EF-x2000-B Bleed Airflow Measurement with Temperature and Alarm Capability

Brand: EBTRON, Inc

The EF-x2000-B is a unique measurement device that can detect very small pressure differentials (as low as 0.0002” H2O) between two adjacent spaces by sensing the airflow rate induced by the pressure gradient. 

The EF-x2000-B can be used to determine the airflow rate across fixed openings when a reference airflow rate is provided.
Features
  • Thermal Dispersion Technology
  • Bi‐directional Airflow Measurement
  • Detect ΔP as low as 0.0002″ H₂0
  • Airflow (or ΔP) and Status Alarm
  • Temperature Output Capability
  • Analog and RS‐485 Output Models
  • Dry Contact Relay
  • 1/2″ NPT Female Pipe Connections
  • Remote Transmitter with LCD Display
  • 3‐year Warranty

1 - 1 of 1 Part Numbers
EF-x2000-B
EF-x2000-B
EBTRON Bleed Airflow Measurement with Temperature and Alarm Capability
The EF-x2000-B is a unique measurement device that can detect very small pressure differentials (as low as 0.0002” H2O) between two adjacent spaces by sensing the airflow rate induced by the pressure gradient. The EF-x2000-B can be used to determine the airflow rate across fixed openings when a reference airflow rate is provided.
1 - 1 of 1 Part Numbers

Specifications

Brand

Probe and Sensor Node Configurations

  • 1 Bi-Directional, Dual 1/2” NPT Female Bleed Sensor Housing

Certifications & Approvals

  • FCC
  • RoHS
  • cULus

Temperature Range

  • Transmitter: -20° to 120° F (-28.9° to 48.9° C)
  • Sensor: -3,000 to 3,000 fpm (-15.24 to 15.24 m/s) 0° to 160° F (-17.8° to 71.1° C)
  • Sensor: -2,000 to 2,000 fpm (-10.16 to 10.16 m/s) -20° to 160° F (-28.9° to 71.1° C)

Humidity

  • Probes: 0 to 100 %
  • Transmitter: 5 to 95 %

Material of Construction

  • Sensor Potting: Waterproof Marine Epoxy
  • Sensing Node Housing: Glass-filled Polypropylene

Accuracy

  • Temperature Measurement: ± 0.15° F (0.08° C) to NIST-traceable Temperature Standards
  • Airflow Measurement: ± 2 % of Reading to NIST-traceable Airflow Standards

Probe to Transmitter Cable

  • Connecting Plug: 0.60” (15.24 mm) Nominal Diameter
  • Standard Lengths: 10, 25 and 50 ft. (3.1, 7.6 and 15.2 m)
  • Type: FEP Jacket, Plenum Rated CMP/CL2P, UL/cUL Listed, -67° to 302° F (-55° to 150° C), UV Tolerant

Power Requirement

  • Transmitter: 24 Vac (22.8-26.4 Under Load) @ 8 V-A

Alarm

  • Airflow/Pressure: Low and/or High User Defined Set Point Alarm
  • System Status: Sensor Diagnostic System Trouble Indication

  • Ultra-low Differential Pressure Detection
  • Parking Garage Pressurization
  • Construction Zone Contaminant Containment
  • Stairwell Pressurization
  • Relief and Exhaust Damper Control
  • Airflow across a Louver or other Fixed Opening