Yodify Product Library
Instantly add the CCR2 Controller and 50,000+ more product series to your store or catalog  
Book Your Demo and See How
or create your store

The CCR2 is a control used for optimising the thermal disinfection process in hot water systems with functions such as temperature registration or monitoring circulation hot water systems. 

The CCR2 can be applied independently, only for temperature registration in circulation hot water systems. 

The CCR2 incorporates LCD display and four manual switches, which allow the user to manually set and monitor measured parameters from the system. 

In addition, the CCR 2 also incorporates memory cash for SD card to store temperature data. The system monitoring function is based on temperature registration and storage of data in the SD card.

1 - 1 of 1 Part Numbers
 003Z3850
003Z3850
DANFOSS CCR 2 Controller: Disinfection Process Control Temperature Registration, Supply Voltage 24 Vac, Actuator NC/16
1 - 1 of 1 Part Numbers

Specifications

Brand

Accuracy

  • Temperature Accuracy: ± 0.5 K

Ambient Temperature Range

  • 0° to 50° C (32° to 122° F)

Battery Life

  • 10-Years

Communication

  • FOUNDATION Fieldbus (Fbus)
  • Modbus RTU
  • RS-485 for Connecting CCR2 to BMS System
  • USB

Consumption

  • Power Consumption: 6 VA

Display

  • LCD Display & 4 Manual Switches

Electrical Contacts

  • Normally Closed

Environmental Protection

  • IP20

Input

  • Free Contact Relay (5 V, 1 mA) - for B0 & B1

Mounting

  • DIN Rail 35 mm

Output

  • 24 Vac, Max.
  • Output OC: 0-20 Vdc NPN Open Collector, Max.

Power Supply

  • 24 Vac, 50 Hz

Relay Output

  • 0 to 24 Vac/Vdc, Max.

Sensor / Probe Type

  • Pt1000

Temperature Range

  • -10° to 60° C (14° to 140° F) - Transport Temperature
  • -20° to 120° C (-4° to 248° F)
  • 50° to 80° C (122° to 176° F) - Temperature of Disinfection

Documentation

Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more