Yodify Product Library
Instantly add the Temperature Input Module for Zone 1 Series 9482/32 and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

Temperature Input Module for Zone 1 Series 9482/32

Brand: R. STAHL AG

The series 9482 temperature input module for Zone 1 has eight channels for the Ex i operation of resistance temperature detectors with two-, three- or four-conductor connection and thermocouples. 

Sensors that comply with DIN, IEC and GOST are supported as well as resistance transmitters up to 10 kΩ and also joysticks for rapid four-channel operation. 

Earthed thermocouples can be connected. 

Cold junction compensation can be performed internally or externally.
Features
  • Eight channels for resistance temperature detectors, potentiometers, thermocouples, mV sensors and joysticks
  • intrinsically safe Ex ia inputs with line fault monitoring and LED error indication
  • module in Zone 1 can be hot swapped

1 - 1 of 1 Part Numbers
217643
217643
R. STAHL Remote I/O IS1+ Temperature Input Module for Zone 1 Ex I
Eight channels for resistance temperature detectors, potentiometers, thermocouples, mV sensors and joysticks

intrinsically safe Ex ia inputs with line fault monitoring and LED error indication

module in Zone 1 can be hot swapped

Ambient Conditions

  • Ambient temperature - -40°C ... +75°C
  • Ambient temperature max. - +75°C
  • Ambient temperature min. - -40°C
  • Max. operating height - < 2000 m
  • Max. relative humidity - 95% (without condensation)
  • Note - (observe operating instructions)
  • Storage temperature - -40°C ... +80°C
  • storage temperature °C - -40 - 80 °C
  • Storage temperature max. - +80°C
  • Storage temperature min. - -40°C

Auxiliary power

  • Auxiliary power Version - Intrin. safe Ex ia via BusRail
  • Current consumption - 42 mA
  • Max. power consumption - 1.00 W
  • Max. power dissipation inputs - 1.0 W
  • Power consumption max. - 1.00 W
  • Power supply connection - BusRail types 9494

Device Specific Data

  • AT_ST00265 - see table (connectable sensors)
  • In. behaviour in case of error - hold last value
  • Infl. of ambient temperature - 0,025 % / 10 K
  • LED channel error - LED for each channel, red
  • LED group error - "ERR" LED, red
  • LED operating state - "RUN" LED, green
  • LEDmodule requires maintenance - "M/S" LED, blue
  • Line fault monitoring - OFF ON
  • Module diagnostics message - OFF ON
  • Module status and alarms - Internal bus error primer / redundant No response from IOM Configuration does not correspond to the module Hardware error Excess temperature Slot error Module requires maintenance
  • operating mode - 4 channel fast (joystick) 8 channel precise
  • Ref. junction compensation - internal (adjust. parameters) external 3-wire circuit
  • Retrievable parameters - hardware revision manufacturer serial number software revision type
  • Short circuit input - resist. transmitter < 15 Ω resist. temp. detec. < 15 Ω
  • Signal status bit - 1 = Signal valid 0 = Signal interrupted
  • Type external reference - PT1000 PT100 GOST PT100
  • Type of connection - 2-, 3- and 4-wire circuits
  • Wire breakage input - thermocouple > 1000 Ω resist. transmitter > 100 Ω resist. temp. detec. > 100 Ω mV sensor > 1000 Ω

Electrical Data

  • Measuring range - shortfall exceeding
  • Number of channels - 8 or 4 Ex i inputs (depending on operation mode)

Explosion Protection

  • Ambient temperature °C - -40 - 75 °C
  • Application range (Zone) Note - A suitable enclosure in accordance with the area of application must be used. Refer to the operating instructions.
  • Application range (zones) - 1, 2, 21, 22
  • ATEX dust certificate - DEKRA 13 ATEX 0140 X
  • ATEX gas certificate - DEKRA 13 ATEX 0140 X
  • Certificates - ATEX (DEK), Brazil (ULB), Canada (FM), EAC (STV), IECEx (DEK), Korea (KTL), Russia (Meteorological certificate), USA (FM)
  • Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
  • Dust explosion protection IECEx - [Ex ia Da] IIIC
  • Ex interface zone - 0, 1, 2, 20, 21, 22
  • Gas explosion protection ATEX - II 2 (1) G Ex ia [ia Ga] IIC T4 Gb
  • Gas explosion protection IECEx - Ex ia [ia Ga] IIC T4 Gb
  • IECEX dust certificate - IECEx DEK 13.0046X
  • IECEX gas certificate - IECEx DEK 13.0046X
  • Installation - Zones 1, 2, 21, 22 and in the safe area
  • Ship approval - ABS, CCS, ClassNK, DNVGL, RINA

Galvanic isolation

  • Aux. power/system components - ≥ 1500 V AC
  • I/O channels / ground (PA) - ≥ 500 V AC
  • I/O channels/system components - ≥ 500 V AC
  • I/O module / I/O module - ≥ 500 V AC
  • Test volt. for gal. separation - acc. to standard EN 60079-11

General

  • Functional Description - The series 9482 temperature input module for Zone 1 has eight channels for the Ex i operation of resistance temperature detectors with two-, three- or four-conductor connection and thermocouples. Sensors that comply with DIN, IEC and GOST are supported as well as resistance transmitters up to 10 kΩ and also joysticks for rapid four-channel operation. Earthed thermocouples can be connected. Cold junction compensation can be performed internally or externally.
  • Highlights - Eight channels for resistance temperature detectors, potentiometers, thermocouples, mV sensors and joysticks intrinsically safe Ex ia inputs with line fault monitoring and LED error indication module in Zone 1 can be hot swapped
  • Product Description - Remote I/O IS1+ Temperature input module For Zone 1 Ex i
  • Product Type - 9482/32-08-11
  • Title Product Variant Technical Data - 9482/32-08-11 TIM 08 Z1 LED
  • WebCode - 9482A

Input

  • Connection type 1 - 2-, 3- and 4-wire circuits
  • Connection type 2 - 2-wire circuits
  • Input resistance - max. 10 MΩ per channel
  • Linearity 1 (adj. parameters) - resistance linear temperature linear
  • Linearity 2 (adj. parameters) - voltage linear temperature linear
  • Max. input measuring range - +80 °C
  • Max. line resistance - 100 Ω per wire
  • Measurement accuracy - ± 1 % (4 channel fast) 0.025 % (8 channel precise)
  • Measuring current - < 200 μA multiplexed
  • Min. input measuring range - -40 °C
  • Resistance range - 0 - 10
  • Resolution - 0.1 K
  • Sensor type 1 - resistance temp. detector resistance transmitte
  • Sensor type 2 - thermocouples mV sensors
  • Signal range inputs - -10 ... +100 mV

Mechanical Data

  • Degree of protection IP (IEC 60529) - IP 20
  • Fire resistance (UL 94) - V2
  • Height - 67.000 mm
  • Length - 128.000 mm
  • Module enclosure - Polyamide 6GF
  • Pollutant class - Corresponds to G3
  • Weight - 0.275 kg
  • Width - 96.500 mm

Mounting / Installation

  • Mounting position - vertical horizontal
  • Mounting type - on DIN rail NS 35/15
  • Mounting type 2 - (DIN EN 60715)

Safety Data

  • Internal capacitance C i - negligible
  • Internal inductance L i - negligible
  • Notes - For proof of intrinsic safety, the safety data must be used in accordance with the combination of connections and the corresponding sensor. For further information and combination, see operating instructions.