BF Series Bi-Flame Dual Burner Monitoring System
Brand: Fireye, IncControls startup sequence and monitors flame for two individual burners.
The Fireye Bi-Flame Monitoring System controls the startup sequence and monitors the flame of two individual gas, oil, or combination gas/oil burners connected to a common valve train.
Its dynamic onboard testing checks for faulty relays, proof of valve closure, high and low fire switch interlocks, and shorted air switch.
Its dip switches allow sequence and timing functions, as well as system configuration.
It is also capable of modulation (high and low fire purging) and monitoring up to four auxiliary inputs. It is UL recognized in the US and Canada, and FM approved.
Features- LED indicator lights provide operating and alarm status
- Combustion air flow check terminal
- Main fuel valve proof of closure terminal
- Low fire start terminal
- High fire purge check terminal
- Recycle mode
- Pilot test mode
- Interrupted or intermittent pilot
- Spark, pilot flame & main flame separation
- 4 auxiliary inputs
- Real time flame signal test jacks
- Optional alpha numerical display with history log
Specifications
Brand
Supply
- 120 VAC (+10%, -15%), 50/60 Hz Standard
- Internal Power Consumption: 24VA
Temperature Ranges
- Bi-Flame: -40°F to 140°F (-40°C to 60°C)
- 90° UV Scanner: 0°F to 140°F (-20°C to 60°C)
- UV Scanner: -40°F to 257°F (-40°C to 125°C)
- NEMA4 UV Scanner: 0° to 257°F (-20° to 125°C)
- Self-Check UV: -40°F to 140°F (-40°C to 60°C)
- Remote Display: 32°F to 122°F (0°C to 50°C)
Flame Failure Response
- 3 seconds ± 0.5 seconds
TFI/Pilot Interrupt
- 5, 10, or 15 seconds (Selectable)
Purge Time
- Modulating: Selectable from 0-225 seconds in 15 second Increments, or 0-15 minutes in 1 minute increments
- Process: Selectable from 0-15 minutes in 1 minute Increments, or 0-60 minutes in 4 minute Increments
Approvals
- UL recognized for Canada and USA; File MP1537 (category MCCZ2)
- FM Approved; J.1.2Y3A5.AF (class 7610)