Yodify Product Library
Instantly add the MA15 Range Fieldbus Surge Protection and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

MA15 Range Fieldbus Surge Protection

Brand: MTL Instruments

The MA15 range of surge protection devices protects electronic equipment and computer networks against the effects of ‘noise pollution’ induced in mains power supplies.

MA15 units ‘clean up’ the effects of industrial noise and surges caused by lightning, switching devices, thyristor controls, transmission system overloads and power-factor correction circuits.

Industrial control systems utilising programmable logic controllers - plc and industrial computers are particularly vulnerable due to the aggressive electrical environments for which they are intended, such as process plants, factories and water treatment sites.

Although industrial computers and plcs are designed to be rugged, the extra protection provided by the DIN rail mounting MA15 units is critical.

Ideally suited for protecting panel mounted equipment and typically used in the controls section of a motor control centre: MCC, the MA15 range provides surge and RFI protected power.

Suitable for AC or DC application, MA15 units reduce both electromagnetic emissions and the susceptibility of the associated equipment to emissions from other sources.
Features
  • Protects Panel Loads Up to 15 Amps in Series, Unlimited Amps in Parallel
  • Suitable for AC or DC Application
  • Thermal and Short Circuit Protection
  • Optional LED Status Indication Feature
  • Exceeds Requirements of IEC 61000-4-5
  • 10 year Product Warranty

1 - 6 of 6 Part Numbers
MA15/D/1/SI
MA15/D/1/SI
MCOV: 127, Modes of Protection and MLV: L - N and 560 Vpk, L - G and 560 Vpk, N - G and 560 Vpk
MA15/D/1TT/SI
MA15/D/1TT/SI
MCOV: 127, Modes of Protection and MLV: L - N and 560 Vpk, L - G and 990 Vpk, N - G and 960 Vpk
MA15/D/2/SI
MA15/D/2/SI
MCOV: 254, Modes of Protection and MLV: L - N and 980 Vpk, L - G and 990 Vpk, N - G and 960 Vpk
MA15/D/2TT/L
MA15/D/2TT/L
MCOV: 254, Modes of Protection and MLV: L - N and 975 Vpk, L - G and 975 Vpk, N - G and 975 Vpk
MA15E/D/1/SI
MA15E/D/1/SI
MCOV: 127, Modes of Protection and MLV: L - N and 560 Vpk, L - G and 560 Vpk, N - G and 560 Vpk, Up: <0.6kV
MA15E/D/2/SI
MA15E/D/2/SI
MCOV: 254, Modes of Protection and MLV: L - N and 980 Vpk, L - G and 990 Vpk, N - G and 960 Vpk, Up: <1kV
1 - 6 of 6 Part Numbers

Specifications

Maximum Leakage Current

  • < 0.3 mA

Typical Maximum Attenuation

  • -55 dB at 100 MHz

Humidity

  • 95 % Relative Humidity, Non-Condensing

Connectors

  • Screw Terminal

Mounting

  • T-section (‘Top-hat’)
  • 35 mm DIN Rail

Weight

  • 3.53 oz. (100 g)

Compliance Standards

  • BS EN 61326-1: 2013
  • IEC 61643-11: 2011

LED Indication

  • Green LED On - Protection Present
  • Green LED Off - Internal Failure