Obsolete: Field-Adjustable Thermostats & Temperature Controllers
Brand: Parker HannifinMultitube® Field-Adjustable Thermostats and Temperature Controllers are used to monitor the temperature of the process tubes or observe the ambient temperature in chemical processing and refinery applications.
Each thermostat is a mechanically actuated on/off switch that controls the power to an electric tracer to achieve the desired process tube temperature.
The high and low temperatures are pre-set at the factory but are field adjustable and tamper-proof, in order to meet specific application requirements and to avoid unwanted modifications to required settings.
Features- Field-adjustable to accommodate diverse application conditions
- Tamper proof to eliminate unwanted or unauthorized alterations to desired temperature settings
- Monitors temperature of process tubes to ensure that low/high temperatures are maintained during media conveyance
Specifications
Brand
Bulb Length (inch)
- 5/8” to 2-1/4”
Bulb O.D. (inch)
- 1/8” to 3/8”
Bulb Type
- Typical 304 Stainless Steel or Fluid Filled Stem
Capillary Length (feet)
- Capillary Length Ranges from 6' to 10' Except for 4012-06105 Which Doesn't have A Capillary
Capillary Type
- Typical 304 Stainless Steel
Compatible Series
- Multitube® Electric Trace Bundles
Industry Standards
- NEMA 4X or NEMA 7
Maximum Working Temperature (°C)
- 60° - 265° C
Maximum Working Temperature (°F)
- 140° to 500° F
Minimum Working Temperature (°C)
- Minimum Working Temperature Ranges from -85° to -3° C, Depending on the Part Number.
Minimum Working Temperature (°F)
- Minimum Working Temperature Ranges from -125° F to +25° F, Depending on the Part Number.
Power (Amps)
- 20 or 22 Amps
Switch Type
- SPDT Snap Acting
Temperature Accuracy (°C)
- ± 1 % of Full Scale, Approximately 1.6° C
Temperature Accuracy (°F)
- ± 1 % of Full Scale, Approximately 3° F
Voltage (Vac)
- 125/250/480 or 125/140 Vac
- High-temperature gases, liquids or other process materials
- Low-temperature gases, liquids or other viscous materials