Yodify Product Library
Instantly add the Pilot Monitor (PM) and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

Flammable vent gasses are ignited by a pilot flame when released into the atmosphere by chemical and petrochemical plants of all types. 

The proper incineration of these gasses is a critical safety and environmental concern. Therefore, it is essential to confirm that the pilot is lit at all times.

Monitoring via thermocouple is common, however failures frequently occur and replacements can require costly process shutdowns.

The Williamson Pilot Monitor (PM) utilizes proven dual-wavelength technology to sense the presence of the small, distant pilot flame. 

This technology allows the pilot monitor to view clearly through severe weather conditions caused by fog, wind, rain, snow and sleet.
Features
  • Self-regulating means no on-site calibration
  • May be grade-mounted for easy access
  • 30% greater sensitivity means greater reliability
  • Includes Signal Dilution output for measurement validation and diagnostics
  • Large viewing area for easy alignment

Specifications

Output Scale

  • 0 to 100 %

Spectral Response

  • Proprietary Narrow Wavebands

Optical Resolution

  • D/35 or D/75

Maximum Distance

  • 2,000 ft, 610 m

Response Time

  • Adjustable 0.1 to 24 s

Analog Output

  • 4-20 mA
  • 0-20 mA

Alarm

  • Sensor: One SPST Relay ALarm Output 2 A @ 120 or 250 Vac

Digital Interface

  • Bi-Directional RS-485 and RS-232 Communcations

Human Interface

  • Built-in Menu System with Access to Signal Conditioning, Programmable Outputs & Alarms

Measurement Parameter

  • Filtered Signal
  • Unfilterred Signal
  • Signal Dilution
  • Ambient Temperature

Ambient Temperature

  • Sensor: -40° to 150° F (-40° to 65° C)

Environmental Protection

  • IP65
  • NEMA 4X

Certifications & Approvals

  • CE
  • LVD

Documentation

Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more