AF-600 FP - Fan and Pump Drives
Brand: General ElectricThe AF-600 FP Fan and Pump Drive is a powerful, flexible and easy to use AC variable torque drive.
The drive is available in its standard configuration that includes LCD keypad display that can be remote mounted, DC link reactors, built-in Modbus RTU, Metasys N2, Apogee FLN P1 and RFI Class A2 filter. Available in IP55/IP66 enclosure.
Features- RFI class A2 filter and DC link reactor as standard configuration.
- Built-in communication networks for ModBus RTU, Metasys N2 and Apogee FLN P1
- Field installed network options: BACnet, LonWorks, Profibus DP, Profinet, Modbus TCP/IP, Ethernet/IP and DeviceNet
- 110% current overload for 1 minute (Light Duty)
- Hot pluggable, illuminated LCD display, unit indications, rotation direction indication, trended charts display speed, torque, current, full alarm messages & descriptions
- 4 auto-tuning PID controllers
- Integrated logic control, PLC
- “Pick up” start (catch a spinning motor)
- Easy to use PC software
- Energy monitoring feature
- Flow compensation
- Pump cascade controller
- Sleep mode
- Fan belt monitoring
- Stairwell pressurization
- Fire override mode
- High standard protection Class 3C2, optional class 3C3
1 - 12 of 720 Part Numbers
6KFP23010X1RXCA1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
- Conformal Coating - Conformal Coatings
- Version - 1st Version
6KFP23010X1RXCB1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
- Conformal Coating - Conformal Coatings
- Version - 2nd Version
6KFP23010X1RXCC1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
- Conformal Coating - Conformal Coatings
- Version - Future Version
6KFP23010X1RXXA1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
- Conformal Coating - No Conformal Coatings
- Version - 1st Version
6KFP23010X1RXXB1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
- Conformal Coating - No Conformal Coatings
- Version - 2nd Version
6KFP23010X1RXXC1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - A1/B1 RFI Filter Installed
- Conformal Coating - No Conformal Coatings
- Version - Future Version
6KFP23010X1XXCA1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - Only A2 RFI Filter Installed
- Conformal Coating - Conformal Coatings
- Version - 1st Version
6KFP23010X1XXCB1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - Only A2 RFI Filter Installed
- Conformal Coating - Conformal Coatings
- Version - 2nd Version
6KFP23010X1XXCC1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - Only A2 RFI Filter Installed
- Conformal Coating - Conformal Coatings
- Version - Future Version
6KFP23010X1XXXA1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - Only A2 RFI Filter Installed
- Conformal Coating - No Conformal Coatings
- Version - 1st Version
6KFP23010X1XXXB1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - Only A2 RFI Filter Installed
- Conformal Coating - No Conformal Coatings
- Version - 2nd Version
6KFP23010X1XXXC1
- Input Voltage - 230 V, 50/60 Hz
- Input Phase - 3-Phase
- HP Rating - 10 HP
- Enclosure Type - IP21/type 1
- A1 / B1 RFI Filter - Only A2 RFI Filter Installed
- Conformal Coating - No Conformal Coatings
- Version - Future Version
1 - 12 of 720 Part Numbers
Specifications
Brand
Environmental Conditions
Enclosures
- IP20 Chassis
- IP54
- IP55
- IP21
- IP00 Chassis
Installation Location
- For use at altitudes of 1000 m or Less without derating.
Storage Temperature
- -25° to 65° C
Ambient Temperature
- 10° to +50° C for above 45° C, there will be derating
Ambient Humidity
- 5 to 95 % Relative Humidity, Non-Condensing
Vibration
- 1.0 G
Cooling Method
- Fan Cooled all ratings. Fan Control auto, 50 % level, 75 % level, 100 % level Adjustable
Standards
Approvals & Certifications
- Suitable for use on a Circuit capable of delivering not more than 100,000 RMS symmetrical amperes for 230 V and 400 V.
- C-Tick
- cUL
- UL
- CE
Input Power Supply
Rated Input AC Voltage
- 525-690 Vac, 3-Phase, 50/60 Hz, ± 10 % V
- 380-480 Vac, 3-Phase, 50/60 Hz, ± 10 % V
- 200-240 Vac, 3-Phase, 50/60 Hz, ± 10 % V
Maximum Voltage Imbalance
- 3 % of rated Supply Voltage
True Power Factor
- > 0.9 Nominal at Rated Load
Displacement Power Factor
- > 0.98
Switching on Input Power Supply
- Maximum twice/minute up to 7.5 kW
- Maximum once/minute above 7.5 kW
Environment According to EN60664-1
- Overvoltage Category III/Pollution Degree 2
DC Link Reactors
- Built-In DC Link Reactors on all ratings
RFI Filters
- Built-In RFI Filters to reduce noise generated by the drive
Output
Rated Output Voltage
- 0 to 100 % of Supply Voltage
Output Frequency
- 0 to 590 Hz
Switching on Output
- Unlimited
Acceleration / Deceleration Time
- 1-3600 seconds
Control Method
- Sinusoidal PWM Control (V/Hz, Avd. vector Control)
Control
Starting Torque
- 110 % Starting torque for 1 minute (Variable torque)
Carrier Frequency (Motor Noise, KHz)
- 16
- 14
- 12
- 10
- 8
- 7
- 6
- 5
- 4
- 3.5
- 3
- 2
- 1.5
- 1
- 2.5
Torque Boost
- 0 to 300 % setting to compensate voltage in relation to the load at low speed
Acceleration / Deceleration Time
- 0.01-3600 seconds (4 acceleration and deceleration times are selectable via digital inputs. Acceleration and deceleration patterns can be selected from linear or S-Curve)
Data Protection
- Password Protection for quick menu or main menu, 0-9999
Pattern Operation
- Settings via built-in logic Controller sequencer
Jump Frequency Control
- 4 jump (or skip) frequencies via Parameter set to avoid mechanical vibration
Slip Compensation
- Maintains motor at constant speed with load fluctuations
Torque Limit Control
- Output torque can be controlled within a Range of 0.0 to 110 % (0.1 and steps)
Preset Speeds
- 8 Programmable preset speeds selectable by 3 digital inputs
Built-In Communications
- Apogee FLN P1
- Metasys N2
- Modbus RTU
- Drive RS-485
Trim Reference Setting
- Available for speed reference offset via potentiometer, Voltage Input, or Current Input
DC Injection Braking
- Braking level: 0-100 % of rated Current
- Braking Time: 0.0-60.0 seconds
- Starting frequency: 0.0-590 Hz
Auto-Restart After Power Failure
- Restarts the drive without stopping after instantaneous Power failure
Jogging Operation
- Operation via on Key or Digital Input (Forward or Reverse)
Energy Savings
- Controls output voltage to minimize motor loss during constant speed operation
Start Mode Function
- This functionality smoothly catches a Spinning motor
Fire Override Mode
- Overrides drive’s Protective features and keeps motor running
Pump Cascade Controller
- Distributes running hours evenly over up to 4 pumps
Sleep Mode
- Drive detects Low or no fl ow conditions and Adjusts output
Dry Pump Detection
- Detects pump Operation and can set off Alarm, shuts off, or other Programmed actions
Belt Monitoring
- Drive can detect Relationship between Current and speed to recognize a broken belt
Real Time Clock
- With Programmable timed actions
Logic Controller (LC) Sequencer
Logic Controller Events
- Up to 38 Programmable events
Comparators
- Array of 6 comparators
Timers
- Array of 8 timers, Adjustable from 0.0 to 3600 sec
Logic Rules
- Array of 6 boolean logic rules
Logic Controller States
- Array of 20 logic Controller action States
Process Controller (PID)
Controller
- 4 Auto Tune PID Controllers Built-in
Feedback Select
- Up to 2 references. Selectable - no function, motor feedback, separate encoder, encoder option module, or resolver option module
Anti Windup
- Enabled
- Disabled
Start Speed
- 0.0-200 Hz
Proportional Gain
- 0.00-10.00
Integral Time
- 0.1 - 10000.0 millisecond
Differential Time
- 0.0 - 10 s
Differential Gain
- 1.0-50.00
Feed Forward Factor
- 0 to 500 %
On Reference Bandwidth
- 0 to 200 %
Operation
Operation Method
- Communications: RS-485 Modbus RTU, Metasys N2, and Apogee FLN P1 USB Port for Programming drive with optional PC Software
- Keypad Operation: Hand, off, auto Digital Input: Programmable for Start/stop, forward/reverse, jog timer Operation: Stop after predetermined time frame
Frequency Reference Signal
- 0/4-20 mA Analog Input
- 0-10 Vdc Analog Input
- Speed Potentiometer: 0 to +10 Vdc, 10 to 0 Vdc
- Left or right arrow Buttons on keypad in manual mode
References
- Up to 3 Input references can be selected from analogue Input #1 or #2, frequency Input #1 or #2, network, or potentiometer
Output Signals
- 2x Digital Outputs 24 Vdc (Digital outputs are used in place of 2 of the digital inputs)
- 2x form C Relays rated to 2A at 230 Vac
- 1x analog output 0/4-20 mA
Protective Functions
- Line Phase Loss
- Serial Comms Bus Fault
- Hardware Mismatch
- Speed Limit
- Auto Tuning Fault
- Soft Charge Fault
- No Motor
- Keypad Error
- DC Overvoltage
- DC Undervoltage
- Drive Overload
- Motor Overtemperature
- Motor Thermistor Overtemperature
- Torque Limit
- Overcurrent
- Ground Fault
- Short Circuit
- Control Word Timeout
- Brake Resistor Short-CCircuited
- Brake Chopper Short-Circuited
- Brake Check
- DC Link Voltage High
- Internal Fan Fault
- External Fan Fault
- Power Board Overtemperature
- Missing U Phase
- Missing V Phase
- Missing W Phase
- Internal Fault
- Control Votlage Fault
- Auto Tune Check - Wrong Motor Parameters
- Auto Tune Low Onom - Motor Current is too Low
- Current Limit
- Mechanical Brake Low
- Drive Initialized to Default Value
- DC Link Voltage Low
Keypad
Keypad Features
- LCD display with 6 alpha-numeric lines
- Multi-language support
- Hot pluggable, remote Mount option, and copycat Feature, IP65 rating when remote Mounted on Enclosure
- LED’s - Green - drive is on, Yellow - indicates a warning, Red - indicates an Alarm, amber - indicates active menu keys and H-O-A keys
Password
- 2 level password Protection
Alternate Motor Parameters
- Up to 4 separate complete Parameter set-Ups are available
Graphical Trending
- Trend Speed
- Power
- Frequency
RS-485 Modbus RTU Serial Communications
Physical Level
- EIA/RS-485
Transmission Distance
- 500 m
Node Address
- 32
Transmission Speed
- 2400
- 4800
- 9600
- 19200
- 38400
- 115200
Transmission Mode
- Half Duplex
Transmission Protocol
- Modbus RTU
Character Code
- Binary
Character Length
- 8-bits
Error Check
- CRC
Mounting Clearance
- All AF-600 FP drives can be Mounted
- side-by-side without Spacing. for all drives rated 90 kW or below Allow 100 mm free Space above and below
- For all drives rated 110 kW and above Allow 225 mm free Space above and below
- HVAC
- Cooling Towers
- VAV
- Supply & Return
- Exhaust
- Fume Hood
- Make-up Air
- Induced & Forced Draft
- Furnace Temperature Control
- Chilled Water
- Pressure Boosting
- Cooling Tower
- Wastewater
- Chiller
- Irrigation
- Hydro-storage