Yodify Product Library
Add the RM140W Overfill Protection Rack Monitor to your store or catalog  
Book Your Demo and See How
or create your store

RM140W Overfill Protection Rack Monitor

Brand: OPW Engineered Systems

Overfill protection and grounding monitor for truck or rail loading in petro-chemical applications.

Built to function with all probes designed to the API code: API RP 1004 and the EU Standard EN13922, the RM140W Series is the world’s most flexible and adaptable monitor.

The RM140W provides a fail-safe, state-of-the-art overfill protection and grounding monitoring system that is compatible with all commonly used overfill protection and grounding systems.
Features
  • Automatic Sensing of 2-Wire/Thermistor or 5-Wire Overfill Systems, No Manual Switching or Inspection Required
  • Supports Up to 8 2-Wire/Thermistor Probes and Up to 12 5-Wire Probes
  • High-output Display Visible in Direct Sunlight, Provides Flexibility for Indoor/Outdoor Use
  • Coded Wireless By-pass Key for Secure and Reliable Operation
  • Self-test at Start Up/Continuous Self-monitoring, Ensures Safety Throughout the Loading Process
  • Separate Grounding and Overfill Control Outputs
  • Compact and Functional Design is Easy to Install, Perfect for Tight Spaces or Crowded Work Areas
  • Global Electronic Compatibility, Able to Operate on Almost Any Electric Service
  • RM140W is Directly Compatible with PD100 Probe Doctor as a “Plug-in Replacement”
  • Rack Monitor Electronics Mounted in a 100mm / 4” Deep Flameproof Enclosure.

1 - 12 of 13 Part Numbers
5542
5542
Fuse 5A @ 250VAC anti-surge
6959
6959
Display PCB Assembly
6983
6983
RM140W Bypass Fob
6985
6985
RM100 Safety Ground Harness
6987
6987
Fuse 400mA, 250VAC anti-surge, 1500A Breaking Capacity
7100 Series
7100 Series
Civacon Optic Plug
7300 Series
7300 Series
Civacon 6-Channel Termistor Plug
7500 Series
7500 Series
Civacon Junction Box
7720-7720
7720-7720
Civacon Earth Clamp with Straight Cable
RM100-3
RM100-3
RM100 Aluminium Safety Barrier
RM100-4
RM100-4
RM100 Polycarbonate Terminal Cover
RM100-5K
RM100-5K
RM100 PCB Assembly Complete Kit - RM100-5 + 6959 Display
1 - 12 of 13 Part Numbers

Specifications

Power

  • 240 V Operation
  • 110 V Operation

Minimum Input Voltage

  • 185 Vac
  • 85 Vac

Maximum Input Voltage

  • 275 Vac
  • 135 Vac

In-rush Current

  • 2.2A
  • 2.3A

Maximum Current

  • 400 mA

Normal Power Consumption

  • 8.6W (No probe)
  • 20W (8x 2-wire probes)

Mains Power Fuse Rating

  • 250 V, 400 mA anti-surge
  • 1500 A Breaking Capacity

Nominal Voltage

  • 10.5 V
  • 13.02 V Max

Nominal Current

  • 116 mA
  • 121 mA Max

Relay Outputs

  • 1 x Overfill Monitoring Relay
  • 1 x Ground Monitoring Relay

Relay Contacts

  • Common
  • Normally Open
  • Normally Closed

Maximum Contact Voltage

  • 250 Vac

Maximum Contact Load

  • 5A (resistive)
  • 2.5A (inductive)

Relay Fuse Rating

  • 250 V @ 5A anti-surge

Certification and Compliance

  • Explosion-proof enclosure for Group II, Zone 1, Ex d [ia]
  • IECEx TSA 05.0049X
  • Ex d [ia] IIB T6 (Tamb=60°C) IP66
  • CE 2813 Ex II 2 (1) G Ex db [ia Ga] IIB T6 Gb (-20° C ≤ Tamb ≤ +70° C) IP66
  • ATEX Directive 2014/34/EU EMC Directive 2014/30/EU RoHS 3 2015/863
  • FM Approved for US and Canada.
  • Explosion-proof with I.S. Outputs Intrinsically Safe Sécurité Intrinsèque Exia Class I, Div. 1, Group C & D, T6 Ta = -25° to 60° C