Brand: A-T Controls, IncThe YT-1000R & YT-1000L are advanced electro-pneumatic valve controllers for single or double acting rotary or linear actuators.
No additional parts are necessary to change between single or double acting actuators and direct or reverse acting
Features- Corrosion Resistant Coated Aluminum Diecast Housing Stands Up to Harsh Environments
- Pilot Valve Design Reduces Air Consumption by More than 50%
- Vibration Resistant Design Maintains Superior Performance in Poor Conditions - No Resonance Effects from 5 to 200 Hz
- Optional Gauges and Orifices
1 - 12 of 20 Part Numbers

YT-1000L
- Type of Actuator - Linear
- Agency Approvals - Standard

YT-1000L-CSA
- Type of Actuator - Linear
- Agency Approvals - CSA Approved Class 1, Zone 1, Groups IIB, T5, IP66

YT-1000L-FM
- Type of Actuator - Linear
- Agency Approvals - FM Approved Class I, Division 1, Groups C & D, Class II/III, Div I, Groups E, F & G. Type 4X

YT-1000L-S-N-1-3-2-S-0

YT-1000L-S-N-4-3-2-S-0

YT-1000R
- Type of Actuator - Rotary
- Agency Approvals - Standard

YT-1000R-CSA
- Type of Actuator - Rotary
- Agency Approvals - CSA Approved Class 1, Zone 1, Groups IIB, T5, IP66

YT-1000R-D-F-5-3-2-S-0-0

YT-1000R-D-M-5-2-2-S-0-0

YT-1000R-D-M-5-3-2-S-0-0

YT-1000R-D-N-5-2-2-S-1-0

YT-1000R-D-N-5-2-2-S-1-3
1 - 12 of 20 Part Numbers
Specifications
Brand
Actuator Type
- Double-Acting
- Linear
- Rotary
- Single Action
Air Consumption
- 0.19 scfm (0.32 m³/hour)
Approvals & Certifications
- CSA
- FM
Conduit Connection
- 1/2" NPT
Enclosure Finish
- Corrosion-Resistant Coating
Enclosure, Body Material
- Aluminum Die Cast
Environmental Protection
- Dust-Proof
- Explosion-proof ExiaIIBT6, ExdmIIBT6, ExdmIICT6
- IP66
- Weatherproof
Flow Capacity
- 7 scfm (11.89 m³/hour) - Max.
Frequency
- No Resonance Effects from 5 to 200 Hz
Gauge Connection
- 1/8" NPT
Hysteresis
- ± 1 % of Full Scale
Input Signal
- 4-20 mA DC
Linearity
- ± 2 % of Full Scale
NPT Connection
- 1/4" NPT
Operating Temperature
- -20° to 70° C (-4° to 160° F)
Sensitivity
- 0.5 % of Full Scale
Supply Pressure
- psig: 20 to 100 (kPa: 137.9 to 689.5, bar: 1.37 to 6.89)