Yodify Product Library
Instantly add the MICRO-DCI 53ML5100B Manual Loader and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
MICRO-DCI 53ML5100B Manual Loader
Brand: MicroMod Automation & ControlsThe 53ML5100 features manual adjustment of two independent current outputs. The high visibility dot matrix display permits two process variables to be indicated in a clear and concise manner.
The 53ML5100 accepts two process inputs and provides manual control of two outputs. A built in 24 Vdc transmitter power supply provides up to 80 mA.
Six standard displays allow the user to select the operation screens best suited to the installation. The display order is configurable for easy access to preferred presentation of process information. The displays include: Dual Channel Manual Loader, Single Channel Manual Loader, Manual Loader with Analog Input (2), Analog Input w/Manual Setpoint (2).
53ML5100B is a direct replacement for the 53ML5100A. The standard displays, alarm reporting and alarm acknowledgement are identical, making the transition seamless for operators, and it can be mounted in the same panel cutout.
FeaturesSpecifications
Accuracy
- ± 0.1 % of Span
- ± 0.2 % of Span
Adjustment
- Push-Buttons
Ambient Temperature Range
- 4° to 52° C (40° to 125° F)
Approvals & Certifications
- ISA S71.01 1985
Approvals & Certifications
- FM
Bezel Material
- ULTEM 1000 (Polyetherimide Resin)
Communication
- Baud Rate: 300 to 9,600 Plus 14,400 & 28,800
- RS-232
Consumption
- AC Operation: 15 VA, Max.
Display
- 48 x 96 Pixels
Electrical Connectors
- Rear-of-Case Compression-Typical Terminal Strips
Enclosure Finish
- Baked Enamel
- Light Gray
- Painted with RAL 9002
Environmental Protection
- IP10
- IP20
- NEMA 1
Humidity
- 10 to 90 % Relative Humidity, Max.
Indication
- Alarm Status
Input
- 1-5 Vdc
- Signal Range: 0-5 Vdc - Analog Input
Input Impedance
- 1 Megaohm, Min.
Load
- 0 to 750 ohms
Materials of Construction
- Circuit Boards: Glass Epoxy
Output
- Available Power for Transmitters: 24-26 Vdc, 80 mA, Short Circuit Protected
- Ripple: 200 mV Peak-to-Peak, Max.
- Signal Range: 0-21.84 mA (4-20 mA Dc Typically)
- Slew Rate: 40 mA/second
Power Requirement
- 110-120 Vac, 50/60 Hz
- 120 Vac ± 10 %, 50/60 Hz
- 21-28 Vdc
- 220-240 Vac ± 10 %, 50/60 Hz
- 24 Vdc
Sample Rate
- Input & Output Signal: 50 milliseconds
Scan Time
- Program: 100 milliseconds
Temperature Effect
- ± 0.28 % Per 28° C (50° F) from Reference Temperature of 25° C (77° F)
Update Time
- 100 milliseconds