9116B Universal Converter

Brand: PR Electronics

  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • Supply for 2-wire transmitters
  • Active / passive mA output and relay output
  • Can be supplied separately or installed on power rail, PR type 9400
  • SIL 2-certified via Full Assessment
Features
  • Configuration and monitoring by way of detachable display front (PR 45xx); process calibration, signal and relay simulation.
  • Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
  • Copying of the configuration from one device to others of the same type via PR 45xx.
  • Reduced Uo Ex data < 8.3 V for active input signals.
  • TC inputs with internal CJC or external CJC for higher accuracy.
  • Active / passive mA output via the same two terminals.
  • 1 green and 1 red front LED indicate operation status and malfunction. 1 yellow LED indicates relay status.
  • 2.6 kVAC galvanic isolation between input, output and supply.

1 - 2 of 2 Part Numbers
9116B1
9116B1
  • Maximum Loop Voltage - 28 Vdc
9116B2
9116B2
  • Maximum Loop Voltage - 21.4 Vdc
1 - 2 of 2 Part Numbers

Specifications

Accuracy

  • ± 0.1 %

Approvals & Certifications

  • ATEX 2014/34/EU KEMA 10-ATEX-0053 X
  • CCOE P337349 / 4
  • DNV Marine Standard F. Certificate No. 2.4
  • EAC Ex TR-CU 012 / 2011 RU C-DK.GB08.V.00410
  • EAC TR CU 020/2011
  • EMC 2014/30/EU
  • FM 3038267-C
  • IECEx KM 10.0022X
  • INMETRO NCC 12.1309 X
  • LVD 2014/35/EU
  • SIL 2 Certified & Fully Assessed Accessory to IEC 61508
  • UL 61010-1

Calibration

  • 20° to 28° C (68° to 82° F)

Environmental Protection

  • IP20

Humidity

  • < 95 % Relative Humidity, Non-Condensing

Load

  • ≤ 600 ohms

Maximum Current

  • 0.3 Adc
  • 0.5 A AC

Maximum Voltage

  • 110 Vdc
  • 125 Vac

Output

  • 0-20 mA

Response Time

  • 0.4 to 60 seconds mA/V Input Programmable
  • 1 to 60 seconds Temperature Input Programmable (0 to 90 %, 100 to 10 %)

RTD Type

  • Ni100
  • Ni1000
  • Ni120
  • Ni50
  • Pt10
  • Pt100
  • Pt1000
  • Pt20
  • Pt200
  • Pt250
  • Pt300
  • Pt400
  • Pt50
  • Pt500

Storage Temperature

  • -20° to 85° C (-4° to 185° F)

Supply Voltage

  • 19.2-31.2 Vdc

Temperature Range

  • -20° to 60° C (-4° to 140° F)

Vibration

  • ± 0.7 G, 13.2 to 100 Hz
  • ± 1 mm, 2 to 13.2 Hz

  • 9116B can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
  • Conversion and scaling of temperature, voltage, potentiometer and linear resistance signals.
  • Power supply and signal isolator for 2-wire transmitters.
  • Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
  • The 9116 has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
  • Suitable for the use in systems up to Performance Level “d” according to ISO-13849.

Documentation