Yodify Product Library
Instantly add the AF-600 FP - Fan and Pump Drives and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

AF-600 FP - Fan and Pump Drives

Brand: General Electric

The AF-600 FP Fan and Pump Drive is a powerful, flexible and easy to use AC variable torque drive. 

The drive is available in its standard configuration that includes LCD keypad display that can be remote mounted, DC link reactors, built-in Modbus RTU, Metasys N2, Apogee FLN P1 and RFI Class A2 filter. Available in IP55/IP66 enclosure.
Features
  • RFI class A2 filter and DC link reactor as standard configuration.
  • Built-in communication networks for ModBus RTU, Metasys N2 and Apogee FLN P1
  • Field installed network options: BACnet, LonWorks, Profibus DP, Profinet, Modbus TCP/IP, Ethernet/IP and DeviceNet
  • 110% current overload for 1 minute (Light Duty)
  • Hot pluggable, illuminated LCD display, unit indications, rotation direction indication, trended charts display speed, torque, current, full alarm messages & descriptions
  • 4 auto-tuning PID controllers
  • Integrated logic control, PLC
  • “Pick up” start (catch a spinning motor)
  • Easy to use PC software
  • Energy monitoring feature
  • Flow compensation
  • Pump cascade controller
  • Sleep mode
  • Fan belt monitoring
  • Stairwell pressurization
  • Fire override mode
  • High standard protection Class 3C2, optional class 3C3

1 - 12 of 720 Part Numbers
6KFP23010X1RXCA1
6KFP23010X1RXCA1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
  • Conformal Coating - Conformal Coatings
  • Version - 1st Version
6KFP23010X1RXCB1
6KFP23010X1RXCB1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
  • Conformal Coating - Conformal Coatings
  • Version - 2nd Version
6KFP23010X1RXCC1
6KFP23010X1RXCC1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
  • Conformal Coating - Conformal Coatings
  • Version - Future Version
6KFP23010X1RXXA1
6KFP23010X1RXXA1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
  • Conformal Coating - No Conformal Coatings
  • Version - 1st Version
6KFP23010X1RXXB1
6KFP23010X1RXXB1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
  • Conformal Coating - No Conformal Coatings
  • Version - 2nd Version
6KFP23010X1RXXC1
6KFP23010X1RXXC1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
  • Conformal Coating - No Conformal Coatings
  • Version - Future Version
6KFP23010X1XXCA1
6KFP23010X1XXCA1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - Only A2 RFI Filter Installed
  • Conformal Coating - Conformal Coatings
  • Version - 1st Version
6KFP23010X1XXCB1
6KFP23010X1XXCB1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - Only A2 RFI Filter Installed
  • Conformal Coating - Conformal Coatings
  • Version - 2nd Version
6KFP23010X1XXCC1
6KFP23010X1XXCC1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - Only A2 RFI Filter Installed
  • Conformal Coating - Conformal Coatings
  • Version - Future Version
6KFP23010X1XXXA1
6KFP23010X1XXXA1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - Only A2 RFI Filter Installed
  • Conformal Coating - No Conformal Coatings
  • Version - 1st Version
6KFP23010X1XXXB1
6KFP23010X1XXXB1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - Only A2 RFI Filter Installed
  • Conformal Coating - No Conformal Coatings
  • Version - 2nd Version
6KFP23010X1XXXC1
6KFP23010X1XXXC1
  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 10 HP
  • Enclosure Type - IP21/type 1
  • A1 / B1 RFI Filter - Only A2 RFI Filter Installed
  • Conformal Coating - No Conformal Coatings
  • Version - Future Version
1 - 12 of 720 Part Numbers

Specifications

Environmental Conditions

Enclosures

  • IP20 Chassis
  • IP54
  • IP55
  • IP21
  • IP00 Chassis

Installation Location

  • For use at altitudes of 1000 m or Less without derating.

Storage Temperature

  • -25° to 65° C

Ambient Temperature

  • 10° to +50° C for above 45° C, there will be derating

Ambient Humidity

  • 5 to 95 % Relative Humidity, Non-Condensing

Vibration

  • 1.0 G

Cooling Method

  • Fan Cooled all ratings. Fan Control auto, 50 % level, 75 % level, 100 % level Adjustable

Standards

Approvals & Certifications

  • Suitable for use on a Circuit capable of delivering not more than 100,000 RMS symmetrical amperes for 230 V and 400 V.
  • C-Tick
  • cUL
  • UL
  • CE

Input Power Supply

Rated Input AC Voltage

  • 525-690 Vac, 3-Phase, 50/60 Hz, ± 10 % V
  • 380-480 Vac, 3-Phase, 50/60 Hz, ± 10 % V
  • 200-240 Vac, 3-Phase, 50/60 Hz, ± 10 % V

Maximum Voltage Imbalance

  • 3 % of rated Supply Voltage

True Power Factor

  • > 0.9 Nominal at Rated Load

Displacement Power Factor

  • > 0.98

Switching on Input Power Supply

  • Maximum twice/minute up to 7.5 kW
  • Maximum once/minute above 7.5 kW

Environment According to EN60664-1

  • Overvoltage Category III/Pollution Degree 2

DC Link Reactors

  • Built-In DC Link Reactors on all ratings

RFI Filters

  • Built-In RFI Filters to reduce noise generated by the drive

Output

Rated Output Voltage

  • 0 to 100 % of Supply Voltage

Output Frequency

  • 0 to 590 Hz

Switching on Output

  • Unlimited

Acceleration / Deceleration Time

  • 1-3600 seconds

Control Method

  • Sinusoidal PWM Control (V/Hz, Avd. vector Control)

Control

Starting Torque

  • 110 % Starting torque for 1 minute (Variable torque)

Carrier Frequency (Motor Noise, KHz)

  • 16
  • 14
  • 12
  • 10
  • 8
  • 7
  • 6
  • 5
  • 4
  • 3.5
  • 3
  • 2
  • 1.5
  • 1
  • 2.5

Torque Boost

  • 0 to 300 % setting to compensate voltage in relation to the load at low speed

Acceleration / Deceleration Time

  • 0.01-3600 seconds (4 acceleration and deceleration times are selectable via digital inputs. Acceleration and deceleration patterns can be selected from linear or S-Curve)

Data Protection

  • Password Protection for quick menu or main menu, 0-9999

Pattern Operation

  • Settings via built-in logic Controller sequencer

Jump Frequency Control

  • 4 jump (or skip) frequencies via Parameter set to avoid mechanical vibration

Slip Compensation

  • Maintains motor at constant speed with load fluctuations

Torque Limit Control

  • Output torque can be controlled within a Range of 0.0 to 110 % (0.1 and steps)

Preset Speeds

  • 8 Programmable preset speeds selectable by 3 digital inputs

Built-In Communications

  • Apogee FLN P1
  • Metasys N2
  • Modbus RTU
  • Drive RS-485

Trim Reference Setting

  • Available for speed reference offset via potentiometer, Voltage Input, or Current Input

DC Injection Braking

  • Braking level: 0-100 % of rated Current
  • Braking Time: 0.0-60.0 seconds
  • Starting frequency: 0.0-590 Hz

Auto-Restart After Power Failure

  • Restarts the drive without stopping after instantaneous Power failure

Jogging Operation

  • Operation via on Key or Digital Input (Forward or Reverse)

Energy Savings

  • Controls output voltage to minimize motor loss during constant speed operation

Start Mode Function

  • This functionality smoothly catches a Spinning motor

Fire Override Mode

  • Overrides drive’s Protective features and keeps motor running

Pump Cascade Controller

  • Distributes running hours evenly over up to 4 pumps

Sleep Mode

  • Drive detects Low or no fl ow conditions and Adjusts output

Dry Pump Detection

  • Detects pump Operation and can set off Alarm, shuts off, or other Programmed actions

Belt Monitoring

  • Drive can detect Relationship between Current and speed to recognize a broken belt

Real Time Clock

  • With Programmable timed actions

Logic Controller (LC) Sequencer

Logic Controller Events

  • Up to 38 Programmable events

Comparators

  • Array of 6 comparators

Timers

  • Array of 8 timers, Adjustable from 0.0 to 3600 sec

Logic Rules

  • Array of 6 boolean logic rules

Logic Controller States

  • Array of 20 logic Controller action States

Process Controller (PID)

Controller

  • 4 Auto Tune PID Controllers Built-in

Feedback Select

  • Up to 2 references. Selectable - no function, motor feedback, separate encoder, encoder option module, or resolver option module

Anti Windup

  • Enabled
  • Disabled

Start Speed

  • 0.0-200 Hz

Proportional Gain

  • 0.00-10.00

Integral Time

  • 0.1 - 10000.0 millisecond

Differential Time

  • 0.0 - 10 s

Differential Gain

  • 1.0-50.00

Feed Forward Factor

  • 0 to 500 %

On Reference Bandwidth

  • 0 to 200 %

Operation

Operation Method

  • Communications: RS-485 Modbus RTU, Metasys N2, and Apogee FLN P1 USB Port for Programming drive with optional PC Software
  • Keypad Operation: Hand, off, auto Digital Input: Programmable for Start/stop, forward/reverse, jog timer Operation: Stop after predetermined time frame

Frequency Reference Signal

  • 0/4-20 mA Analog Input
  • 0-10 Vdc Analog Input
  • Speed Potentiometer: 0 to +10 Vdc, 10 to 0 Vdc
  • Left or right arrow Buttons on keypad in manual mode

References

  • Up to 3 Input references can be selected from analogue Input #1 or #2, frequency Input #1 or #2, network, or potentiometer

Output Signals

  • 2x Digital Outputs 24 Vdc (Digital outputs are used in place of 2 of the digital inputs)
  • 2x form C Relays rated to 2A at 230 Vac
  • 1x analog output 0/4-20 mA

Protective Functions

  • Line Phase Loss
  • Serial Comms Bus Fault
  • Hardware Mismatch
  • Speed Limit
  • Auto Tuning Fault
  • Soft Charge Fault
  • No Motor
  • Keypad Error
  • DC Overvoltage
  • DC Undervoltage
  • Drive Overload
  • Motor Overtemperature
  • Motor Thermistor Overtemperature
  • Torque Limit
  • Overcurrent
  • Ground Fault
  • Short Circuit
  • Control Word Timeout
  • Brake Resistor Short-CCircuited
  • Brake Chopper Short-Circuited
  • Brake Check
  • DC Link Voltage High
  • Internal Fan Fault
  • External Fan Fault
  • Power Board Overtemperature
  • Missing U Phase
  • Missing V Phase
  • Missing W Phase
  • Internal Fault
  • Control Votlage Fault
  • Auto Tune Check - Wrong Motor Parameters
  • Auto Tune Low Onom - Motor Current is too Low
  • Current Limit
  • Mechanical Brake Low
  • Drive Initialized to Default Value
  • DC Link Voltage Low

Keypad

Keypad Features

  • LCD display with 6 alpha-numeric lines
  • Multi-language support
  • Hot pluggable, remote Mount option, and copycat Feature, IP65 rating when remote Mounted on Enclosure
  • LED’s - Green - drive is on, Yellow - indicates a warning, Red - indicates an Alarm, amber - indicates active menu keys and H-O-A keys

Password

  • 2 level password Protection

Alternate Motor Parameters

  • Up to 4 separate complete Parameter set-Ups are available

Graphical Trending

  • Trend Speed
  • Power
  • Frequency

RS-485 Modbus RTU Serial Communications

Physical Level

  • EIA/RS-485

Transmission Distance

  • 500 m

Node Address

  • 32

Transmission Speed

  • 2400
  • 4800
  • 9600
  • 19200
  • 38400
  • 115200

Transmission Mode

  • Half Duplex

Transmission Protocol

  • Modbus RTU

Character Code

  • Binary

Character Length

  • 8-bits

Error Check

  • CRC

Mounting Clearance

  • All AF-600 FP drives can be Mounted
  • side-by-side without Spacing. for all drives rated 90 kW or below Allow 100 mm free Space above and below
  • For all drives rated 110 kW and above Allow 225 mm free Space above and below

  • HVAC
  • Cooling Towers
  • VAV
  • Supply & Return
  • Exhaust
  • Fume Hood
  • Make-up Air
  • Induced & Forced Draft
  • Furnace Temperature Control
  • Chilled Water
  • Pressure Boosting
  • Cooling Tower
  • Wastewater
  • Chiller
  • Irrigation
  • Hydro-storage

Documentation

Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team