Yodify Product Library
Instantly add the MVHK Digital Limit Alarm and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
MVHK Digital Limit Alarm
Brand: Yokogawa Electric CorporationThis plug-in type Limit Alarm for DC input receives DC current or DC voltage signal.
It is equipped with Active color PV display (PV display color changing function).
Features- Either 2 points of alarms (relay transfer contact [1a1b], 2 points), 4 points of alarms (relay NO contact, 4 points) or 2 points of alarms/1 point fail output can be selected.
- An alarm status in the event of an alarm can be recognized.
- Detects FAIL condition by self-diagnosis function (FAIL output type)
- Equipped with easy-to-see large LED display as standard.
- Using the economical mode enables the low power consumption operation (normal operation: approx. 0.5 W, 1 VA).
- Input range and each parameter setting can be changed by the operation keys on the front panel.
- Can be equipped with monitor output (1 to 5 V DC, 4 to 20 mA DC or RS-485 communication) .
Specifications
Accuracy
- ± 0.1 % of Output Span - Output Accuracy
- ± 0.1 %, ± 1 % Digit of Instrument Input Range Span - Input Display Accuracy & Alarm Action Point Setting Accuracy
Alarm
- 2 Orange LEDs for 2-Points of Alarms - Alarm Indicator Lamp
- 4 Orange LEDs for 4-Points of Alarms - Alarm Indicator Lamp
- High-Limit Alarm
- Low-Limit Alarm
Communication
- 2-Wire Half-Duplex
- Baud Rate: 1,200, 2,400, 4,800 or 9,600 bit/sec
- Data Length: 7-bits, 8-bits
- EIA RS-485
- LADDER Communication
- Modbus ASCII/RTU
- PC-Link Communication Protocol
- PC-Link with Sum
- Start-Stop Synchronization
- Stop Bit: 1-bit, 2-bits
Consumption
- 0.5 W, 1 VA (Normal Operation: Approximately) - Power Consumption Operation
- 2.4 W, 110 Vdc - Power Consumption
- 3 W, 24 Vdc - Power Consumption
- 3.9 VA, 100 Vac - Power Consumption
- 5.3 VA, 200 Vac - Power Consumption
Display
- -1999 to 9999 - Input Scaling (Displayed Value)
- 4-Digits - PV (Measured Value) Display & Data Display
- 7-Segment - PV (Measured Value) Display & Data Display
- Character Height of 0.35” (9 mm) - Data Display
- Character Height of 0.53” (13.5 mm) - PV (Measured Value) Display
- Green LED - PV (Measured Value) Display & Data Display
- LED Display
- Red LED - PV (Measured Value) Display
Distance
- 1,200 metres - Max.
Electrical Connectors
- 3-Pin 2-Piece Connector for Monitor Output
- M3.5 Screw Terminal for Input/Output & Power Supply
Electrical Rating
- 0.1 A at 120 Vdc - Contact Rating
- 0.5 A at 220 Vac - Contact Rating
- 1 A at 120 Vac - Contact Rating
- 1 A at 30 Vdc - Contact Rating
Enclosure, Body Material
- ABS Resin (Black), UL 94 V-0
Humidity
- 5 to 90 % Relative Humidity, Non-Condensing - Operating Humidity Range
Input Signal
- 0-50 mA DC
- -10-10 Vdc
Insulation Resistance
- 100 megaohms at 500 Vdc between Inputs, Alarm Outputs, Power Supply & Monitor Output Mutually
Materials of Construction
- Modified Polyphenylene Oxide Resin, Including Glass Fiber (Black), UL 94 V-1 - Socket
Mounting
- DIN Rail Mounting for Side-by-Side Mounting
- Plug-In Typical
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 1-5 Vdc
- 4-20 mA DC
- -6 to 106 % - Output Variable Range
Output Format
- Relay Contact - Signal Typical
Power Supply
- 100-240 Vac/dc (-15 %, 10 %), 50/60 Hz
- 24 Vdc ± 10 %
Power Supply Effect
- ± 0.1 % of Span or Less for the Fluctuations within the Allowable Range of Each Power Supply Specification - Effect of Power Supply Fluctuation
Resistance
- 1 Megaohm (100 kiloohms During Power Off) - for Voltage Input Resistance
- 100 ohms (with External Receiving Resistor) - for Current Input Resistance
- 2 kiloohms or more for 1-5 Vdc - Allowable Load Resistance
- 250 ohms (with External Receiving Resistor) - for Current Input Resistance
- 350 ohms or Less for 4-20 mA DC - Allowable Load Resistance
Resolution
- 1 second - for Alarm ON & OFF Delay Setting Resolution
- 1-Digit - Setting Resolution
Response Time
- 500 milliseconds
Supply Voltage
- 1,000 Vac/minute between (Alarm Outputs 1 & 4) & (Alarm Outputs 2 & 3) & between Inputs & Monitor Output - Withstand Voltage
- 2,000 Vac/minute between Inputs, (Alarm Outputs 1, 2, 3, 4), Monitor Output & Power Supply Mutually - Withstand Voltage
Temperature Effect
- ± 0.2 % of Span or Less for a Temperature Change of 10° C (50° F)