Yodify Product Library
Instantly add the Digital Indicator for Panel Mounting - DI25 and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
Digital Indicator for Panel Mounting - DI25
Brand: WIKA Alexander Wiegand SE & Co. KGThe model DI25 digital indicator is a multi-function, competitively priced instrument for a wide variety of measuring tasks.
The basic version of the DI25 indicator features three alarm outputs. Instruments with the optional DC 24 V transmitter power supply have two alarm outputs available.
With the high IP66 ingress protection at the front, the DI25 digital indicator is also suitable for use under harsh environmental conditions.
All configuration and programming can be carried out through the front-panel keys.
Features- Multi-function input for current and voltage signals and thermocouples and resistance thermometers.
- Ingress protection IP 66 (front panel).
- two or three freely programmable alarm outputs as standard (depending on the instrument version).
- 4 ... 20 mA Analog signal output as standard.
- HOLD function.
Specifications
Principle
- 7-segment LED
Actual Value Display (PV Display)
- 4-1/2-Digit, Red, character size 16 mm
Set Value Display (SV Display)
- 4-1/2-Digit, Green, character size 10 mm
Indication Range
- 2000 ... 10000
Number & Type
- 1 x multi-function Input for resistance thermometers, thermocouples and Standard signals
Input Configuration
- Selectable via Terminal Connections and Menu-Driven Programming
Resistance Thermometers
- Pt100, JPt100, 3-Wire, Max. permissible resistance per connection lead: 10 Ω
Thermocouples
- Types K, J, R, S, E, T, N, PL-II, C (W/Re5-26): Max. permissible external resistance: 100 Ω
- Type B: Max. permisible external resistance: 40 Ω
Standard Signals (DC)
- 0 to 20 mA, 4-20 mA: Input Resistance 50 Ω
- Maximum 50 mA DC
- 0 to 1 V: Input Resistance > 1 MΩ, Max. 5 Vdc
- Maximum internal resistance of Voltage source: 2 k Ω
- 0 to 5 V, 1 to 5 V, 0-10 V: Input Resistance > 100 k Ω
- Maximum 15 Vdc, Maximum internal resistance of Voltage source: ,100 Ω
Measuring Time
- 125 milliseconds
Output Signal
- 4 ... 20 mA, load ≤ 550 Ω
Accuracy
- ± 0.3 % of the output Span
Transmitter Power Supply (Option)
- DC 24 V ± 3 V, Max. 30 mA
Power Supply
- AC/DC 24 V (Permissible Voltage: AC/DC 20 ... 28 V), 50/60 Hz
- AC 100 ... 240 V (Permissible Voltage: AC 85 ... 264 V), 50/60 Hz
Power Consumption
- Maximum 10 VA
Insulation Resistance
- Minimum 10 MΩ for DC 500 V
Electrical Connection
- Screw terminals
Alarm Types of Switching Outputs
- High Alarm
- High Alarm with Standby
- Low Alarm
- Low Alarm with Standby
- High-low Alarm (Only for switch Contact 3)
Switch Behaviour
- Normally closed or Normally Open, can be set via keyboard
Load Capacity
- AC 250 V, 3 A (Resistive load)
Switching Cycles
- Maximum 100,000
Hysteresis
- Adjustable
- Thermocouples and resistance thermometers: 0.1 ... 1,000° C
- Standard signals: 1 ... 1,000 (with a scaling of the Input with one decimal point, this is taken over by the hysteresis)
Hold Function
- Selectable: Instantaneous/minimum or Max. Value Activation of the HOLD function via Connection terminals
Case Material
- Polycarbonate, Black
Ingress Protection (per IEC / EN 60529)
- Front: IP66
- Read: IP00
Dimensions
- 96 x 48 x 110 mm
Weight
- Approximately 300 g
Mounting
- Screw-Type Mounting bracket for wall thicknesses from 1 ... 8 mm
Operating Temperature
- 0° to 50° C
Storage Temperature
- -20° to +50° C
Relative Humidity
- 35 ... 85 % Relative Humidity Annual mean without condensation
- Plant Construction
- Machine Tools
- Plastics Technology and Processing
- Ventilation and Air-Conditioning
- General Industrial Applications