Brand: MicroMod Automation & ControlsThe 53SL6000 Micro-Mite is a highly versatile, cost-effective panel-mounted PID process controller that can provide a wide range of control loop applications, from basic to complex. Process information is presented clearly on the LED display and large pushbutton keys with tactile feedback make operation fast and easy. The Micro-Mite comes with all control functionality included in the base unit, from single PID to cascade and override control with math and logic operations. Additional I/O is easily added with plug-in modules.
Fully configurable through the easy-to-navigate front panel menus or PC configuration software, the Micro-Mite can be commissioned rapidly and then tuned using the Easy-Tune feature. Serial communication options ensure easy integration into a control system.
FeaturesSpecifications
Accuracy
- Analog Output: ± 0.2 %
Approvals & Certifications
- ISA S71.04 Airborne Contaminants G3 for 10-Years
Approvals & Certifications
- CE EN 61000-3, EN 61000-4 & EN 61010-1
- CSA Class I, Div. 2, Grade A, B, C, D
- FM
Communication
- RS-232
- RS-485
- USB
Consumption
- 20 W / 35 VA (with Modules)
Current
- On Load: ≤ 50 mA - Transmitter Supply
Environmental Protection
- Faceplate: NEMA 4
- Housing: NEMA 1
- IP10
- IP20
- IP64
- IP66
Execution Time
- Program Execution: 50 milliseconds
Flow Time
- Contact Recognitation: 50 milliseconds Min. - Digital Input
Frequency
- 0.5 Hz to 30 kHz
- 2.5 Hz to 100 kHz
- 8 Hz to 100 kHz
- Pulse Input: 0 to 100 kHz
Humidity
- 5 to 95 % Relative Humidity, Non-Condensing
Input
- 0-5 V, ± 5.3 V
- 0-83 mV, ± 83 mV
- 1-5 V
- Common Mode Rejection: 160 dB
- Common Mode Voltage: 250 Vrms
- Off: 0-1 Vdc - Digital Input
- On: 4-24 Vdc - Digital Input
- Signal Range: 0-20 mA
- Signal Range: 4-20 mA
Input Impedance
- 1,000 ohms - Digital Input
- 250 ohms
Measuring Error
- ≤ ± 0.2 % of Full Scale
- Input: ≤ ± 0.02 mA
Mounting
- Panel
Operating Temperature
- -5° to 50° C (23° to 122° F)
Operating Voltages
- 30 Vdc, Max.
Output
- 0-20 mA
- 100 mA - Max.
- 4-20 mA DC
- Open Contact (OFF): ≤ 1 mA Leakage - Digital Output
- Operating Current: 50 mA DC, Max.
- Switching Current: ≤ 5 A
- Switching Power: ≤ 1250 Vac
- Switching Power: ≤ 30 W at 250 Vdc
- Switching Voltage: ≤ 250 V
Output Impedence
- 0 to 750 ohms
Power Supply
- 120-240 Vac at 50/60 Hz - Transmitter Supply
- 93.5-276 Vac, 47 to 63 Hz
Pulse Range
- Pulse Width Duration: 5 µs
RTD Type
- Cu10 (0.00427)
- Cu100 (0.00427)
- Cu53 (0.00427)
- Ni100 (0.00672)
- Ni120 (0.00672)
- Pt100 (0.00385, 0.00392, & 0.00391)
Sample Rate
- Contact Recognitation Duration: 50 milliseconds - Digital Input
- Sampling Range: 300 milliseconds - Analog Input
Sensor, Probe Type
- B Thermocouple
- C Thermocouple
- D Thermocouple
- E Thermocouple
- F Thermocouple
- G Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- PL2 Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
- U Thermocouple
Shock
- Operation: 5 G, 1/2 Sine Wave, 36.09 feet (11 metres)
Storage Temperature
- -40° to 85° C (-40° to 185° F)
Time Constant
- Filter: 25 milliseconds - Analog Input
Update Time
- 50 milliseconds - Digital Input
Vibration
- 0.3 G, 14 to 200 Hz
- 0.76 mm, 5 to 14 Hz
Voltage
- 25 V, ± 1 V - Digital Input
Voltage Drop