Yodify Product Library
Add the RY1 Relay Input Card to your store or catalog  
Book Your Demo and See How
or create your store

This unit receives contact signal from the field and outputs 2 contact signals (1 for use of DCS status card input and the other is re-transmit contact signal) isolated electrically from the field. One unit stores 2 channels.
Features
  • Output contact consists of 2 contacts; 1 for DCS contact and the other for re-transmit contact (transfer contact) of current capacity 1A
  • Electrically isolated between field input and power supply since DC/DC converter for relay driving power supply is installed
  • Furnished with test switch convenient for debugging of DCS or checking operation and LED for status display

1 - 2 of 2 Part Numbers
RY1-10
RY1-10
  • Relay Output - Output 1: A Contact (Output Through Connector) / Output-2: (Re-Transmit Output) Transfer Contact
  • Test Switch - No Test Switch
RY1-11
RY1-11
  • Relay Output - Output 1: A Contact (Output Through Connector) / Output-2: (Re-Transmit Output) Transfer Contact
  • Test Switch - With Test Switch
1 - 2 of 2 Part Numbers

Specifications

Alarm

  • Output Non-Voltage Contact from Alarm Terminal when Power Fuse Break

Ambient Temperature Range

  • 0° to 50° C (32° to 122° F)

Dissipation

  • 70 mA at 24 Vdc - Current Dissipation

Electrical Connectors

  • M3.5 Screw Terminal - Output-2 (Re-Transmit Output) & Input

Electrical Rating

  • 0.2 A at 125 Vac, 0.5 A at 30 Vdc - Output-2 Inductance Load
  • 0.2 A at 30 Vdc (Both Resistance & Inductance Loads) - Output-1
  • 0.4 A at 125 Vac, 1 A at 30 Vdc - Output-2 Resistance Load

Humidity

  • 5 to 90 % RH - Normal Operating Conditions
  • 5 to 95 % RH, Non-Condensing - Operating Limit/Storage Conditions

Indication

  • LED - Light on (Green) when Relay Magnetized

Input

  • Non-Voltage Contact
  • Open Collector

Input Signal

  • 24 Vdc, more than 30 mA

Insulation Resistance

  • 100 MΩ at 500 Vdc between Input, Output-1, Output-2, Alarm Contact Output

Mounting

  • M3 Screws
  • Nest-Mounting

Operating Temperature

  • -10° to 60° C (14° to 140° F)

Operating Voltages

  • 125 Vdc - Max.
  • 250 Vac - Max.

Power

  • 0.5 A Alarm Fuse

Screw Material

  • Nickel-Plated-Iron

Storage Temperature

  • -40° to 70° C (-40° to 158° F)

Supply Voltage

  • 1,500 Vac/minute between Input, Alarm Contact Output, Output-1, Output-2, Power Supply - Withstand Voltage
  • 24 Vdc ± 10 % (Ripple Content Below 10 % Peak-to-Peak)
  • 500 Vac/minute between Input, Alarm Contact Output - Withstand Voltage

Torque

  • Below 6.94 in/lb - Fastening Torque

Instantly populate your store or catalog 
CREATE YOUR SITE
or book a demo with the Yodify Team
show more