LC-4 Flow Monitor with Level Discriminator

Brand: Ingram Products Inc

The LC-4 Flow Monitor provides a stand alone solution for liquid level flow monitoring, requiring only 2 wire connections to an existing Duplex controller.

Pump run verification ensures pumps operate within specification.

The Base unit supports Flow Monitoring, Level Detection and Run Verification with outputs supporting status indicators and a 5 Level Discriminator.

Additional status information and Bubbler controller output capabilities may be added using the APB-22MRDL expansion unit.

To connect to a Modbus network an APB-EXPMC adaptor will be required.

The optional Windows based LC Config software requires either an APB-EXPMC Modbus adaptor or a APB-DUSB programming cable.

The LC-4 is UL508a compliant when used with Class II power. Slave UL508a compliant relays should be used when switching voltages greater than 48 Vdc.

The LC Config application software provides an Windows based graphical interface for the LC product family. Using an Modbus interface the program allows:
  • Monitoring the state of all control functions
  • Configuring of all operating parameters
  • Project management tools
  • Saving and loading configurations to disk
  • Printing configuration reports
  • Operating remote units in Simulation Mode
NOTE: The software supports an 'offline' mode allowing the capabilities of the LC family to be evaluated with no hardware connected. To connect to the LC controller a APB-DUSB adaptor is required.

1 - 1 of 1 Part Numbers
ALC-4
ALC-4
Flow Monitor with Level Discriminator
1 - 1 of 1 Part Numbers

Specifications

Controller & I/O Expander

  • Power: 24 Vdc, 100 mA
  • Size: 126 mm x 90 mm x 58.5 mm
  • Environment: IEC68-2
  • EMC: IEC801-3

Inputs

  • 24 Vdc
  • 0-10 Vdc/4-20 mA (Level Detect)

Outputs

  • NO Relay (0-240 Vac, 10 Amp Resistive)
  • Optional (Contact Factory): NPN (Sink) - 24 Vdc, 2 Amp/ PNP (Source) - 24 Vdc, 2 Amp

Level Detection

  • 6 Levels: Zero Lockout, Off, Low, Mid, High, Purge
  • Specified in Inches, Feet or Meters

Run Verification

  • Aux Contact, Current, Phase Error

Flow Monitoring

  • Flow in Gallons, Imp. Gallons & Liters
  • Reported in Seconds, Minutes or Hours