Yodify Product Library
Instantly add the 5531B Loop Powered LCD Indicator and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

5531B Loop Powered LCD Indicator

Brand: PR Electronics

  • 4 digit 1/8 DIN (48 x 96 mm) loop-powered LCD display
  • Easy push-button configuration
  • Backlit LCD display is readable in low light conditions
  • Display can be mounted in the safe area or in I.S. / Ex zone
Features
  • With a full measurement range of 3.6 to 23 mA, the 5531 is NAMUR NE43 compliant.
  • The display can be push-button scaled to any range between -9999 to 9999, and reverse display action is possible.
  • The LCD backlight can be set to half or full intensity for easy viewing in low light conditions.
  • The display only requires 1.5 VDC, (75 Ω loop load), with the backlight turned off.
  • The input is HART transparent.
  • The front push-buttons can be disabled to prevent unauthorized adjustment.

1 - 3 of 3 Part Numbers
5531B
5531B
  • Input - 4-20 mA from Zone 0
5531B1
5531B1
  • Input - 4-20 mA from Safe & Zone 2
5531B2
5531B2
  • Input - 4-20 mA from Zone 0 & 20
1 - 3 of 3 Part Numbers

Specifications

Approvals & Certifications

  • ATEX 2014/34/EU
  • CE
  • EAC Ex TR-CU 012 / 2011
  • EAC TR CU 020/2011
  • Ex

Cable Entry

  • 0.2” to 0.3” (5 to 8 mm) - Cable Diameter
  • M16 x 1.5

Dimensions

  • 1.89” x 3.78” x 4.72” {(48 x 96 x 120 mm) (H x W x D)}

Display

  • 4-Digits up to ± 9999
  • LCD Display

Electrical Connectors

  • 26 to 14 AWG (0.13 to 2.08 mm²)

Environmental Protection

  • IP65

Humidity

  • < 95 % Relative Humidity

Input

  • < 1.5 V at 20 mA - Input Voltage Drop, without Backlight
  • < 10.5 V at 20 mA - Input Voltage Drop, with Full Backlight
  • 3.6-23 mA
  • NAMUR NE43

Mounting

  • Panel Mount

Output Noise

  • > 60 dB - Signal/Noise Ratio

Response Time

  • < 1 second

Span & Zero Effect

  • < ± 0.5 % of Span - EMC Immunity Influence

Storage Temperature

  • -10° to 60° C (14° to 140° F)

Supply Voltage

  • Input Loop Powered

Temperature Range

  • 20° to 28° C (68° to 82.4° F) - Calibration Temperature
  • -20° to 60° C (-4° to 140° F)

Update Time

  • 500 milliseconds

  • The 5531 indicator is powered by the 4 to 20 mA current loop and is easily scaled to display the correct process value.
  • Because it does not require separate power wiring, the 5531 is perfect for remote display of process loops.
  • The 5531B can be mounted in Ex Zone 1.
  • The 5531B1 Ex display includes the 8501 enclosure and can be mounted in Ex Zone 2 or 22 (gas or dust).
  • The 5531B2 includes the 8501 enclosure and can be mounted in Ex Zone 1, 2, 21 or 22 (gas or dust).
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more