TC-10B ON/OFF Power-Line Carrier (REPLACED BY UPLC-II)
Brand: PulsarTC-10B ON/OFF Power Line Carrier is one of the most reliable and economical choices available for pilot relaying applications.
Features- Reliable - proven by more than fifty years of field experience at Electric Utilities all over the world
- Economical - uses the power line itself as the medium, eliminating expensive alternatives such as microwave, leased circuits or fiber optics
- Fully Frequency Programmable
- Rotary Switches
- Direct Frequency Readout
- 30 to 535 kHz (Steps of 0.1 kHz)
- Minimal effort to change frequency
- Frequency easily identified w/o binary conversions
- No cost to change frequencies now or in the future
- Common Modules on TC-10B and TCF-10B
- Power Supply
- Transmitter
- Receiver
- RF Interface
- 10 watt Power Amplifier
- Voice Adaptor
Specifications
Brand
Frequency Range
- 30-535 kHz in 0.5 kHz (500 Hz) Steps, Transmitter Selection in 100 Hz Steps
4-Wire Receiver Input Impedance
- 5,000 ohms or 1,000 ohms
RF Input Impedance
- 50 Ω, 75 Ω or 100 Ω (Nominal Unbalanced)
Output Power
- 10 Watts (max)
Frequency Stability
- ± 10 Hz (Typical)
Nominal Receiver Bandwidths
- Narrow Band: (800 Hz at 3 dB points)
- Wide Band (1600 Hz at 3 dB points)
- On-Off Phase Comparison (3,500 Hz at 3 dB points)
Harmonic Distortion
- 55 dB Below Full Power
Receive Sensitivity (Narrow or Wide Band)
- 22.5 mV (min) to 70 V (max) Standard Setting
- 5 mV (min) to 17 V (max) High Setting
Channel Speed at 15 dB Margin, Solid State Output
- Narrow Band (800 Hz): 3.8 ms (Pickup), 6.0 ms (Dropout)
- Standard (Wide) Band (1,600 Hz): 2.4 ms (Pickup), 3.8 ms (Dropout)
- Phase Comparison Band (3,500 Hz): 1.3 ms (Pickup), 1.5 ms (Dropout)
System (Minimum Channel Spacing)
- Wideband: 4 kHz
- Narrow Band: 2 kHz
- With Voice Adapter: 4 kHz
- Phase Comparison: 4 kHz
- An External Hybrid or Other Device Offering at Least 20 dB Rejection of the Adjacent Channel must be used in the Application
Keying
- Carrier Start, Carrier Stop Auxiliary (Reduced Power) Keying: All Optically Isolated for Operation at 15 V, 48 V, 125 V, or 250 Vdc, Strappable for either presence or Absence of Voltage for Keying, as well as Carrier Start or Stop Priority (Max. Burden is 20 mA)
- Manual Keying: Recessed Push Button Switches for Carrier Start and Auxiliary Keying
Receiver Output
- Two Independent Relaying Outputs: Outputs (Fully Isolated) provide up to 1 A Transistor Switch for Microprocessor Relaying or 200 mA (into 24 ohms), 20 mA (into 2,200 ohms), will operate from any Battery Supply (20 to 280 Vdc)
- One Receive Alarm Output (Detect): One Form A 100 VA, 125 Vdc (maximum)
- One Carrier Level Output: 0-100 μA for External Indicator
Alarm & Level Option
- Alarm Contacts (DC Power Loss RF “ON”, and Receive at Margin, 3 Separate Relays): Form A or B Contacts (Field Strappable) Rated 100 VA, 0.5 sec. of Dropout Delay
- Carrier Level Indication Meter: -20 dB to +10 dB
Voice Adapter Option
- Modulation: Amplitude Modulation with Compandor
- Transmission: Half-Duplex
- Frequency Response: 300 Hz to 2 kHz
- Signaling: Carrier Alarm
Environmental
- Ambient Temperature Range of Air: -20 to +60° C (Derated per Table 1-9 in System Manual) (ANS C37.90)
- Relative Humidity: Up to 95 % (Non-Condensing) at 40° C (for 96 hrs. Cumulative) (ANS/UL 508)
- Altitude: Up to 1,500 m (Without Derating), 6,000 m (Using Table 1-8 & 1-9 in System Manual)
- SWC and FAST Transient: All External User Interfaces meet SWC and FAST Transients of ANS C37.90.1 & IEC 255-6
- Dielectric: Only Isolated Inputs and Outputs, and all Alarms: 2,500 Vdc from each Terminal to Ground Derated per Table 1-8 in System Manual (IEC 255-5)
- Center Conductor of Coaxial Cable to Ground: 3.000 Vdc Impulse Level, Using 1.2 x 50 msec Impulse
- Electro-Magnetic Interference Compatibility: IEEE Standard (ANS C37.90.2)
Documentation
Data Sheets
Manuals
- CC44-VER02 TC-10B-ON/OFF PLC System Manual pdf 10.0 MB
- CC44-VER03 TC-10B-ON/OFF PLC System Manual pdf 4.0 MB
- CC44-VER04 TC-10B-ON/OFF PLC System Manual pdf 4.1 MB
- CC44-VER05 TC-10B-ON/OFF PLC System Manual pdf 2.8 MB
- CC44-VER06 TC-10B-ON/OFF PLC System Manual pdf 4.5 MB
- CC44-VER07 TC-10B-ON/OFF PLC System Manual pdf 2.7 MB
Product Advisory Letters
- C046-03002 No Alarm on PLC Power Supply When DC Voltage Output Fails (Low Criticality) pdf 15 KB
- C046-15001 TC-10B/TCF-10B and 50/100W LPA Product Obsolescence Notice (Medium Criticality) pdf 52 KB
- C046-95001 Transmitter Outputs Wrong Frequency or Shuts Down During High Temperature (High Criticality) pdf 29 KB
- C046-96001 10 Watt PA Fails During High Transient or Surge Conditions (High Criticality) pdf
- C046-97001 Receiver Output Failure if TB1-2 or RB1-5 is Connected to Station Battery Negative (High Criticality).pdf 29 KB
- C046-97002 Receiver's Output Varies When Frequency Switches Changed (High Criticality) pdf
- CC46-00002 Phase Comparison Trip Positive and Negative Ratios not Equal (Medium Criticality) pdf 31 KB
- CC46-03001b Universal Check Back not Functioning Reliably (Medium Criticality) pdf 140 KB
- CC46-99002a Drop Out delay too Long for Transmitter, CLI Meter and Output Fluctuates (High Criticality) pdf 32 KB