Yodify Product Library
Instantly add the CI 141-180 Contactor and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
CI 141-180 Contactor
Brand: DanfossContactors CI 141-180 are intended for AC coil voltages and cover the power range 55-220 kW.
The largest types, CI 210-420 EI have electronic control circuits that mean low holding power and wide coil voltage ranges on both 50 and 60 Hz.
The "EI" version is supplied with an integrated interface relay for PLC applications with 24 Vdc output.
Accessories include a wide selection of clip-on auxiliary contact blocks and timers. In addition, the range also includes thermal overload relays and an electronic motor protection relay for the protection of squirrel-cage motors.
1 - 8 of 8 Part Numbers
037H308222
- Type - CI 180
- Coil Voltages - 110 V, 50 Hz / 120 V, 60 Hz
037H308231
- Type - CI 180
- Coil Voltages - 220-230 V, 50 Hz / 240 V, 60 Hz
037H308233
- Type - CI 180
- Coil Voltages - 240 V, 50 Hz / 277 V, 60 Hz
037H308237
- Type - CI 180
- Coil Voltages - 380-400 V, 50 Hz / 440 V, 60 Hz
037H333922
- Type - CI 141
- Coil Voltages - 110 V, 50 Hz / 120 V, 60 Hz
037H333931
- Type - CI 141
- Coil Voltages - 220-230 V, 50 Hz / 240 V, 60 Hz
037H333933
- Type - CI 141
- Coil Voltages - 240 V, 50 Hz / 277 V, 60 Hz
037H333937
- Type - CI 141
- Coil Voltages - 380-400 V, 50 Hz / 440 V, 60 Hz
1 - 8 of 8 Part Numbers
Specifications
Brand
Ambient Temperature Range
- -25° to 80° C (-13° to 176° F)
Approvals & Certifications
- DIN 40046
- DIN 50016
- EN 60947
- EN 60947-4-1
Approvals & Certifications
- BV
- CE
- CSA
- IEC 60947-4-1
- LLOYD
- UL
Coil Voltage
- 110-440 V, 50/60 Hz
Consumption
- 7 W - Coil Consumption AC
Current
- 1 A - secondary Current
- 189 A at 60° C (140° F)
- 225 A at 40° C (104° F)
- 5 A - secondary Current
Direct Mount
- Yes
Electrical Connectors
- Screw Typical
- Terminal Block
Electrical Contacts
- Normally Closed
- Normally Open
Frequency
- 50/60 Hz
Indication
- LED - Overload Indication
Input Impedance
- 0.42 megaohms
Load Limit
- 220-1,000 V
Mounting
- Direct Mounting
Operating Temperature
- -25° to 60° C (-13° to 140° F)
Output
- 24 Vdc
Power
- 13 VA - Holding Power
- 240 W - Inrush Power
- 380 VA - Inrush Power
- 55-220 KW
- 6 W - Holding Power
Process Connection Style
- Lug
Response Time
- 2 to 30 seconds
Storage Temperature
- -40° to 80° C (-40° to 176° F)
Supply Voltage
- 12 kV - Pulse Voltage
Torque
- 10 to 12 Nm (88.50 to 106.2 In/Lbs)
Turn-Off Time
- 25 to 110 milliseconds - Break Time
Turn-On Time
- 20 to 45 milliseconds - Make Time
Vibration
- 2 G, 10 to 150 Hz - Tested & Passed in Accordance with IEC 68-2-6