Yodify Product Library
Add the Model M80XP Methane Monitor to your store or catalog
Book Your Demo and See How
or create your store
Model M80XP Methane Monitor
Brand: Envent Engineering LtdThe M80XP infrared gas sensor has been designed for easy integration into a wide range of gas detection systems where high quality, long term stability, excellent repeatability and reliable measurement of Methane gas concentrations are required.
These features can be attributed to a proprietary dual wavelength, fail to safe, infrared (NDIR) sensor technology.
The M80XP provides solutions for measuring and analyzing both industrial and environmental gases.
Features- Class I, Division 1
- Dual-Beam NDIR Technology
- Long-term stability
- Low power consumption (2 watts)
- Dual alarm outputs
- 4-20 mA output
- RS-232 and RS-485 Modbus communications
- Two Adjustable set point control relays
- Natural gas and Biogas application specific sensors available
- Field replaceable IR Source
Benefits:
- Quick delivery on standard systems
- Full service & training
- Available with differing sample systems and accessories as required in various applications
Specifications
Brand
Operating Power
- 24 VDC standard
- 12 VDC, 120/240 VAC optional
Sensing Cell Proof Pressure
- 5 to 25 psig
Measurement Range
- 0–20% Standard
- 0-100% Optional
Repeatability
- ± 0.1 % of reading
Drift
- Less than 2.5% of reading/year
Accuracy
- ± 3% of reading or 0.1% CO2 at cal temperature
- ± 5% of reading or 0.1% CO2 over full operating temperature range
Warmup Time
- < 5 min
Operating Temperature
- 10° to 50° C (standard)
Storage Temperature
- -20° to 60° C (-4° to 140° F)
Humidity
- Sensing Cell: 0–100% RH (Non-condensing)
- Electronics: 0 – 90% RH (Non-condensing)
Digital Interface
- RS-232 (all parameters)
Output
- Analog: Isolated 4–20 mA (concentration only)
- Alarm: 2 solid state drivers 2 Amp, 30 VDC maximum
Certifications and Approvals
- COR
- ISO
- cETLus
- CH4 Is Measured Routinely in Natural Gas for Product Quality and Process Control Purposes. Common Ranges Are from 0-5% for Sales Gas and Up to 0-30% for Inlet CH4 Concentration
- Biogas Plants:
- Wastewater Facilities
- Agriculture/Farming
- Green Waste