Yodify Product Library
Instantly add the 120 Series Type C120 120 & 121 Temperature Switch and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

120 Series Type C120 120 & 121 Temperature Switch

Brand: United Electric Controls Ltd

As safety requirements become more stringent, the determining factor in specifying an industrial pressure, differential pressure and/ or temperature switch rests upon that switch protecting equipment, processes and personnel. 

Meeting hazardous location requirements through worldwide approvals and certifications, UE’s 120 Series is the choice where potentially explosive or highly corrosive atmospheres exist.

The 120 Series offers a variety of pressure, vacuum, differential pressure and temperature ranges, as well as process connections, wetted materials and sensor types. 

With a common flexible platform, models can quickly be adapted at the factory for special requirements, such as ranges, process connections and electrical ratings. Typical industries using 120 Series switches include chemical, petrochemical, refinery and oil & gas production and transmission.
Features
  • Standard product approvals include cULus, ATEX & IECEx
  • Many models compliant to NACE MR-0175
  • Internal adjustment hex screw or external adjustment via calibrated dial(s) with tamper resistant cover
  • Integral cover lock
  • Wide variety of sensor materials
  • Wide adjustable deadband models
  • Heat tracing temperature models

Specifications

Adjustment Type

  • Factory Set (Pre-Set)

Ambient Temperature Range

  • -50° to 71° C (-58° to 160° F)

Applications

  • Chemicals
  • Oil & Gas Production
  • Petrochemical
  • Refinery
  • Transmission

Approvals & Certifications

  • ISO 9001

Approvals & Certifications

  • ATEX Directive (94/9/EC) II 2 G Ex d IIC T6 Gb II 2 D Ex Tb IIIC T85° C Db IP66 Tamb: -40° to 75° C (-40° to 167° F) UL International Demko A/S (N.B.# 0539) Certificate # Demko 09-ATEX-0815573X Rev. 2 EN 60079-0, 60079-1, 60079-31 II 1 G Ex ia IIC T6 Ga
  • CE
  • CQST: CNEx15.2541X Ex d IIC T6 Gb Ex TD A21 T85° C IP66 Tamb. = -40° to 75° C (-40° to 167° F) GB3836.1,GB3836.2 & GB12476
  • CRN
  • CSA C22.2 No. 25 & 30 - File # E43374
  • GOST-R 0Ex ia IIC T6 Ga x Tamb: -50° to 60° C (-58° to 140° F) NANIO CCVE Certification Center RU C-US.ГБ05.B.01185 ГOCT P MЭК 60079-11, ГOCT P MЭК 60079-0-2011, ГOCT 31610.26, IEC 60079-26
  • GOST-R 1Ex d IIC T6 Gb x Tamb: -50° to 80° C (-58° to 176° F)
  • GOST-U 1ExdIICT6X Tamb: -56° to 85° C (-68.8° to 185° F) СВIДОЦТВО #720 by DVSTS VE (TCCExEE)
  • IECEx Certified Ex d IIC T6 Gb Ex Tb IIIC T85° C Db IP66 Tamb. = -40° to 75° C (-40° to 167° F) IEC 60079-0, 60079-1, 60079-31 Certificate # IECEx UL 03.0001X
  • INMETRO Ex d IIC T6 Gb Ex Tb IIIC T85° C Db IP66 -40° ≤ Ta ≤ 75° C UL-BR 15.0179X ABNT NBR IEC 60079-0 ABNT NBR IEC 60079-1 ABNT NBR IEC 60079-31
  • INMETRO Ex ia IIC T6 Ga -50° ≤ Ta ≤ 60° C UL-BR 15.0169X ABNT NBR IEC 60079-0 ABNT NBR IEC 60079-11 ABNT NBR IEC 60079-26
  • KC
  • KOSHA, Article 34 of Industrial Safety & Health Law Ex d IIC T6 -40° C < Tamb < 75° C, Certification# 10-AV4BO-0712, 10-AV4BO-0713
  • Low Voltage Directive (LVD) 2006/95/EC
  • PESO: CCEs Identification# P314108 / 1 EN 60079-0, 60079-1 Ex ia IIC T6 Ga, CCEs Identification# P305465 / 1 EN 60079-0, 60079-11, 60079-26
  • PED: 97/23/EC
  • TS ML041200701BZ4
  • UL (C,US) 50 & 1203: Class I, Div. 1 & 2, Groups B, C, D, Class II, Div. 1 & 2, Groups E, F, G, Class III, Class I, Zone 1, Group IIB + H₂ T6

BSP Connection

  • G 1/2” Male

Bulb Material

  • 304 Stainless Steel

Capillary Length

  • 6 feet (1.82 metres)

Cover Material

  • Gasketed Stainless Steel Tamper-Resistant Dial Cover

Deadband

  • Temperature Deadband: Typically 2 % of Range Under Laboratory Conditions (21.11° C (70° F) Ambient Circulating Bath at Rate of 0.5° F Per Minute Change)

Electrical Connectors

  • 3/4” NPT
  • Terminal Block

Electrical Contacts

  • Gold
  • Normally Closed
  • Normally Open

Electrical Rating

  • 0.25 A at 250 Vdc Resistive
  • 0.5 A at 125 Vdc
  • 1 A at 125 Vac Resistive
  • 1 A at 48 Vdc
  • 10 A at 125 Vac/dc
  • 11 A at 125/250 Vac Resistive
  • 15 A at 125/250 Vac Resistive
  • 15 A at 125/250/480 Vac Resistive
  • 20 A at 125/250/480 Vac Resistive
  • 3 A at 28 Vdc
  • 30 A at 125/250/277 Vac Resistive
  • 5 A at 125/250 Vac Resistive
  • 5 A at 30 Vdc

Enclosure Finish

  • Epoxy Powder-Coated

Enclosure, Body Material

  • Gasketed Die Cast Aluminum

Environmental Protection

  • Flameproof
  • Intrinsically Safe
  • IP66
  • Typical 4X
  • Typical 7
  • Typical 9

Fill Material

  • Non-Toxic Oil

Mounting

  • Pipe
  • Surface

Name Plate, Tag Material

  • Aluminum
  • Stainless Steel, Paper ID Tag & Wire Attachment

NPT Connection

  • 1/2” NPT Male

Process Connection Material

  • 304 Stainless Steel
  • Brass

Repeatability

  • Set Point Repeatability: ± 1 % of Full Scale Range

Service

  • Oxygen Service Cleaned in Accordance with ASTM G93, Verification Typical I, Tests 1 through 3

Set Point - Decreasing

  • -17.8° to 218.3° C (0° to 425° F)

Set Point - Increasing

  • -17.8° to 218.3° C (0° to 425° F)

Shock

  • Set Point Repeats after 15 G, 10 millisecond Duration

Stem Material

  • 316L Stainless Steel
  • Brass

Storage Temperature

  • -54° to 71° C (-65° to 160° F)

Switch Type

  • Hermetically Sealed
  • One or Two SPDT, Dual Switch may be separated up to 100 % of Range

Temperature Range

  • Maximum

Vibration

  • Set Point Repeats after 2.5 G, 5 to 500 Hz
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more