Transmitter Supply Unit with Limit Value Series 9162

Brand: R. STAHL AG

9162 series Ex i transmitter power supply units with limit values can be used for the intrinsically safe operation of two- and three-conductor transmitters or for connecting to intrinsically safe mA sources. 

Two limit values can be easily set using the ISpac Wizard software. 

If the value exceeds or falls below these limit values, these units will issue an alert. 

A wire-breakage and short-circuit monitoring system affords increased availability.
Features
  • Compact limit value switch with two configurable limit values and output of 4 to 20 mA
  • bidirectional HART transmission
  • can be used up to SIL 2 (IEC/EN 61508)

1 - 2 of 2 Part Numbers
238251
238251
R. STAHL Transmitter Supply Unit with Limit Contact Ex I Field Circuit
Compact limit value switch with two configurable limit values and output of 4 to 20 mA

bidirectional HART transmission

can be used up to SIL 2 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -40 °C ... +70 °C (Single device) -40 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -40 °C
  • Ambient temperature min. 2 - -40 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - "The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide""
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power nom. voltage - 24 V DC
  • Auxiliary power voltage range - 18 ... 31,2 V
  • Nominal current - 85.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 2.00 W
  • Power dissipation max. - 1.50 W
  • Undervoltage monitoring - Yes
  • Voltage range residual ripple - ≤ 3,6 VSS

Electrical Data

  • communication signal - HART, 0.5 .... 10 kHz
  • Isolating repeater mode - Yes
  • Limiting values configuration - using ISpac wizard (V3.04.00 and following)
  • Number of channels - 1
  • Transmitter supply mode - Yes

Explosion Protection

  • Application range (zones) - 2
  • ATEX dust certificate - BVS 15 ATEX E018 X
  • ATEX gas certificate - BVS 15 ATEX E018 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 15.0013 X
  • IECEX gas certificate - IECEx BVS 15.0013 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i input to auxiliary power - 1.5 kV AC
  • Galvanic isolation Ex i input to fault message contact - 1,5 kV AC
  • Galvanic isolation Ex i input to output - 1.5 kV AC
  • Galvanic isolation fault message contact to power supply - 350 V AC
  • Galvanic isolation output to auxiliary power - 350 V AC
  • Galvanic isolation output to output - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9162 series Ex i transmitter power supply units with limit values can be used for the intrinsically safe operation of two- and three-conductor transmitters or for connecting to intrinsically safe mA sources. Two limit values can be easily set using the ISpac Wizard software. If the value exceeds or falls below these limit values, these units will issue an alert. A wire-breakage and short-circuit monitoring system affords increased availability.
  • Highlights - Compact limit value switch with 2 configurable limiting values and 4 ... 20 mA output Suitable for 2-, 3-wire transmitter, 2-wire HART transmitter and mA-sources Intrinsically safe input [Ex ia] IIC Open-circuit and short-circuit monitoring and messaging For use up to SIL 2 (IEC 61508)
  • Product Description - Transmitter supply unit With limit contact Ex i field circuit
  • Product Type - 9162/13-11-14s
  • Title Product Variant Technical Data - 9162/13-11-14s transmitter supply u.w.G
  • WebCode - 9162A

Input

  • Input - 4 ... 20 mA with HART
  • Input current max. mA sources - 50 mA
  • Input function - Isolation amplifier Transmitter power unit
  • Input functional range - 2 - 22 mA
  • Input open circuit voltage U a - ≤ 26 V
  • Input resistance - 30 ohms
  • input signal - 4 ... 20 mA with HART
  • Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
  • short-circuit current - ≤ 35 mA
  • Supply voltage for transmitter - ≥ 16 V at 20 mA
  • Supply voltage note - (T < -10 °C: US - 0.2 V / 10K)

Mechanical Data

  • Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve
  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.225 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 0.2 mm²
  • Conduct cross-section flexible max. - 2.5 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Screw terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Analog signal delay - < 30 ms
  • Auxiliary power influence error limits - ≤ 0,01 %
  • Behaviour of the output - = input signal
  • deviation - ≤ 0,2 %
  • Error detection wire breakage - < 3.6 mA
  • Indication of line fault - "LF" LED, red
  • LFD relay - Yes
  • Limit contact (per channel) - 2 NOs
  • linearity error - ≤ 0,1 %
  • Load resistance influence - ≤ 0,02 %
  • Load resistance R L - 0 … 600 Ω (terminal 1+ / 2-)
  • Load resistance R L max. - 600.00 Ω
  • offset error - ≤ 0,1 %
  • Output - 4 ... 20 mA with HART
  • Output A - 2 ... 22 mA
  • Output functional range - 2.0 - 22.0 mA
  • Output residual ripple - ≤ 40 µAeff
  • output signal - 4 ... 20 mA with HART
  • Settling time 10 … 90 % - < 45 ms
  • Short circuit error detection - > 21 mA
  • Switch user adjustment line fault - activated / deactivated
  • Switch-back delay - < 100 ms
  • Switch-on resistance - ≤ 2.5 ohms (typical < 1 ohm)
  • Switching capacity fault message contact - 30 V / 100 mA
  • Switching current limiting values - ≤ 100 mA
  • switching delay - < 80 ms
  • Switching state indication - Yellow LED "OUT"
  • Switching voltage limiting values - ≤ ± 30 V
  • Temperature influence error limits - ≤ 0.1% / 10 K

Safety Data

  • Internal capacitance C i - negligible
  • Internal capacitance C i isolating repeater - negligible
  • Internal inductance L i - negligible
  • Internal inductance L i isolating repeater - negligible
  • Max. current I i - 100.0 mA
  • Max. Current I o - 87.9 mA
  • Max. permissible external capacitance C o for IIB - 0.705 μF
  • Max. permissible external capacitance C o for IIC - 0.090 μF
  • Max. permissible external inductance L o for IIB - 14.000 mH
  • Max. permissible external inductance L o for IIC - 2.300 mH
  • Max. Power P o - 574.000 mW
  • Max. voltage U i - 30.0 V
  • Max. Voltage U o - 27.00 V
  • Max. voltage U o isolation amplifier - 4.1 V
  • Safety-related maximum voltage - 253 V
238252
238252
R. STAHL Transmitter Supply Unit with Limit Contact Ex I Field Circuit
Compact limit value switch with two configurable limit values and output of 4 to 20 mA

bidirectional HART transmission

can be used up to SIL 2 (IEC/EN 61508)

Ambient Conditions

  • Ambient temperature - -40 °C ... +70 °C (Single device) -40 °C ... +60 °C (Group assembly)
  • Ambient temperature max. - +70 °C
  • Ambient temperature max. note - Single device
  • Ambient temperature max. note 2 - Group assembly
  • Ambient temperature max.2 - +60 °C
  • Ambient temperature min. - -40 °C
  • Ambient temperature min. 2 - -40 °C
  • Ambient temperature min. note - Single device
  • Ambient temperature min. note 2 - Group assembly
  • Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment
  • Relative humidity max. - 95%
  • Storage temperature - -40 °C ... +80 °C
  • Storage temperature max. - +80 °C
  • Storage temperature min. - -40 °C
  • Umgebungsbedingungen Hinweis - "The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide""
  • Use at the height of - < 2000 m

Auxiliary power

  • Auxiliary power - 24 V DC
  • Auxiliary power nom. voltage - 24 V DC
  • Auxiliary power voltage range - 18 ... 31,2 V
  • Nominal current - 85.00 mA
  • Operation indication - Green "PWR" LED
  • Polarity reversal protection - yes
  • Power consumption - 2.00 W
  • Power dissipation max. - 1.50 W
  • Undervoltage monitoring - Yes
  • Voltage range residual ripple - ≤ 3,6 VSS

Electrical Data

  • communication signal - HART, 0.5 .... 10 kHz
  • Isolating repeater mode - Yes
  • Limiting values configuration - using ISpac wizard (V3.04.00 and following)
  • Number of channels - 1
  • Transmitter supply mode - Yes

Explosion Protection

  • Application range (zones) - 2, 22
  • ATEX dust certificate - BVS 15 ATEX E018 X
  • ATEX gas certificate - BVS 15 ATEX E018 X
  • Certificate EAC - TS RU S-DE.GB04.B.00353
  • Certificates - ATEX (BVS), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), SIL (exida), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection EAC - [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
  • Ex interface zone - 0, 1, 20, 21, 22
  • Gas explosion protection ATEX - II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
  • Gas explosion protection EAC - 2 Ex nA nC [ia Ga] IIC T4 Gc X
  • Gas explosion protection IECEx - Ex nA nC [ia Ga] IIC T4 Gc
  • IECEX dust certificate - IECEx BVS 15.0013 X
  • IECEX gas certificate - IECEx BVS 15.0013 X
  • Installation in Division NEC 500 - (Class I, II, III) 2
  • Ship approval - CCS, DNVGL

Galvanic isolation

  • Galvanic isolation Ex i input to auxiliary power - 1.5 kV AC
  • Galvanic isolation Ex i input to fault message contact - 1,5 kV AC
  • Galvanic isolation Ex i input to output - 1.5 kV AC
  • Galvanic isolation fault message contact to power supply - 350 V AC
  • Galvanic isolation output to auxiliary power - 350 V AC
  • Galvanic isolation output to output - 350 V AC
  • Test voltage according to standard - IEC EN 60079-11
  • Test voltage according to standard 2 - EN 50178

General

  • Functional Description - 9162 series Ex i transmitter power supply units with limit values can be used for the intrinsically safe operation of two- and three-conductor transmitters or for connecting to intrinsically safe mA sources. Two limit values can be easily set using the ISpac Wizard software. If the value exceeds or falls below these limit values, these units will issue an alert. A wire-breakage and short-circuit monitoring system affords increased availability.
  • Highlights - Compact limit value switch with two configurable limit values and output of 4 to 20 mA bidirectional HART transmission can be used up to SIL 2 (IEC/EN 61508)
  • Product Description - Transmitter supply unit With limit contact Ex i field circuit
  • Product Type - 9162/13-11-14k
  • Title Product Variant Technical Data - 9162/13-11-14k transmitter supply u.w.G
  • WebCode - 9162A

Input

  • Input - 4 ... 20 mA with HART
  • Input current max. mA sources - 50 mA
  • Input function - Isolation amplifier Transmitter power unit
  • Input functional range - 2 - 22 mA
  • Input open circuit voltage U a - ≤ 26 V
  • Input resistance - 30 ohms
  • input signal - 4 ... 20 mA with HART
  • Message of line fault and Auxilliary power failure - - Contact (30 V / 100 mA) closed to ground in case of fault - pac-Bus, floating contact (30 V / 100 mA)
  • short-circuit current - ≤ 35 mA
  • Supply voltage for transmitter - ≥ 16 V at 20 mA
  • Supply voltage note - (T < -10 °C: US - 0.2 V / 10K)

Mechanical Data

  • Degree of protection (IP) - IP30
  • Enclosure material - Polyamide
  • Fire resistance (UL 94) - V0
  • Grid dimension - 17.60 mm
  • Terminal degree of protection (IP) - IP20
  • Weight - 0.225 kg

Mounting / Installation

  • Conduct cross-section flexible max. - 2.5 mm²
  • Conduct cross-section flexible max. - 0.2 mm²
  • Conductor cross-section solid max. - 2.5 mm²
  • Conductor cross-section solid min. - 0.2 mm²
  • Connection type - Spring clamp terminal
  • Mounting position - vertical horizontal
  • Mounting type - NS35/15, NS35/7.5 DIN rail

Output

  • Analog signal delay - < 30 ms
  • Auxiliary power influence error limits - ≤ 0,01 %
  • Behaviour of the output - = input signal
  • deviation - ≤ 0,2 %
  • Error detection wire breakage - < 3.6 mA
  • Indication of line fault - "LF" LED, red
  • LFD relay - Yes
  • Limit contact (per channel) - 2 NOs
  • linearity error - ≤ 0,1 %
  • Load resistance influence - ≤ 0,02 %
  • Load resistance R L - 0 … 600 Ω (terminal 1+ / 2-)
  • Load resistance R L max. - 600.00 Ω
  • offset error - ≤ 0,1 %
  • Output - 4 ... 20 mA with HART
  • Output A - 2 ... 22 mA
  • Output functional range - 2.0 - 22.0 mA
  • Output residual ripple - ≤ 40 µAeff
  • output signal - 4 ... 20 mA with HART
  • Settling time 10 … 90 % - < 45 ms
  • Short circuit error detection - > 21 mA
  • Switch user adjustment line fault - activated / deactivated
  • Switch-back delay - < 100 ms
  • Switch-on resistance - ≤ 2.5 ohms (typical < 1 ohm)
  • Switching capacity fault message contact - 30 V / 100 mA
  • Switching current limiting values - ≤ 100 mA
  • switching delay - < 80 ms
  • Switching state indication - Yellow LED "OUT"
  • Switching voltage limiting values - ≤ ± 30 V
  • Temperature influence error limits - ≤ 0.1% / 10 K

Safety Data

  • Internal capacitance C i - negligible
  • Internal capacitance C i isolating repeater - negligible
  • Internal inductance L i - negligible
  • Internal inductance L i isolating repeater - negligible
  • Max. current I i - 100.0 mA
  • Max. Current I o - 87.9 mA
  • Max. permissible external capacitance C o for IIB - 0.705 μF
  • Max. permissible external capacitance C o for IIC - 0.090 μF
  • Max. permissible external inductance L o for IIB - 14.000 mH
  • Max. permissible external inductance L o for IIC - 2.300 mH
  • Max. Power P o - 574.000 mW
  • Max. voltage U i - 30.0 V
  • Max. Voltage U o - 27.00 V
  • Max. voltage U o isolation amplifier - 4.1 V
  • Safety-related maximum voltage - 253 V