Yodify Product Library
Instantly add the Motor Protection Relay Series 8510 and 50,000+ more product series to yourĀ store or catalogĀ Ā 
Book Your Demo and See How
or create your store

Motor Protection Relay Series 8510

Brand: R. STAHL AG

R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. 

The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
Features
  • Cost-effective overload protection for motors
  • Easy to adjust and reset the release
  • Robust modules, simple and anti-vibration installation

1 - 12 of 21 Part Numbers
145747
145747
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Main contacts - 3-pole (3 NOs)
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/122-05-235-..0
  • Title Product Variant Technical Data - 8510/122-05-235-..0 motor protection rel
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Möller
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 168.000 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.300 kg
  • Width - 70.000 mm
145757
145757
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Main contacts - 3-pole (3 NOs)
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/141-05-335-..0
  • Title Product Variant Technical Data - 8510/141-05-335-..0 motor prot. relay
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Siemens
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 110.500 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.600 kg
  • Width - 80.000 mm
217528
217528
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 1.00 - 1.60 A
  • Current-setting range max. - 1.60 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 1.00 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/122-05-235-070
  • Title Product Variant Technical Data - 8510/122-05-235-070 m.p.rel. 1,0-1,6 A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Möller
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 168.000 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.300 kg
  • Width - 70.000 mm
217529
217529
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 1.60 - 2.40 A
  • Current-setting range max. - 2.40 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 1.60 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/122-05-235-080
  • Title Product Variant Technical Data - 8510/122-05-235-080 m.p.rel. 1,6-2,4 A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Möller
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 168.000 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.300 kg
  • Width - 70.000 mm
217530
217530
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 4.00 - 6.00 A
  • Current-setting range max. - 6.00 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 4.00 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/122-05-235-100
  • Title Product Variant Technical Data - 8510/122-05-235-100 m.p.rel. 4,0-6,0 A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Möller
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 168.000 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.300 kg
  • Width - 70.000 mm
217531
217531
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 6.00 - 10.00 A
  • Current-setting range max. - 10.00 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 6.00 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/122-05-235-120
  • Title Product Variant Technical Data - 8510/122-05-235-120 m.p.rel. 6,0-10 A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Möller
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 168.000 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.300 kg
  • Width - 70.000 mm
217532
217532
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 10.00 - 16.00 A
  • Current-setting range max. - 16.00 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 10.00 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/122-05-235-130
  • Title Product Variant Technical Data - 8510/122-05-235-130 m.p.rel. 10-16 A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Möller
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 168.000 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.300 kg
  • Width - 70.000 mm
217533
217533
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 16.00 - 22.50 A
  • Current-setting range max. - 22.50 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 16.00 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/122-05-235-140
  • Title Product Variant Technical Data - 8510/122-05-235-140 m.p.rel. 16-22,5 A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Möller
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 168.000 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.300 kg
  • Width - 70.000 mm
217534
217534
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 0.35 - 0.50 A
  • Current-setting range max. - 0.50 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 0.35 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/141-05-335-060
  • Title Product Variant Technical Data - 8510/141-05-335-060 m.p.rel. 0,35-0,5 A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Siemens
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 110.500 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.600 kg
  • Width - 80.000 mm
217535
217535
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 0.45 - 0.50 A
  • Current-setting range max. - 0.50 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 0.45 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/141-05-335-070
  • Title Product Variant Technical Data - 8510/141-05-335-070 m.p.rel. 0,45-0,63A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Siemens
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 110.500 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.600 kg
  • Width - 80.000 mm
217536
217536
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 0.70 - 1.00 A
  • Current-setting range max. - 1.00 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 0.70 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/141-05-335-090
  • Title Product Variant Technical Data - 8510/141-05-335-090 m.p.rel. 0,7-1,0 A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Siemens
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 110.500 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.600 kg
  • Width - 80.000 mm
217537
217537
R. STAHL Motor Protection Relay
Cost-effective overload protection for motors

Easy to adjust and reset the release

Robust modules, simple and anti-vibration installation

Ambient Conditions

  • Ambient temperature - -20 °C ... +40 °C
  • Ambient temperature max. - +40 °C
  • Ambient temperature min. - -20 °C

Electrical Data

  • Auxiliary contacts - 2 (1 NO + 1 NC)
  • Current-setting range - 0.90 - 1.25 A
  • Current-setting range max. - 1.25 A
  • Main contacts - 3-pole (3 NOs)
  • Min. current-setting range - 0.90 A
  • Rated operational voltage 2 - 690 V AC

Explosion Protection

  • Application range (zones) - 1, 2
  • ATEX firedamp certificate - DMT 00 ATEX E 073 U
  • ATEX gas certificate - DMT 00 ATEX E 073 U
  • Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), IECEx (BVS), USA (FM)
  • Firedamp protection ATEX - I M2 Ex de I
  • Firedamp protection IECEx - Ex de I
  • Gas explosion protection ATEX - II 2 G Ex de IIC
  • Gas explosion protection IECEx - Ex de IIC
  • IECEx firedamp certificate - IECEx BVS 07.0029U
  • IECEX gas certificate - IECEx BVS 07.0029U

General

  • Functional Description - R. STAHL Series 8510 motor protection relays offer cost-effective overload protection for motors with adjustment ranges up to 22.5 A. The release can be easily adjusted and reset. The relay modules in the corrosion-resistant enclosure have an anti-vibration screw connection in Ex e enclosures. Easily accessible terminals enable a safe connection and simple installation.
  • Highlights - Cost-effective overload protection for motors Easy to adjust and reset the release Robust modules, simple and anti-vibration installation
  • Product Description - Motor Protection Relay
  • Product Type - 8510/141-05-335-100
  • Title Product Variant Technical Data - 8510/141-05-335-100 m.p.rel. 0,90-1,25A
  • WebCode - 8510J

Mechanical Data

  • Built-in device manufacturer - Siemens
  • Connection cross-section of auxiliary contact finely stranded max. - 1.50 mm²
  • Connection cross-section of auxiliary contact solid max. - 2.50 mm²
  • Connection terminals finely-stranded max. - 6.00 mm²
  • Connection terminals min. - 1.50 mm²
  • Connection terminals of auxiliary contact min. - 0.75 mm²
  • Connection terminals solid max. - 10.00 mm²
  • Degree of protection (IP) - IP20
  • Depth - 110.500 mm
  • Enclosure material - Epoxy resin
  • Height - 130.000 mm
  • Type of connection cable - Finely stranded, solid
  • Weight - 1.600 kg
  • Width - 80.000 mm
1 - 12 of 21 Part Numbers