Yodify Product Library
Instantly add the ZIRCOMAT Zirconia Oxygen Analyzer and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

ZIRCOMAT Zirconia Oxygen Analyzer

Brand: MicroMod Automation & Controls

Controlling excess oxygen in the flue gas to reduce fuel consumption is a well established control tool that’s well understood by energy management and process engineers worldwide. Field proven in over 25 years of service, the revolutionary, modular ZIRCOMAT system provides important installation, operation and service benefits when compared to other analyzers of conventional design.
Features
  • Direct insertion system eliminates gas sampling devices 

  • High-speed response 

  • Modular detector design for easy field replacement of zirconia element 

  • One-person maintenance, even with long probes 

  • High reliability, high system availability 

  • Twelve programmable alarm functions including fuel rich mode
  • 1 - 1 of 1 Part Numbers
    ZIRCOMAT
    ZIRCOMAT
    • Base Instrument - ZKM Transmitter with ZFK Oxygen Detector
    • Probe Type - Oil or Gas Applications, Flue Gas Temperatures Up to 621° C (1,150° F) (304 Stainless Steel or 316 Stainless Steel)
    • Probe Length - 40" (101.6 cm) - ZTA Probe
    • Transmitter Options - No Transmitter Options
    • Connecting Cable - 20 feet (6.1 meters) with Terminals. Supplied without Flexible Conduit
    • Optional Equipment - No Optional Equipment
    1 - 1 of 1 Part Numbers

    Specifications

    Accuracy

    • ± 1 %
    • 0.05%

    Ambient Temperature Range

    • -10° to 55° C (15° to 130° F)

    Approvals & Certifications

    • EN 15267-1
    • ISA

    Approvals & Certifications

    • CE
    • FM (C,US)
    • IEC
    • NEC
    • TÜV 25932 / 2010

    Calibration

    • Span: 20.6 to 21 % O₂
    • Zero: 0.25 to 2 % O₂

    Communication

    • RS-485 Modbus (Option)

    Consumption

    • 250 VA, Max.
    • 70 VA (Normal)

    Display

    • LCD Display

    Electrical Contacts

    • Alarm Contacts: 3 A at 250 V
    • Normally Open

    Environmental Protection

    • IP66
    • NEMA 4X

    Humidity

    • 95 % Relative Humidity, Non-Condensing

    Linearity

    • ± 2 % of Full Scale

    Measuring Range

    • 0.2 to 50 % Configurable in 1.0 % Steps

    Mounting

    • Flush
    • Horizontal Plane ± 45°
    • Panel Mount
    • Pipe Mounting Kit
    • Wall Mounting

    Operating Temperature

    • -20° to 100° C (-4° to 212° F)

    Output

    • 4-20 mA Isolated, 500 ohms, Max.

    Power Supply

    • 90-100 Vac, 50/60 Hz

    Process Temperature

    • -20° to 1,500° C (-4° to 2,732° F) (High Temperature)
    • -20° to 600° C (-4° to 1,112° F) (General Use)

    Repeatability

    • ± 0.5 % of Full Scale / Max.

    Response Time

    • 7 seconds

    Sensor, Probe Material

    • 304 Stainless Steel
    • 316 Stainless Steel

    Storage Temperature

    • -20° to 70° C (-4° to 158° F)
    • -30° to 70° C (-22° to 158° F)

    Tube Connection

    • 1/4” Tube Fitting

    Wetted Materials

    • 316 Stainless Steel