Yodify Product Library
Instantly add the Operator Station MT-638 and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

Operator Station MT-638

Brand: R. STAHL AG

The MT-638-DVI3 HMI series includes KVM systems for hazardous zones 2 and 22. 

The systems are rugged, i.e. extremely robust: IP66, shock, vibration and seawater-proof and suitable for temperatures ranging from -40 to +65 °C. As an option, the 15" display with a resolution of 1024 x 768 pixels is also available as a sunlight-readable version. 

The display and additional function keys are well-protected underneath a chemically hardened and non-glare glass screen. 

Further options include a camera, a Bluetooth antenna and a projected capacitive touchscreen with multi-touch function. 

Depending on the distance to be crossed, choose from the following types of data transmission technology: via copper cable up to 150 m, via multimode fibre optic up to 550 m or via single mode fibre optic up to 10 km.
Features
  • KVM System, 15" display, optional sunlight-readable 1200 cd/m²
  • Rugged design: IP66, shock, vibration and seawater-proof, temperature range -40 °C to +65 °C
  • Compact, lightweight HMI design < 18 kg / 40 lbs

1 - 1 of 1 Part Numbers
MT638A
MT638A
R. STAHL KVM Systems Series 600 Device Platform SHARK
KVM System, 15" display, optional sunlight-readable 1200 cd/m²

Rugged design: IP66, shock, vibration and seawater-proof, temperature range -40 °C to +65 °C

Compact, lightweight HMI design < 18 kg / 40 lbs

Ambient Conditions

  • Ambient temperature operation - -10 °C … +65 °C
  • Ambient temperature operation 1 - -40 °C … +65 °C with heater
  • Cold start temperature - -10 °C or -40 °C
  • Corrosion resistance - Salt water 5 % NaCl / +20 °C / 2 h 93 % r.H. / +40 °C / 168 h ISA-S71.04-1985, severity level G3
  • Damp heat - +55 °C / 95 %
  • Damp heat cyclic - +55 °C (±2 °C) ≥ 95 % Humidity location class B
  • Heat dissipation - Via heat pipes and cooling fins
  • Heater operation - Automatic
  • Shock - 18 Shocks 25 g / 6 ms Axis X, Y, Z
  • Storage temperature - -40 °C … +70 °C
  • Temperature note 1 - The cold-start temperature depends on the "outdoor installation" (with / without heater).
  • Temperature note 2 - Cold-start temperature: If the HMI device is switched on at temperatures below -10 °C, the electronics and the display will need a certain warm-up time before everything works smoothly and the display starts to be legible. Depending on how low the temperature is, this process may last up to 3 hours.
  • Vibration sinus - 5 to 13.2 Hz: ±1 mm 13.2 to 100 Hz: ±0.7 g Change cycle 1 oct/min Axis X, Y, Z
  • Vibration sinus 1 - 5 to 58 Hz: ±0.075 mm 58 to 500 Hz: ±1 g Change cycle 1 oct/min Axis X, Y, Z
  • Vibration sinus 2 - 5 to 1000 Hz 5 g

Components

  • Keyboard - optional, attached keyboard and pointing device (trackball, or joystick (Ex ia)) or desktop keyboard with 105 keys (Ex ia) and optical desktop mouse (Ex ia)

Display

  • Backlight - LED Technology
  • Backlight service life - 70 000 h at +25 °C
  • Display brightness - TFT 450 cd/m² SR 1200 cd/m²
  • Display contrast - TFT 500:1 SR 600:1
  • Display dimensions - 4:3
  • Display resolution - XGA
  • Display size centimetres - 38
  • Display size inch - 15
  • Display version - TFT colour display or sunlight-readable display
  • Display version 2 - 16.7 million colours
  • Function keys - 8 of which 2 brightness keys
  • Total pixels - 1024 x 768
  • Touch screen - optional, projected, capacitive (PCAP), multi-touch
  • Touch screen technology - Glass touch

Electrical Data

  • Bluetooth - optional
  • Connection compartment - Power supply direct in integrated Ex-e connection box
  • Connections - Via plug-in screw terminals, green
  • Data cable - CAT7 installation cable AWG23
  • Data cable length - max. 150 m
  • Ethernet / Data - 1x 100/1000Base-TX (Ex nA)
  • Frequency range - 50 - 60 Hz
  • Front camera - optional, 5 megapixel, in-built
  • Further connections - 12 / 24 V DC output 2 x fan
  • Interface Audio - 1 x Audio line out (Ex nA)
  • Interface medium - CAT7 Data transmission
  • Interface reader - 1 x reader / barcode reader interface (Ex i)
  • Interface Serial - 1 x RS-232 / RS-422 / RS-485 (Ex nA)
  • Interface USB - 3 x USB (Ex ia) 1 x USB (Ex nA)
  • Language support - User menu: English
  • Max. input voltage Um - 250 VAC
  • Operating system - independent
  • Optional interface 1 - Bluetooth
  • Plug version USB - USB-A connector
  • Power consumption AC 1 - 0.6 A at 230 VAC (0.8 A when heater is in use)
  • Power consumption AC 2 - 1.1 A at 110 VAC (1.7 A when heater is in use)
  • Power consumption DC - 4.6 A at 24 VDC (6.9 A when heater is in use)
  • Protection fuse AC - 5 A
  • Protection fuse DC - 12 A
  • Rated operational power - typically 100 W / max. 150 W (typically 340 BTU / max. 510 BTU)
  • Rated operational voltage AC - 230 V
  • Rated operational voltage DC - 24 V
  • Status LED - LEDs - on / off (green) - voltage applied to supply line / power supply OK (orange) - heater on (blue)
  • Transfer technology - KVM-DVI3
  • Voltage range AC - 100 - 240 V
  • Voltage range DC - 20 - 30 V
  • Wiring - Flexible conductors 0.2 to 2.5 mm² (AWG24 to AWG14) Rigid conductors 0.2 to 2.5 mm² (AWG24 to AWG14)

Explosion Protection

  • Application range (divisions) - Class I, Zone 2 Class I, Division 2 Class II, Division 2 Class III
  • Application range (zones) - 2 22
  • Certification ATEX - BVS 14 ATEX E 134 X
  • Certification CEC - FM 16 CA 0141 X
  • Certification CNEX - CNEx17.2233X
  • Certification EAC - TC RU C-DE.ME92.B.00843
  • Certification IECEx - IECEx BVS 14.0116X
  • Certification NEC - FM 16 US 0278 X
  • Certifications - ATEX, IECEx, EAC, NEC, CEC, CNEX
  • Dust explosion protection ATEX - II 3(1) D Ex tc [ia op is Da] IIIC T115°C Dc
  • Dust explosion protection CEC - Zone 22, Ex tc [ia Da] IIIC T115°C Dc Class II, Div. 2 Groups E, F, G T4 Class III
  • Dust explosion protection CNEX - Ex tc [ia op is Da] IIIC T115°C Dc
  • Dust explosion protection EAC - Ex tb [ia op is Da] IIIC T115°C Dc X
  • Dust explosion protection IECEx - Ex tc [ia op is Da] IIIC T115°C Dc
  • Dust explosion protection NEC - Zone 22, AEx tc [ia op is Da] IIIC T115°C Dc Class II, Div. 2 Groups F, G T4 Class III
  • Gas explosion protection ATEX - II 3(1) G Ex nA nR [ia op is Ga] IIC T4 Gc
  • Gas explosion protection CEC - Ex nA nR [ia Ga] IIC T4 Gc Class I, Div. 2 Groups A, B, C, D, T4
  • Gas explosion protection CNEX - Ex ec nR [ia op is Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2Ex nA nR [ia op is Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex ec nR [ia op is Ga] IIC T4 Gc
  • Gas explosion protection NEC - Class I, Zone 2 AEx nA nR [ia op is Ga] IIC T4 Gc Class I, Div. 2 Groups A, B, C, D T4

General

  • Functional Description - The MT-638-DVI3 HMI series includes KVM systems for hazardous zones 2 and 22. The systems are rugged, i.e. extremely robust: IP66, shock, vibration and seawater-proof and suitable for temperatures ranging from -40 to +65 °C. As an option, the 15" display with a resolution of 1024 x 768 pixels is also available as a sunlight-readable version. The display and additional function keys are well-protected underneath a chemically hardened and non-glare glass screen. Further options include a camera, a Bluetooth antenna and a projected capacitive touchscreen with multi-touch function. Data is transmitted via CAT7 copper cable up to 150 m.
  • Highlights - KVM System, 15" display, optional sunlight-readable 1200 cd/m² Rugged design: IP66, shock, vibration and seawater-proof, temperature range -40 °C to +65 °C Compact, lightweight HMI design < 18 kg / 40 lbs Data transmission via CAT7 copper cable up to 150 m
  • HMI type - Operator station
  • Product description - 15" KVM systems
  • Product Description - KVM Systems SERIES 600 Device platform SHARK
  • Product Type - MT-638-DVI3-1TX
  • Series - Product Series MT-638
  • Technology - Remote HMI KVM
  • WebCode - MT638A

Mechanical Data

  • Cable gland cable diameter range (1) - M16 = 4 … 8 mm / M20 = 10 … 14 mm / M25 = 14 … 18 mm
  • Cable gland number (1) - 3 x M16, 3 x M20, 2 x M25
  • Cable gland number (2) - 3 x M16, 3 x M20
  • Cable gland thread size (1) - M16 x 1.5 / M20 x 1.5 / M25 x 1.5
  • Cable gland thread size (2) - M16 x 1.5 / M20 x 1.5
  • Cable gland type (1) - HSK-MZ-Ex
  • Cable gland type (2) - Screw plug
  • Cable gland wrench size (1) - M16 = SW 19 / M20 = SW 22 / M25 = SW 30
  • Cut-out - No panel mount
  • Dimensions (WxHxD) (1) - 380 mm x 394 mm x 137 mm (+52 mm cable entries)
  • Dimensions (WxHxD) (2) - 380 mm x 394 mm x 212 mm
  • Enclosure / Design (1) - VESA 200 Standard
  • Enclosure / Design (2) - VESA 200 Top Connect
  • Ingress protection - IP66
  • IP enclosure back - IP66
  • IP enclosure front - IP66
  • Material back - Seawater-resistant powder coated aluminum
  • Material front - Seawater resistant and coated aluminium, hardened glass
  • Mounting position - any
  • Weight - 18 kg

Mounting / Installation

  • Enclosure design - VESA 200 Standard, VESA 200 Top Connect
  • Enclosure type - Rugged Panel Design (RP)
  • Mounting option - Yoke, handle and feet, sun-shade, panel mounting (with xx8 Mounting-Kit)
  • Mounting type - when switched on: a fixed device (stationary, non-portable equipment)
1 - 1 of 1 Part Numbers
Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team