G108-0001 DC Powered DC Input Limit Alarm
Brand: EurothermThe Ultra SlimPak G108 is a DIN rail mount, DC voltage or current input limit alarm with dual setpoints and two contact closure outputs.
The field configurable input and alarm functions offer flexible setpoint capability. Input voltage spans from 10 mV to 200 V and input current spans from 1-100 mA can be field configured. Bipolar inputs are also accepted.
The G108 is configurable as a single or dual setpoint alarm, with HI or LO trips and failsafe or non-failsafe operation.
Also included are adjustable deadbands (0.25% to 5% of full scale input) for each setpoint, a 24 Vdc voltage source (Isolated from line power) for transducer excitation, and a flexible DC power supply which accepts any voltage between 9 and 30 Vdc.
Features- Programmable HI or LO, failsafe or non-failsafe
- Field configurable input ranges
- 24 Vdc Transducer excitation
- LED Trip and input indicators
- Flexible power supply accepts 9 to 30 Vdc
- ASIC Technology for enhanced reliability
- RoHS Compliant
Specifications
Brand
Approvals & Certifications
- CE
- CSA C22.2, No. 0-M91 & 142-M1987 (File No. LR42272)
- EMC: EN 61326-1: 2013, Directive 2004/108/EC
- LVD 2006/95/EC
- RoHS
- UL 508 (File No. E99775)
- UR
Voltage Range
- 10 mV to +200 V
Stability
- +0.05 % of Full Scale/°C, Max.
Operating Temperature
- 0° C to 55° C
- 32° F to 131° F