ITC-XX-BIO Isolated Bi-Polar Signal Conditioner
Brand: Pribusin, IncThe ITC-XX-BIO provides high isolation and surge withstand capability from Input to Output to Power in a small, easy to install package. The universal DIN rail mount often makes it possible to install the ITC-XX-BIO right next to the instrument that is to be isolated. The many different input and output configurations allow it to be used in a great variety of applications ranging from PLC front end conditioning to adding an extra loop with lots of drive to an existing, almost fully loaded, loop.
Uni-polar and Bi-polar input and output ranges are available for voltages from as low as +/-100mV to +/-10VDC.
Uni-polar input and output ranges are available for currents from 0 to 20mA
The surge withstand capability (SWC) complies with the IEEE C37.90.1.1989 standard.
Features- High Input-Output-Power Isolation (1500Vac Test).
- Bi-Polar Voltage and mV Input & Output Signal Ranges.
- Uni-Polar Current Ranges available also.
- Small Size - Fits on Terminal Block Rail.
- Industry Standard Inputs and Outputs.
- Power: 24 Vdc, 100 mA.
- High Noise Rejection.
- Complies with IEEE C37.90.1.1989.
Specifications
Brand
Accuracy, Linearity
- ± 0.1 % Max., ± 0.05 % Typical
Change Effects
- -0.03 % Per 100 ohms Change (4-20 mA Only) Calibrated at 250 ohms
Common Mode Rejection
- at 60 Hz = 120 dB
Coupling Capacitance
- Input-Output-Power less than 10 PF
Drift at 25° C
- 24 Hours: ± 0.03 % / 30 Days: ± 0.1 %
Input Impedance (4-20 mA Only)
- 50 ohms
Isolation
- 1500 Vac Input to Output to Power (Test)
Operating Temperature
- -40° to + 50° C
Power
- 24 Vdc (19-29 Vdc) at 100 mA / 140 mA if 2-Wire Supply is Used
Response Time
- 50 ms to 63 % of Final Value / 250 ms to 99 % of Final Value
SWC
- 3KV Peak, 1.5 MHz Damped Oscillation at 60 Hz
Temperature Effects
- ± 0.5 % Max., ± 0.2 % Typical for 40° C Change