Yodify Product Library
Instantly add the SEM310 Temperature Transmitter and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

SEM310 Temperature Transmitter

Brand: Status Instruments

The SEM310 has the HART communications protocol which allows the user to quickly and easily down-load information or interrogate the device enabling the following:
  • Simple re-ranging of sensor type and range
  • Easy on site re-calibration
  • Operation with proprietary software packages such as AMS Plant Web and Cornerstone
  • Remote configuration on the 4-20 mA loop with a hand held communicator or with a PC and HART modem
  • Online digital communication concurrent with a 4-20 mA Analog signal

1 - 2 of 2 Part Numbers
SEM310
SEM310
  • Communication - HART Transmitter
SEM310X
SEM310X
  • Communication - HART Transmitter is Version
1 - 2 of 2 Part Numbers

Specifications

Accuracy

  • ± 5 µA
  • Basic Measurement Accuracy: ± 10 µV ± 0.07 % of Reading
  • Basic Measurement Accuracy: 0.01 % of Full Range Input ± 0.07 % of Reading
  • Basic Measurement Accuracy: 0.04 % of Full Range Input ± 0.04 % of Reading or 0.5° C (0.9° F), whichever is greater
  • Basic Measurement Accuracy: 0.1 % of Full Range Input
  • Cold Junction: ± 0.5° C (± 0.9° F) Tracking 0.05° C/°C
  • Cold Junction: 0.5° C (0.9° F) Tracking 0.05° C/°C

Approvals & Certifications

  • ATEX: II1 GEExia IICT4-T6
  • EMC: BS EN 61326
  • FM: 3610-IS/I/1/ABCD/T4
  • IEC 584-1

Burn-Out

  • Sensor Burn-Out: Downscale (3.75 mA)
  • Sensor Burn-Out: Upscale (21.5 mA)

Communication

  • HART

Control Functions Characteristics

  • Linear

Current

  • RTD Excitation Current: 300-500 µA

Enclosure, Body Material

  • ABS

Environmental Protection

  • Hazardous Area

Humidity

  • 0 to 95 % Relative Humidity, Non-Condensing

Input

  • 3-Wire Potentiometer
  • Input Out of Range: 20.5 mA - Max.
  • Input Out of Range: 3.8 mA Min.
  • Voltage Source

Input Impedance

  • 10 megaohms

Isolation

  • Input/Output Breakdown Isolation: 500 Vac

Operating Temperature

  • Cold Junction: -40° to 85° C (-40° to 185° F)

Output

  • 4-20 mA
  • Maximum
  • Minimum 3.75 mA

Output Load

  • Minimum Loop Load: 250 ohms
  • Minimum Loop Load: 500 ohms when Supply Voltage is over 30 V

Power Supply Effect

  • 0.2 μA/V

Range

  • -10 to 75 mV
  • Slidewire: 0 to 100 %

Resistance

  • 10 to 390 ohms
  • Maximum

RTD Type

  • Ni100
  • Pt100

Sensor, Probe Connection

  • 2-Wire
  • 3-Wire
  • 4-Wire

Sensor, Probe Type

  • E Thermocouple
  • J Thermocouple
  • K Thermocouple
  • L Thermocouple
  • N Thermocouple
  • RTD
  • R Thermocouple
  • S Thermocouple
  • Thermocouples
  • T Thermocouple

Span - Minimum

  • 25° to 100° C (77° to 212° F)
  • 5 mV
  • 5 % of Full Range Input

Storage Temperature

  • -50° to 85° C (-58° to 185° F)

Supply Voltage

  • 10-40 Vdc

Temperature Range

  • Sensor Range: -200° to -850° C (-328° to -1,498° F) (18 to 390 ohms)
  • Thermocouple: -200° to 1,760° C (-328° to 3,200° F)

Thermal Drift

  • 1 µA/°C
  • Span: 0.01 %/°C
  • Zero: 0.005 % of Span/°C
  • Zero: 0.008° C/°C
  • Zero: 0.1 µV/°C

Time Constant

  • Filter Off: 0.5 second (To 90 % of Final Value) Filter Factor Off / Selectable between 1 second & 32 seconds or Adaptive

Update Time

  • 120 seconds

Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more