Yodify Product Library
Instantly add the Bus-Carrier Yokogawa ALF111 Version Series 9419 and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Bus-Carrier Yokogawa ALF111 Version Series 9419
Brand: R. STAHL AG9419 series bus carriers allow 9412 series fieldbus power supplies for FF H1 segments to be installed quickly and securely. Variants are available for eight segments with simplex supply and for four or eight segments with redundant supply.
Connectors are integrated in this version to connect the AKB336 system cable for Yokogawa ALF111 host assemblies.
Features- Time- and cost-saving installation on DIN rails or mounting plates
- High availability thanks to redundant auxiliary power supply with signaling contact and separate signaling contact for segment errors
- Special slot for 9415 series DCM for online transmission of physical layer diagnostics
1 - 3 of 3 Part Numbers
221454
Time- and cost-saving installation on DIN rails or mounting plates
High availability thanks to redundant auxiliary power supply with signalling contact and separate signalling contact for segment errors
Special slot for 9415 series DCM for online transmission of physical layer diagnostics
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C
- Ambient temperature max. - +70 °C
- Ambient temperature min. - -20 °C
- Relative humidity max. - < 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
Auxiliary power
- Nominal voltage - 24 V DC
- Redundant supply - yes, diode-decoupled
Electrical Data
- Error detection Diagnostic - Contact "Dia" (35 V /100 mA) closed in good conditions
- Error detection Power Fail (pri / red) - Contact "PF" (35 V /100 mA) closed in good conditions
- Number of segments - 8
- Trunk supply - simplex
Explosion Protection
- Application range (zones) - 2
- ATEX gas certificate - BVS 09 ATEX E 100 X
- Certificate EAC - TS RU S-DE.GB04.B.00081
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), EAC (Sertium), IECEx (BVS), India (PESO), USA (FM)
- Gas explosion protection ATEX - II 3 G Ex nA nC IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC IIC T4 Gc
- IECEX gas certificate - IECEx BVS 09.0042X
General
- Description - Yokogawa bus-Carrier for 8 segments, simplex
- Functional Description - 9419 series bus carriers allow 9412 series fieldbus power supplies for FF H1 segments to be installed quickly and securely. Variants are available for eight segments with simplex supply and for four or eight segments with redundant supply. Connectors are integrated in this version to connect the AKB336 system cable for Yokogawa ALF111 host assemblies.
- Highlights - Time- and cost-saving installation on DIN rails or mounting plates High availability thanks to redundant auxiliary power supply with signalling contact and separate signalling contact for segment errors Special slot for 9415 series DCM for online transmission of physical layer diagnostics
- Product Description - ISbus fieldbus technology Yokogawa bus-Carrier
- Product Type - 9419/08F-YO1-01A5
- Product Variant - Yokogawa bus-Carrier
- Title Product Variant Technical Data - 9419/08F-YO1-01A5 8SEG YOKO-bus-carrier
- WebCode - 9419B
Mechanical Data
- Connection DCM - via ribbon cable using plug connectors
- Connection Host / red. host - via system plug for Yokogawa AKB336 system cable
- Connection Shield - via integrated shield bus or to terminal connections "S"
- Connection Trunk - to the terminals of the bus-Carrier or of the fieldbus power supply
- Degree of protection IP (IEC 60529) - IP00
- Number of slots - 8 FPS + 1 DCM
- Terminal degree of protection (IP) - IP20
- Weight - 0.600 kg
Mounting / Installation
- Connection - to Yokogawa ALF111 FF H1 hosts
221455
Time- and cost-saving installation on DIN rails or mounting plates
High availability thanks to redundant auxiliary power supply with signalling contact and separate signalling contact for segment errors
Special slot for 9415 series DCM for online transmission of physical layer diagnostics
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C
- Ambient temperature max. - +70 °C
- Ambient temperature min. - -20 °C
- Relative humidity max. - < 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
Auxiliary power
- Nominal voltage - 24 V DC
- Redundant supply - yes, diode-decoupled
Electrical Data
- Error detection Diagnostic - Contact "Dia" (35 V /100 mA) closed in good conditions
- Error detection Power Fail (pri / red) - Contact "PF" (35 V /100 mA) closed in good conditions
- Number of segments - 4
- Trunk supply - redundant
Explosion Protection
- Application range (zones) - 2
- ATEX gas certificate - BVS 09 ATEX E 100 X
- Certificate EAC - TS RU S-DE.GB04.B.00081
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), EAC (Sertium), IECEx (BVS), India (PESO), USA (FM)
- Gas explosion protection ATEX - II 3 G Ex nA nC IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC IIC T4 Gc
- IECEX gas certificate - IECEx BVS 09.0042X
General
- Description - Yokogawa bus-Carrier for 4 segments, redundant
- Functional Description - 9419 series bus carriers allow 9412 series fieldbus power supplies for FF H1 segments to be installed quickly and securely. Variants are available for eight segments with simplex supply and for four or eight segments with redundant supply. Connectors are integrated in this version to connect the AKB336 system cable for Yokogawa ALF111 host assemblies.
- Highlights - Time- and cost-saving installation on DIN rails or mounting plates High availability thanks to redundant auxiliary power supply with signalling contact and separate signalling contact for segment errors Special slot for 9415 series DCM for online transmission of physical layer diagnostics
- Product Description - ISbus fieldbus technology Yokogawa bus-Carrier
- Product Type - 9419/04R-YO1-02A5
- Product Variant - Yokogawa bus-Carrier
- Title Product Variant Technical Data - 9419/04R-YO1-02A5 4SEG YOKO-bus-carrier
- WebCode - 9419B
Mechanical Data
- Connection DCM - via ribbon cable using plug connectors
- Connection Host / red. host - via system plug for Yokogawa AKB336 system cable
- Connection Shield - via integrated shield bus or to terminal connections "S"
- Connection Trunk - to the terminals of the bus-Carrier or of the fieldbus power supply
- Degree of protection IP (IEC 60529) - IP00
- Number of slots - 8 FPS + 1 DCM
- Terminal degree of protection (IP) - IP20
- Weight - 0.600 kg
Mounting / Installation
- Connection - to Yokogawa ALF111 FF H1 hosts
221456
Time- and cost-saving installation on DIN rails or mounting plates
High availability thanks to redundant auxiliary power supply with signalling contact and separate signalling contact for segment errors
Special slot for 9415 series DCM for online transmission of physical layer diagnostics
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C
- Ambient temperature max. - +70 °C
- Ambient temperature min. - -20 °C
- Relative humidity max. - < 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
Auxiliary power
- Nominal voltage - 24 V DC
- Redundant supply - yes, diode-decoupled
Electrical Data
- Error detection Diagnostic - Contact "Dia" (35 V /100 mA) closed in good conditions
- Error detection Power Fail (pri / red) - Contact "PF" (35 V /100 mA) closed in good conditions
- Number of segments - 8
- Trunk supply - redundant
Explosion Protection
- Application range (zones) - 2
- ATEX gas certificate - BVS 09 ATEX E 100 X
- Certificate EAC - TS RU S-DE.GB04.B.00081
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), EAC (Sertium), IECEx (BVS), India (PESO), USA (FM)
- Gas explosion protection ATEX - II 3 G Ex nA nC IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA nC IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA nC IIC T4 Gc
- IECEX gas certificate - IECEx BVS 09.0042X
General
- Description - Yokogawa bus-Carrier for 8 segments, redundant
- Functional Description - 9419 series bus carriers allow 9412 series fieldbus power supplies for FF H1 segments to be installed quickly and securely. Variants are available for eight segments with simplex supply and for four or eight segments with redundant supply. Connectors are integrated in this version to connect the AKB336 system cable for Yokogawa ALF111 host assemblies.
- Highlights - Time- and cost-saving installation on DIN rails or mounting plates High availability thanks to redundant auxiliary power supply with signalling contact and separate signalling contact for segment errors Special slot for 9415 series DCM for online transmission of physical layer diagnostics
- Product Description - ISbus fieldbus technology Yokogawa bus-Carrier
- Product Type - 9419/08R-YO1-02A5
- Product Variant - Yokogawa bus-Carrier
- Title Product Variant Technical Data - 9419/08R-YO1-02A5 8SEG YOKO-bus-carrier
- WebCode - 9419B
Mechanical Data
- Connection DCM - via ribbon cable using plug connectors
- Connection Host / red. host - via system plug for Yokogawa AKB336 system cable
- Connection Shield - via integrated shield bus or to terminal connections "S"
- Connection Trunk - to the terminals of the bus-Carrier or of the fieldbus power supply
- Degree of protection IP (IEC 60529) - IP00
- Number of slots - 16 FPS + 1 DCM
- Terminal degree of protection (IP) - IP20
- Weight - 1.200 kg
Mounting / Installation
- Connection - to Yokogawa ALF111 FF H1 hosts
1 - 3 of 3 Part Numbers