Yodify Product Library
Instantly add the IDM+ Multi-Function Power System Monitor and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
IDM+ Multi-Function Power System Monitor
Brand: Qualitrol CompanyA multi-function substation monitor offering advanced fault recording and long duration disturbance monitoring with options of phasor measurement in compliance to the IEEE C37.118 2005 specification; the most accurate fault location available using traveling wave methodology and Class A power quality in compliance with IEC 61000-4-30 Class A (Edition 2.0).
Features- Utilizes the most accurate measurement chain including sampling rate of 512 samples per cycle and Analog resolution of 20 bits on current channels
- Option of travelling wave fault location with accuracy of ±60 meters (200 feet)
- Full solid state device and high reliability – all data stored on CompactFlash
- Advanced iQ+ client-server multifunction master station software
- Achieve cost effective, integrated, automated substation integration with IEC 61850
- Advanced HMI provision
- Flexible sampling rates for fault and disturbance monitoring
Specifications
Brand
Accuracy
- 0.1 % of Full Scale (Analog Channels)
- 100 Nanoseconds when Locked to Internal GPS Module
Alarm Relays
- 4 Relays Per 9 or 18 Analog Channel Block
Analog Channel Current Range
- 10 A, 20 A, 50 A & 100 A Selectable
Analog Channel Voltage Range
- 140 V, 170 V, 480 V & 800 V Selectable
Analog Channels
- 9, 18 or 36 (In Two Blocks of 18) - Can be Voltage, Current or DC
Clock
- Internal Real Time Clock Synchronized by GPS Module, IRIG-B (with 1 pps), IRIG-J
Communication
- Ethernet Ports: 2 Provided - RJ45 for Local Connection at the Front, RJ45 (with Option for Fiber) on the Rear
- Serial Ports: 3 x RS-232 Provided (One Front Panel, Two on Rear), 1 x RS-485 on Rear Panel
- USB
Data Storage
- Minimum 4 GB CompactFlash with Option for 8 GB or 16 GB
Digital Channels
- 32, 64 or 128 (In Two Blocks of 64) - Wide Ranging Input from 35-250 Vdc (18-250 Vdc Optional), Selectable De-bounce
Front Panel
- LCD Display with 7 Button Keypad
- LED Indicators
Immunity
- Storage: Conforms to Relevant Specifications for Monitoring/Control Equipment in HV SubStations
Operating Temperature
- -5° to 50° C (23° to 122° F)
Power
- 40 VA
Power Supply
- 35-650 Vdc
- 88-300 Vac/dc
Resolution
- 16-bits on Voltage & DC Analog Channels
- 20-bits on Current Analog Channels
Sample Rate
- 25.6 kHz, 12.8 kHz, 6.4 kHz, 3.2 kHz & 1.6 kHz Selectable (50 Hz)
- 30.7 kHz, 15.3 kHz, 7.6 kHz, 3.8 kHz & 1.9 kHz Selectable (60 Hz)
Storage Temperature
- -30° to 70° C (-22° to 158° F)