Yodify Product Library
Instantly add the mA-Isolating Repeater Series 9164 - Non Ex i and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

mA-Isolating Repeater Series 9164 - Non Ex i

Brand: R. STAHL AG

The mA - isolating repeaters are used for connection of 4-wire transmitters to active 2-wire inputs (source) as well as to galvanic isolation. The devices bidirectionally transfer a superimposed HART communications signal.
Features
  • Interconnection of two mA-sources and active 2-wire inputs is possible
  • Ideal solution for integrating 4-conductor measuring transmitters into analogue input supplies.
  • Bidirectional HART transmission 4 ... 20 mA
  • Galvanic isolation between input and output

1 - 1 of 1 Part Numbers
224366
224366
R. STAHL mA Isolating Repeater Non-Ex I Field Circuit
Interconnection of two mA-sources and active 2-wire inputs is possible

Ideal solution for integrating 4-conductor measuring transmitters into analogue input supplies.

Bidirectional HART transmission 4 ... 20 mA

Galvanic isolation between input and output

Ambient Conditions

  • Ambient temperature - -40 °C ... +75 °C
  • Ambient temperature max. - +75 °C
  • Ambient temperature min. - -40 °C
  • Relative humidity max. - ≤ 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - without
  • Auxiliary power nom. voltage - 30 V
  • Nominal current - 30.00 mA
  • Polarity reversal protection - yes
  • Power dissipation max. - 3.7 V x 20 mA + 20 mA x
  • Power dissipation max. 2 - (supply voltage - RL x 20 mA)

Electrical Data

  • communication signal - HART, 0.5 ... 5 kHz
  • Isolating repeater mode - Yes
  • Number of channels - 1
  • Transmitter supply mode - No

Explosion Protection

  • Application range (zones) - 2
  • ATEX dust certificate - BVS 15 ATEX E 068 X
  • ATEX gas certificate - R. STAHL Test Report 11006
  • Certificates - Canada (FM), SIL (exida), USA (FM)
  • Gas explosion protection ATEX - II 3 G Ex ec IIC T4 Gc
  • Installation in Division NEC 500 - (Class I) 2

Galvanic isolation

  • Galvanic isolation Ex i to Ex i - 500 V AC

General

  • Functional Description - The mA - isolating repeaters are used for connection of 4-wire transmitters to active 2-wire inputs (source) as well as to galvanic isolation. The devices bidirectionally transfer a superimposed HART communications signal.
  • Highlights - Interconnection of two mA-sources and active 2-wire inputs is possible Ideal solution for integrating 4-conductor measuring transmitters into analogue input supplies. Bidirectional HART transmission 4 ... 20 mA Galvanic isolation between input and output
  • Product Description - mA isolating repeater Non-Ex i field circuit
  • Product Type - 9164/13-20-55
  • Title Product Variant Technical Data - 9164/13-20-55 mA-isolating repeat. nEx i
  • WebCode - 9164B

Input

  • Active supply voltage range - 5 - 30 V
  • Input - 4 ... 20 mA HART (sink)
  • Input function - Isolation amplifier
  • Input functional range - 3,6 - 25 mA
  • Input resistance - > 10 kΩs
  • input signal - 3,8 ... 20,5 mA with HART
  • voltage drop - < 3,7 V

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Grid dimension - 12.00 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.090 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 1.5 mm²
  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 1.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Behaviour of the output - = input signal
  • deviation - ≤ 0,1 %
  • LFD relay - No
  • linearity error - ≤ 0,05 %
  • offset error - ≤ 0,05 %
  • Output - passive HART (sink)
  • Output current at I e =0 - 0 mA
  • output signal - 3.8 - 20.5 mA with HART
  • Settling time 10 … 90 % - ≤ 1 ms
  • Temperature influence error limits - ≤ 0,05 % / 10K
1 - 1 of 1 Part Numbers
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more