Yodify Product Library
Instantly add the ITC-7X-TXX Isolated Thermocouple Signal Conditioner/Converter and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
ITC-7X-TXX Isolated Thermocouple Signal Conditioner/Converter
Brand: Pribusin, IncThe ITC-7X-TXX provides high isolation from Input to Output to Power in a small, easy to install package. The universal DIN rail mount often makes it possible to install the ITC-7X-TXX right next to other instruments that it is to be wired to. The many different Thermocouple types and ranges as well as output configurations allow it to be used in a great variety of temperature measurement applications.
The high output drive (1000 Ohms @ 4-20 mA) allows the ITC-7X-TXX to drive several other instruments directly from its output.
Upscale protection is standard on all units unless downscale protection is specified.
Features- High Input-Output-Power Isolation (1500Vac Test).
- Small Size - Fits on Terminal Block Rail.
- Industry Standard T/C Types: J, K, E, T, S, R.
- Special Ranges & Types Available.
- Cold Junction Compensated.
- Industry Standard Output: 4-20 mA, 1-5 Vdc, and more.
- High Output Drive on Current Outputs (1000 Ohms for 4-20 mA output).
- Power: 24 Vdc, 80 mA.
- High Noise Rejection.
- CSA and NRTL Approved (LR 51078).
Specifications
Brand
Accuracy, Linearity
- ± 0.2 % Max., ± 0.1 % Typical (Linear with Material)
Common Mode Rejection
- 120 dB @ 60 Hz
Coupling Capacitance
- Input-Output-Power = 20 PF
Input Impedance
- 1 Megaohm Min.
Isolation
- Input to Output to Power 1500 Vac (Test)
Loop Drive
- Maximum
Loop Resistance Change Effects
- -0.03 % Per 100 ohms Change (4-20 mA Only) Calibrated at 250 ohms
Operating Temperature
- -40° to +50° C
Power
- 24 Vdc (19-29 Vdc) @ 80 mA (160 mA if Two Wire Supply Used)
Response Time
- 100 milliseconds to 63 % of Final Value, 500 milliseconds to 99 % of Final Value
Temperature Effects
- ± 0.025 % Per °C
Zero Drift
- 1 UV/mV Offset Per °C or 1 uV/°C, whichever is Higher