Brand: Yokogawa Electric CorporationThe EJA-E series of transmitters is Yokogawa's most recent evolution of the DPharp family.
Released in 2012, it combines the ruggedness and success of the work-horse EJA-E series with the performance of the thoroughbred EJX-A series to deliver the type of product you have come to expect from Yokogawa.
The EJA310E is our traditional-mount absolute pressure transmitter in the series.
Features- ± 0.1% Accuracy
- ± 0.2% Stability for 10 years
- 90 ms Response Time
- Exida and TUV SIL 2/3 Certified
- 3,600 psia Maximum Over Pressure (MWP)
- Local Parameter Setting (LPS)
Available with HART 5/7, 1 to 5 VDC HART 7 (Low Power), FOUNDATION Fieldbus, PROFIBUS PA, or BRAIN communication.
Specifications
Accuracy
- ± (0.045 + 0.009 URL/Span) % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability)
- ± (0.062 + 0.0038 URL/Span) % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability)
- ± (0.095 + 0.0297 URL/Span) % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability)
- ± 0.1 % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability)
- ± 0.15 % of Span (Includes Terminal-based Linearity, Hysteresis, & Repeatability)
Alarm
- Down-Scale: -5 %, 0.8 Vdc or Less - for 1-5 V HART
- Down-Scale: -5 %, 3.2 mA DC or Less - for Output 4-20 mA HART/BRAIN
- Up-Scale: 110 %, 21.6 mA DC or more - for Output 4-20 mA HART/BRAIN
- Up-Scale: 110 %, 5.4 Vdc or more - for 1-5 V HART
Ambient Temperature Range
- -30° to 80° C (-22° to 176° F) with LCD Display
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- SIL 2 Capability for Single Transmitter Use, SIL 3 Capability for Dual Transmitter Use & IEC 61508: 2000, Part1 to Part 7
Approvals & Certifications
- ATEX - Flameproof & Intrinsically Safe
- CSA - Explosion-proof & Intrinsically Safe
- EMC - EN 61326-1 Class A (Industrial Locations), EN 61326-2-3 & EN 61326-2-5 (Fieldbus)
- FM - Explosion-proof & Intrinsically Safe
- IEC 61518 - Process Connection of Cover Flange
- IECEx - Flameproof Approval & Intrinsically Safe
- NAMUR NE43
BSP Connection
- 1/2” BSPT Female
- 1/4” BSPT Female
Burst Pressure
- psi: 10,000 (kPa: 68,950, bar: 689)
Communication
- BRAIN
- FOUNDATION Fieldbus
- HART
- PROFIBUS PA
Consumption
- 0.96-3 mA, 27 mW - Power Consumption
Damping Adjustment
- 0 to 100 seconds
Diagnostics
- Configuration Error
- CPU Failure
- Hardware Failure
- Process Alarm for Pressure or Capsule Temperature
Diaphragm Material
- Hastelloy C-276
Display
- 5-Digit Numerical Display
- 6-Digit Unit Display
- Bar Graph
- LCD Display
- User-Configurable 10-Segment Signal Characterizer
Distance
- Up to 2 Kilometers - Communication Distance
Drain, Vent Valves & Plug
- 316 Stainless Steel
Electrical Connectors
- 1/2” NPT Female
- G 1/2” Female
- M20 Female
Electrical Protection
- Lightning Protection as Per IEC 61000-4-4, IEC 61000-4-5
Enclosure Finish
- Anti-Corrosion Coating
- Polyurethane Paint - Deep Sea Moss Green Paint (Munsell 0.6 GY3.1/2.0 or its Equivalent)
Enclosure, Body Material
- Aluminum Alloy - Copper Cast
- ASTM CF-8M Stainless Steel
Environmental Protection
- IP66
- IP67
- NEMA 4X
Fill Material
- Fluorinated Oil
- Silicone
Flange Material
- ASTM CF-8M - Cover Flange
Gasket Material
- Fluorinated Rubber - Process Connector Gasket
- PTFE Teflon - Process Connector Gasket
- Teflon-Coated 316L Stainless Steel - Capsule Gasket
Humidity
- 0 to 100 % Relative Humidity - Ambient Humidity
Input Impedance
- 10 kiloohms at 2.4 kHz
Length
- Vent: 1.33 (34 mm) Standard
- Vent: 4.6” (119 mm)
Load
- 0 to 1,290 ohms - for Operation
- 0.22 μF or Less - Load Capacitance
- 250 to 600 ohms - for Digital Communication
- 3.3 MH or Less - Load Inductance
Materials of Construction
- 304 Stainless Steel - Mounting Bracket
- 316 Stainless Steel - Name Plate & Tag, Mounting Bracket & Exterior Parts (Screws & Setscrews)
Mounting
- 2” (50.8 mm) Pipe Mounting Bracket
Mounting Position
- Horizontal
- Universal
- Vertical
Mounting Position Effect
- Tilting up to 90 Degree will cause Zero Shift up to 0.5 kPa
NACE & NIST
- NACE MR-0103
- NACE MR-0175, ISO 15156
NPT Connection
- 1/2” NPT Female
- 1/4” NPT Female
Nut & Bolt Material
- 316L Stainless Steel
- 660 Stainless Steel
- B7 Carbon Steel
O-Ring Material
- Buna-N - Cover O-Ring
- Fluororubber - Cover O-Ring
Output
- 0.9-5.4 Vdc - HART
- 1-5 Vdc (3 or 4-Wire)
- 3.6-21.6 mA
- 4-20 mA DC (2-Wire)
Output Load
- 1 Megaohm or Greater
Overpressure & Static Pressure Limits
- psia: 2,300 (MPa: 16, bar: 160) - Max.
- psia: 3,600 (MPa: 25, bar: 250) - Max.
- psia: 72 (kPa: 500, bar: 5) - Max.
Power Supply
- 9-28 Vdc - General Use & Flameproof Typical (For 1-5 V HART)
Power Supply Effect
- ± 0.005 % Per Volt (From 21.6 to 32 Vdc, 350 ohms)
Pressure Range
- bar: 0 to 160
- Inches Hg: 0 to 38
- kPa: 0 to 16,000
- mmHg: 0 to 970
- psi: 0 to 2,300
Pressure Type
- Absolute
Process Connection Material
- ASTM CF-8M Stainless Steel
Process Temperature
- -40° to 100° C (-40° to 212° F) - L Capsule
- -40° to 120° C (-40° to 248° F) - M, A & B Capsules
Response Time
- 90 milliseconds
Stability
- ± 0.1 % of URL Per Year
Supply Pressure - Maximum
- psia: 1.45 (kPa: 10, bar: 0.1) - Capsule L
- psia: 18.8 (kPa: 130, bar: 1.3) - Capsule M
- psia: 2,300 (MPa: 16, bar: 160) - Capsule B
- psia: 500 (MPa: 3.5, bar: 35) - Capsule A
Supply Voltage
- 10.5-30 Vdc - for Intrinsically Safe, Typical N, or Non-Incendive
- 10.5-32 Vdc - for Lightning Protector
- 10.5-42 Vdc - for General Use & Flameproof Typical
- 16.6 Vdc - Min. Voltage for Digital Communications, BRAIN & HART
- 24 Vdc Supply, up to 550 ohms
Temperature Effect
- ± (0.06 % of Span + 0.012 % of URL) Per 28° C (50° F) - Ambient Temperature Effect (Capsule A & B)
- ± (0.06 % of Span + 0.035 % of URL) Per 28° C (50° F) - Ambient Temperature Effect (Capsule M)
- ± (0.12 % of Span + 0.35 % of URL) Per 28° C (50° F) - Ambient Temperature Effect (Capsule L)
Update Time
- 45 milliseconds
Vibration Effect
- < ± 0.1 % of URL as Per IEC 60770-1 Pipeline with Low Vibration Level (10-60 Hz 0.15 mm Displacement / 60-500 Hz 2 G)
- < 0.1 % of URL as Per IEC 60770-1 Pipeline with High Vibration Level (10-60 Hz, 0.21 mm Displacement / 60-2,000 Hz 3 G)
Wetted Materials
- 316L Stainless Steel
- F316L Stainless Steel
Zero Offset
- 0.01 % Incremental Resolution of Span - External Zero Adjustment
Documentation
Data Sheets
Brochure
Certificate
Manual
- Differential Pressure and Pressure Transmitter pdf 6.3 MB
- DPharp BRAIN Communication Type pdf 2.7 MB
- DPharp Fieldbus Communication Type pdf 3.7 MB
- DPharp HART 5/7 Communication Type pdf 12.2 MB
- DPharp PROFIBUS PA Communication Type pdf 6.2 MB
- EJX and EJA-E Series Differential Pressure and Pressure Transmitters Installation Manual pdf 7.2 MB
- EJX/EJA-E series NEPSI Certification[Option code: /NF2, /NF21, /NS21, /NS24 and /NS25] pdf 622 KB
- Manual Change 22-24E: EJX-A and EJA-E Series Differential Pressure and Pressure Transmitters pdf 186 KB
- Manual Change 22-25E: EJX/EJA-E series NEPSI Certification[Option code: /NF2, /NF21, /NS21, /NS24 and /NS25] pdf 312 KB