Yodify Product Library
Instantly add the BF Series Bi-Flame Dual Burner Monitoring System and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

BF Series Bi-Flame Dual Burner Monitoring System

Brand: Fireye, Inc

Controls startup sequence and monitors flame for two individual burners.

The Fireye Bi-Flame Monitoring System controls the startup sequence and monitors the flame of two individual gas, oil, or combination gas/oil burners connected to a common valve train.

Its dynamic onboard testing checks for faulty relays, proof of valve closure, high and low fire switch interlocks, and shorted air switch.

Its dip switches allow sequence and timing functions, as well as system configuration.

It is also capable of modulation (high and low fire purging) and monitoring up to four auxiliary inputs. It is UL recognized in the US and Canada, and FM approved.
Features
  • LED indicator lights provide operating and alarm status
  • Combustion air flow check terminal
  • Main fuel valve proof of closure terminal
  • Low fire start terminal
  • High fire purge check terminal
  • Recycle mode
  • Pilot test mode
  • Interrupted or intermittent pilot
  • Spark, pilot flame & main flame separation
  • 4 auxiliary inputs
  • Real time flame signal test jacks
  • Optional alpha numerical display with history log

1 - 2 of 2 Part Numbers
BF22P1211-FR
BF22P1211-FR
Complete Assembly RS-232
BF22P1212-FR
BF22P1212-FR
Complete Assembly RS-485
1 - 2 of 2 Part Numbers

Specifications

Brand

Supply

  • 120 VAC (+10%, -15%), 50/60 Hz Standard
  • Internal Power Consumption: 24VA

Temperature Ranges

  • Bi-Flame: -40°F to 140°F (-40°C to 60°C)
  • 90° UV Scanner: 0°F to 140°F (-20°C to 60°C)
  • UV Scanner: -40°F to 257°F (-40°C to 125°C)
  • NEMA4 UV Scanner: 0° to 257°F (-20° to 125°C)
  • Self-Check UV: -40°F to 140°F (-40°C to 60°C)
  • Remote Display: 32°F to 122°F (0°C to 50°C)

Flame Failure Response

  • 3 seconds ± 0.5 seconds

TFI/Pilot Interrupt

  • 5, 10, or 15 seconds (Selectable)

Purge Time

  • Modulating: Selectable from 0-225 seconds in 15 second Increments, or 0-15 minutes in 1 minute increments
  • Process: Selectable from 0-15 minutes in 1 minute Increments, or 0-60 minutes in 4 minute Increments

Approvals

  • UL recognized for Canada and USA; File MP1537 (category MCCZ2)
  • FM Approved; J.1.2Y3A5.AF (class 7610)
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more