as (0-20) mA, (4-20) mA, (0-10) V, (1-5) Vdc.
The SEM1750 is configured using our easy to use configuration software USB Speed Link.
USB speed link offers the user two levels of configuration: a basic current/voltage signal converter where the device can be set as dual channel or signal splitter, or for more advanced applications, a configuration menu offering a wide range of user set functions, including process scaling and profiling, maths functions, signal damping, sensor linearisation and signal preset for diagnostics purposes.
Features- Dual Channel Voltage Or Current (Active/Passive)Inputs and Outputs
- 5 Port Isolation To 3.75Kv
- Can Be Configured As An Active Signal Splitter
- User Selectable Maths Functions On Each Output Channel
- Signal Linearisation
- Signal Simulate Function For Diagnostics
Specifications
Brand
Accuracy
- ± 5 µA or (mA Out/2,000), whichever is greater - Output Current (Channel 1 & 2)
- ± 5 mV - Output Voltage (Channel 1 & 2)
- Range -22 to 22 mA: ± 5 µA - Input Current (Channel 1 & 2)
- Range -22 to 22 V: ± 5 mV - Input Voltage (Channel 1 & 2)
- Range -50 to 50 mA: ± 10 µA - Input Current (Channel 1 & 2)
- Range -50 to 50 V: ± 10 mV - Input Voltage (Channel 1 & 2)
Approvals & Certifications
- BS EN 61010-1
Communication
- USB
Damping Adjustment
- 0 to 3,600 seconds, Independent Rise & Fall Delays Per 1 V or 1 mA Output Change
Electrical Connectors
- Screw Terminal
Electrical Protection
- Internal Fuse (0.5 A)
- Overvoltage Protection at 250 V
Humidity
- 10 to 90 % Relative Humidity, Non-Condensing
Input
- ± 50 mA (Current)
- ± 50 Vdc (Voltage)
- Transmitter Supply: 22 Vdc at 25 mA
Input Impedance
- 1 Megaohm (Voltage)
- 10 ohms (Current)
Isolation
- 3,750 Vdc - Isolation Test Voltage (Input Output Ports)
- 4,000 Vac - Isolation Test Voltage (Supply to Input/Output)
Linearization
- User Linearization: 22-Segment Input to Process Variable
- User Linearization: 3 to 22-Segment Input to Process Range
Load
- Maximum
- Output Voltage Load: Min. 1 Kiloohm (Compensation Provided)
Operating Temperature
- -30° to 70° C (-22° to 158° F)
Output
- 0-10 V - Voltage Working Range
- 0-20 mA - Current Working Range
- Current Sink: Supply Voltage 10-28 Vdc
- Maximum
Power
- 3 W at Full Output Current
Power Supply Effect
- 0.2 µA/V (Sink Mode) - Loop Voltage Effect
Stability
- 0.02 % of Full Scale/°C
Storage Temperature
- -40° to 85° C (-40° to 185° F)
Supply Voltage
- 20-240 Vac, 50/60 Hz
- 20-240 Vdc
System Requirements
- Windows® XP
Thermal Drift
- ± 1 mV/°C - Output Voltage
- 1 µA/°C - Output Current
Turn-On Time
- 4 seconds
Update Time
- 140 milliseconds (16-bits Full Range)
- 420 milliseconds (18-bits Full Range)
- 70 milliseconds (14-bits Full Range)
- Warm-Up Time: 1 Minute to Full Accuracy
Voltage
- Maximum
- Working Voltage: 253 Vac