GPL 10000 Odorization System
Brand: GPL OdorizersThe GPL 10000 is intended for high-pressure and high-volume applications at transmission companies and large city gate stations.
The odorizer has high rangeability, achieving precision odorization over a wide operating range of volume.
The industry-leading programmable logic controller (PLC) interfaces with the flow meter and its system components to maintain constant odorant injection proportional to the gas flow rate.
FeaturesA closed-loop system means no gas or odorant discharges to atmosphere
- No smell during operation and maintenance
- Lowers false leak calls and complaints
- Eco-friendly; better for the environment
Does not use gas to actuate the system
- Saves pipeline gas
Continuous odorant injection proportional to the gas flow rate
- Eliminates under or over-odorization issues
- Accurate and reliable odorant injection
High rangeability (100:1 turndown ratio)
- Odorization over a wide range of flows
Few moving parts
- Simple operation
- Low maintenance
- Long-lasting performance
- No smelly pneumatic pumps to replace or maintain
Dual stroke electric-powered bellows pump
- Back up if one pump ever fails
Modular solid-state manifold
- Easy to replace and work on
Industry-leading PLC with large (7”), intuitive, color touchscreen and SD card data storage (Spanish mode available upon request)
- Easy to learn and operate
- The data stores on PLC SD Card permitting accessible audit-trail reports for regulatory or company inspections
- Communicates real-time critical alarms and soft alarms (maintenance reminders)
- Allows for Modbus (SCADA)
PLC Interfaces with SCADA Systems
- SCADA systems save time and energy, increase reliability, reduces cost, improves worker safety, higher customer satisfaction, and improves utilization.
Wireless modem
- Remote communication (using a wireless modem or Modbus) permits real-time mobile alerts and online monitoring to mobile phones and computers to prevent small problems from becoming big ones and speeds up restoration time.
Easy-to-use software provided
- No additional software required
Class I Division 2, Groups C and D
- Adheres to standards
Specifications
Brand
Weight
- 194 lb (88 kg)
Power
- Typical: 24 Vdc, 0.036 HP, 27.05 W
- Maximum: 24 Vdc, 0.193 HP, 124.8 W
- Optional: AC
Gas Pipeline Pressure
- Up to 1480 psi (102 bar)
Odorant Blanket Pressure
- 20 psi (1 to 2 bar)
Data Logging
- Hourly archives with audit trail, FTP data retrieval, internal micro SD storage
Enclosure
- 304 Stainless Steel
Hazardous Area Classification
- Class I, Div. 2, Groups C and D
Overall Dimensions
- 32½” (H) x 25⅝” (W) x 10⅞” (D), 82.55 cm x 65.09 cm x 27.62 cm
Odorant Injection Rate, Continuous
- From 2.4 MMSCFD to 240 MMSCFD(at an injection rate of 0.5 lb/MMSCFH)
Odorant Injection Rate, Batch
- From 480 MSCFD to 2.4 MMSCFD(at an injection rate of 0.5 lb/MMSCFH)
Connections
- Myers hub: (2) ¾ in NPT, (1) ½ in NPT Odorant outlet, odorant return, odorant inlet: ¼ in comp
Operating Temperature Range
- 0° to 140 ̊F (-18° to 60° C)
- Optional: Heater assembly available for below 0° F (-18° C)
User Interface Options
- 320 x 240 LCD Color Graphics Display with Touch Screen
- IP Remote Communication