VESDA-E VEA Detector
Brand: Xtralis by HoneywellThe VESDA-E VEA series of detectors combine VESDA reliability and early warning smoke detection with pinpoint addressability and a variety of annunciation options that truly surpass traditional spot detectors.
They use patented air sampling points and multi-channel microbore air-sampling with three alarm sensitivity settings for the sampling points. As a multi-channel addressable system, the VEA detector is able to divide a protected space into sampling locations, enabling the localization of potential sources of fire for faster incident response.
The detectors are suitable for protection of areas where pinpoint location of fire events is essential, thus providing ideal fire detection solutions for healthcare, offices, education, retail, prisons and electrical cabinets. A wide range of features provide flexibility, field programmability, enhanced connectivity and reduced total cost of ownership.
Features- Pinpoint addressability with superior detection compared to spot detectors
- 40 addressable microbore tubes with individual sampling points
- Assured detection with end to end system integrity monitoring
- Interruption-free business operation with centralised testing and maintenance
- Single sampling point or single tube blockage detection
- Automatic sampling point presence and tube breakage detection
- Automatic sampling point cleaning
- Three sensitivity settings for the sampling points
Specifications
Brand
Ambient Temperature Range
- 0° to 39° C (32° to 103° F)
Approvals & Certifications
- EN 54-20, ISO 7240-20: Class A, B & C
Approvals & Certifications
- UL/ULC
Communication
- Ethernet (RJ45)
- USB 2.0
- WiFi (802.11 B/g/n)
Consumption
- 27 W Quiescent & Alarm at 24 Vdc
Current
- Peak Current (Scan Mode) 3.5 A
Environmental Protection
- IP40
Humidity
- 10 to 95 % Relative Humidity, Non-Condensing
Sensitivity
- 0.020 %/m (0.006 %/ft) to 16 %/m (4.88 %/ft)
Supply Voltage
- 18-30 Vdc