Yodify Product Library
Instantly add the Isolating Repeater Input Series 9163 and 50,000+ more product series to yourĀ store or catalogĀ Ā
Book Your Demo and See How
or create your store
Isolating Repeater Input Series 9163
Brand: R. STAHL AGThe 9163 series isolating repeater for input signals can be used for the intrinsically safe operation of intrinsically safe power sources.
Features- Conversion of Ex i voltage signals in 0/4 ... 20 mA signals
- Can be used for safety levels up to SIL 2 (IEC/EN 61508)
1 - 6 of 6 Part Numbers
214910
Conversion of Ex i voltage signals in 0/4 ... 20 mA signals
Can be used for safety levels up to SIL 2 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 46.00 mA
- Nominal voltage - 24 V DC
- Polarity reversal protection - yes
- Power consumption - 1.10 W
- Power dissipation max. - 1.00 W
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 1
- Open-circuit voltage U a - ≤ 15,50 V
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 010 X
- ATEX firedamp certificate - DMT 03 ATEX E 010 X
- ATEX gas certificate - DMT 03 ATEX E 010 X
- Certificate EAC - TS RU S-DE.GB04.B.00132
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), Russia (Meteorological certificate), SIL (exida), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Firedamp protection ATEX - I (M1) [Ex ia Ma] I
- Firedamp protection IECEx - [Ex ia Ma] I
- Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 08.0050 X
- IECEx firedamp certificate - IECEx BVS 08.0050 X
- IECEX gas certificate - IECEx BVS 08.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
General
- Functional Description - The 9163 series isolating repeater for input signals can be used for the intrinsically safe operation of intrinsically safe power sources.
- Highlights - Conversion of Ex i voltage signals in 0/4 ... 20 mA signals Can be used for safety levels up to SIL 2 (IEC/EN 61508)
- Product Description - Isolating repeater input Ex i field circuit ISpac
- Product Type - 9163/11-81-10s
- Title Product Variant Technical Data - 9163/11-81-10s voltage repeater input
- WebCode - 9163A
Input
- Input - 0/1 to 5 V, 0/2 to 10 V
- Input functional range - 0 - 6 V / 0 - 12 V
- input signal - 0 - 5 V / 0 - 10 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.2-2.5 mm² rigid 0.25-2.5 mm² flexible core end sleeve
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.177 kg
Mounting / Installation
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - Rail (NS35/15, NS35/7.5)
Output
- deviation - ≤ 0,2 %
- LFD relay - No
- Load resistance R L - 0 ... 600 Ω (terminal 1+/2- resp. 5+/6-)
- Output - 0/4 ... 20 mA
- output signal - 0/4 - 20 mA
- Temperature influence error limits - ≤ 0,05 % / 10K
Safety Data
- Internal capacitance C i - negligible
- Internal inductance L i - negligible
- Max. current l i note - Internally limited
- Max. power P o note - negligible
- Max. power Pi note - Internally limited
- Max. voltage U i - 30.0 V
- Max. Voltage U o - 4.10 V
- Safety-related maximum voltage - 253 V
214911
Conversion of Ex i voltage signals in 0/4 ... 20 mA signals
Can be used for safety levels up to SIL 2 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... -60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - -60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 46.00 mA
- Nominal voltage - 24 V DC
- Polarity reversal protection - yes
- Power consumption - 1.10 W
- Power dissipation max. - 1.00 W
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- Number of channels - 1
- Open-circuit voltage U a - ≤ 15,50 V
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 010 X
- ATEX firedamp certificate - DMT 03 ATEX E 010 X
- ATEX gas certificate - DMT 03 ATEX E 010 X
- Certificate EAC - TS RU S-DE.GB04.B.00132
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), Russia (Meteorological certificate), SIL (exida), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Firedamp protection ATEX - I (M1) [Ex ia Ma] I
- Firedamp protection IECEx - [Ex ia Ma] I
- Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 08.0050 X
- IECEx firedamp certificate - IECEx BVS 08.0050 X
- IECEX gas certificate - IECEx BVS 08.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
General
- Functional Description - The 9163 series isolating repeater for input signals can be used for the intrinsically safe operation of intrinsically safe power sources.
- Highlights - Conversion of Ex i voltage signals in 0/4 ... 20 mA signals Can be used for safety levels up to SIL 2 (IEC/EN 61508)
- Product Description - Isolating repeater input Ex i field circuit ISpac
- Product Type - 9163/11-81-10k
- Title Product Variant Technical Data - 9163/11-81-10k voltage repeater input
- WebCode - 9163A
Input
- Input - 0/1 to 5 V, 0/2 to 10 V
- Input functional range - 0 - 6 V / 0 - 12 V
- input signal - 0 - 5 V / 0 - 10 V
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.177 kg
Mounting / Installation
- Connection type - Spring clamp terminal
- Mounting position - horizontal vertical
- Mounting type - Rail (NS35/15, NS35/7.5)
Output
- deviation - ≤ 0,2 %
- LFD relay - No
- Load resistance R L - 0 ... 600 Ω (terminal 1+/2- resp. 5+/6-)
- Output - 0/4 ... 20 mA
- output signal - 0/4 - 20 mA
- Temperature influence error limits - ≤ 0,05 % / 10K
Safety Data
- Internal capacitance C i - negligible
- Internal inductance L i - negligible
- Max. current l i note - Internally limited
- Max. power P o note - negligible
- Max. power Pi note - Internally limited
- Max. voltage U i - 30.0 V
- Max. Voltage U o - 4.10 V
- Safety-related maximum voltage - 253 V
214914
Conversion of Ex i voltage signals in 0/4 ... 20 mA signals
Can be used for safety levels up to SIL 2 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... -60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - -60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power nom. voltage - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 46.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.10 W
- Power dissipation max. - 1.00 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- communication signal - HART, 0.5 .... 10 kHz
- Isolating repeater mode - Yes
- Number of channels - 1
- Transmitter supply mode - No
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 010 X
- ATEX firedamp certificate - DMT 03 ATEX E 010 X
- ATEX gas certificate - DMT 03 ATEX E 010 X
- Certificate EAC - TS RU S-DE.GB04.B.00132
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), Russia (Meteorological certificate), SIL (exida), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Firedamp protection ATEX - I (M1) [Ex ia Ma] I
- Firedamp protection IECEx - [Ex ia Ma] I
- Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 08.0050 X
- IECEx firedamp certificate - IECEx BVS 08.0050 X
- IECEX gas certificate - IECEx BVS 08.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 1.5 kV AC
- Galvanic isolation Ex i input to output - 1.5 kV AC
- Galvanic isolation output to auxiliary power - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - The 9163 series isolating repeater for input signals can be used for the intrinsically safe operation of intrinsically safe power sources.
- Highlights - Conversion of Ex i voltage signals in 0/4 ... 20 mA signals Can be used for safety levels up to SIL 2 (IEC/EN 61508)
- Product Description - Isolating repeater input Ex i field circuit
- Product Type - 9163/13-11-10s
- Title Product Variant Technical Data - 9163/13-11-10s HART mA-repeater in
- WebCode - 9163A
Input
- Input - 0/4 ... 20 mA with HART
- Input current max. mA sources - 50 mA
- Input function - Isolation amplifier
- Input functional range - 0 - 24 mA
- Input open circuit voltage U a - ≤ 15,50 V
- Input resistance - ≤ 150 ohms
- Input resistance (AC) HART - ca. 300 Ω
- input signal - 0/4 ... 20 mA with HART
- short-circuit current - ≤ 35 mA
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.177 kg
Mounting / Installation
- Conduct cross-section flexible max. - 2.5 mm²
- Conduct cross-section flexible max. - 0.2 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Behaviour of the output - = input signal
- deviation - ≤ 0,1 %
- LFD relay - No
- Load R L max. with resistor - 379 Ω
- Load resistance R L - 0 ... 600 Ω (terminal 1+/2- resp. 5+/6-) 0 ... 479 Ω (terminal 3+/2- resp. 4+/6-) (with internal 221 Ω resistor for HART)
- Load resistance R L max. - 600.00 Ω
- Load resistance R L max. HART - 379 ohms
- Load resistance R L max. note - With internal 221 ohm resistor
- Output - 0/4 ... 20 mA with HART
- Output functional range - 0.0 - 24.0 mA
- Output residual ripple - ≤ 40 µAeff
- output signal - 0/4 ... 20 mA with HART
- Settling time 10 … 90 % - ≤ 100 µs
- Temperature influence error limits - ≤ 0,05 % / 10K
Safety Data
- Internal capacitance C i - negligible
- Internal capacitance C i isolating repeater - negligible
- Internal inductance L i - negligible
- Internal inductance L i isolating repeater - negligible
- Max. current I i - 150.0 mA
- Max. power P i - 1000.0 mW
- Max. power P o note - negligible
- Max. voltage U i - 30.0 V
- Max. voltage U o isolation amplifier - Negligible
- Safety-related maximum voltage - 253 V
214915
Conversion of Ex i voltage signals in 0/4 ... 20 mA signals
Can be used for safety levels up to SIL 2 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power nom. voltage - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 46.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.10 W
- Power dissipation max. - 1.00 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- communication signal - HART, 0.5 .... 10 kHz
- Isolating repeater mode - Yes
- Number of channels - 1
- Transmitter supply mode - No
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 010 X
- ATEX firedamp certificate - DMT 03 ATEX E 010 X
- ATEX gas certificate - DMT 03 ATEX E 010 X
- Certificate EAC - TS RU S-DE.GB04.B.00132
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), Russia (Meteorological certificate), SIL (exida), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Firedamp protection ATEX - I (M1) [Ex ia Ma] I
- Firedamp protection IECEx - [Ex ia Ma] I
- Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 08.0050 X
- IECEx firedamp certificate - IECEx BVS 08.0050 X
- IECEX gas certificate - IECEx BVS 08.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 1.5 kV AC
- Galvanic isolation Ex i input to output - 1.5 kV AC
- Galvanic isolation output to auxiliary power - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - The 9163 series isolating repeater for input signals can be used for the intrinsically safe operation of intrinsically safe power sources.
- Highlights - Conversion of Ex i voltage signals in 0/4 ... 20 mA signals Can be used for safety levels up to SIL 2 (IEC/EN 61508)
- Product Description - Isolating repeater input Ex i field circuit
- Product Type - 9163/13-11-10k
- Title Product Variant Technical Data - 9163/13-11-10k HART mA-repeater in
- WebCode - 9163A
Input
- Input - 0/4 ... 20 mA with HART
- Input current max. mA sources - 50 mA
- Input function - Isolation amplifier
- Input functional range - 0 - 24 mA
- Input open circuit voltage U a - ≤ 15,50 V
- Input resistance - ≤ 150 ohms
- Input resistance (AC) HART - ca. 300 Ω
- input signal - 0/4 ... 20 mA with HART
- short-circuit current - ≤ 35 mA
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.177 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Spring clamp terminal
- Mounting position - horizontal vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Behaviour of the output - = input signal
- deviation - ≤ 0,1 %
- LFD relay - No
- Load R L max. with resistor - 379 Ω
- Load resistance R L - 0 ... 600 Ω (terminal 1+/2- resp. 5+/6-) 0 ... 479 Ω (terminal 3+/2- resp. 4+/6-) (with internal 221 Ω resistor for HART)
- Load resistance R L max. - 600.00 Ω
- Load resistance R L max. HART - 379 ohms
- Load resistance R L max. note - With internal 221 ohm resistor
- Output - 0/4 ... 20 mA with HART
- Output functional range - 0.0 - 24.0 mA
- Output residual ripple - ≤ 40 µAeff
- output signal - 0/4 ... 20 mA with HART
- Settling time 10 … 90 % - ≤ 100 µs
- Temperature influence error limits - ≤ 0,05 % / 10K
Safety Data
- Internal capacitance C i - negligible
- Internal capacitance C i isolating repeater - negligible
- Internal inductance L i - negligible
- Internal inductance L i isolating repeater - negligible
- Max. current I i - 150.0 mA
- Max. power P i - 1000.0 mW
- Max. power P o note - negligible
- Max. voltage U i - 30.0 V
- Max. voltage U o isolation amplifier - Negligible
- Safety-related maximum voltage - 253 V
214920
Conversion of Ex i voltage signals in 0/4 ... 20 mA signals
Can be used for safety levels up to SIL 2 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... -60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - -60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power nom. voltage - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 76.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.80 W
- Power dissipation max. - 1.60 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- communication signal - HART, 0.5 .... 10 kHz
- Isolating repeater mode - Yes
- Number of channels - 2
- Transmitter supply mode - No
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 010 X
- ATEX firedamp certificate - DMT 03 ATEX E 010 X
- ATEX gas certificate - DMT 03 ATEX E 010 X
- Certificate EAC - TS RU S-DE.GB04.B.00132
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), Russia (Meteorological certificate), SIL (exida), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Firedamp protection ATEX - I (M1) [Ex ia Ma] I
- Firedamp protection IECEx - [Ex ia Ma] I
- Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 08.0050 X
- IECEx firedamp certificate - IECEx BVS 08.0050 X
- IECEX gas certificate - IECEx BVS 08.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 1.5 kV AC
- Galvanic isolation Ex i input to output - 1.5 kV AC
- Galvanic isolation Ex i to Ex i - 500 V
- Galvanic isolation output to auxiliary power - 350 V AC
- Galvanic isolation output to output - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - The 9163 series isolating repeater for input signals can be used for the intrinsically safe operation of intrinsically safe power sources.
- Highlights - Conversion of Ex i voltage signals in 0/4 ... 20 mA signals Can be used for safety levels up to SIL 2 (IEC/EN 61508)
- Product Description - Isolating repeater input Ex i field circuit
- Product Type - 9163/23-11-10s
- Title Product Variant Technical Data - 9163/23-11-10s HART mA-repeater in
- WebCode - 9163A
Input
- Input - 0/4 ... 20 mA with HART
- Input current max. mA sources - 50 mA
- Input function - Isolation amplifier
- Input functional range - 0 - 24 mA
- Input open circuit voltage U a - ≤ 15,50 V
- Input resistance - ≤ 150 ohms
- Input resistance (AC) HART - ca. 300 Ω
- input signal - 0/4 ... 20 mA with HART
- short-circuit current - ≤ 35 mA
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.177 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Behaviour of the output - = input signal
- deviation - ≤ 0,1 %
- LFD relay - No
- Load R L max. with resistor - 379 Ω
- Load resistance R L - 0 ... 600 Ω (terminal 1+/2- resp. 5+/6-) 0 ... 479 Ω (terminal 3+/2- resp. 4+/6-) (with internal 221 Ω resistor for HART)
- Load resistance R L max. - 600.00 Ω
- Load resistance R L max. HART - 379 ohms
- Load resistance R L max. note - With internal 221 ohm resistor
- Output - 0/4 ... 20 mA with HART
- Output functional range - 0.0 - 24.0 mA
- Output residual ripple - ≤ 40 µAeff
- output signal - 0/4 ... 20 mA with HART
- Settling time 10 … 90 % - ≤ 100 µs
- Temperature influence error limits - ≤ 0,05 % / 10K
Safety Data
- Internal capacitance C i - negligible
- Internal capacitance C i isolating repeater - negligible
- Internal inductance L i - negligible
- Internal inductance L i isolating repeater - negligible
- Max. current I i - 150.0 mA
- Max. power P i - 1000.0 mW
- Max. power P o note - negligible
- Max. voltage U i - 30.0 V
- Max. voltage U o isolation amplifier - Negligible
- Safety-related maximum voltage - 253 V
214921
Conversion of Ex i voltage signals in 0/4 ... 20 mA signals
Can be used for safety levels up to SIL 2 (IEC/EN 61508)
Ambient Conditions
- Ambient temperature - -20 °C ... +70 °C (Single device) -20 °C ... +60 °C (Group assembly)
- Ambient temperature max. - +70 °C
- Ambient temperature max. note - Single device
- Ambient temperature max. note 2 - Group assembly
- Ambient temperature max.2 - +60 °C
- Ambient temperature min. - -20 °C
- Ambient temperature min. 2 - -20 °C
- Ambient temperature min. note - Single device
- Ambient temperature min. note 2 - Group assembly
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - 95%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - 24 V DC
- Auxiliary power nom. voltage - 24 V DC
- Auxiliary power voltage range - 18 ... 31,2 V
- Nominal current - 76.00 mA
- Operation indication - Green "PWR" LED
- Polarity reversal protection - yes
- Power consumption - 1.80 W
- Power dissipation max. - 1.60 W
- Undervoltage monitoring - Yes
- Voltage range residual ripple - ≤ 3,6 VSS
Electrical Data
- communication signal - HART, 0.5 .... 10 kHz
- Isolating repeater mode - Yes
- Number of channels - 2
- Transmitter supply mode - No
Explosion Protection
- Application range (zones) - 2, 22
- ATEX dust certificate - DMT 03 ATEX E 010 X
- ATEX firedamp certificate - DMT 03 ATEX E 010 X
- ATEX gas certificate - DMT 03 ATEX E 010 X
- Certificate EAC - TS RU S-DE.GB04.B.00132
- Certificates - ATEX (BVS), Brazil (ULB), Canada (FM), EAC (STV), IECEx (BVS), India (PESO), Korea (KTL), Russia (Meteorological certificate), SIL (exida), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Firedamp protection ATEX - I (M1) [Ex ia Ma] I
- Firedamp protection IECEx - [Ex ia Ma] I
- Gas explosion protection ATEX - II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
- Gas explosion protection EAC - 2 Ex nA [ia Ga] IIC T4 Gc X
- Gas explosion protection IECEx - Ex nA [ia Ga] IIC T4 Gc
- IECEX dust certificate - IECEx BVS 08.0050 X
- IECEx firedamp certificate - IECEx BVS 08.0050 X
- IECEX gas certificate - IECEx BVS 08.0050 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i input to auxiliary power - 1.5 kV AC
- Galvanic isolation Ex i input to output - 1.5 kV AC
- Galvanic isolation Ex i to Ex i - 500 V
- Galvanic isolation output to auxiliary power - 350 V AC
- Galvanic isolation output to output - 350 V AC
- Test voltage according to standard - IEC EN 60079-11
- Test voltage according to standard 2 - EN 50178
General
- Functional Description - The 9163 series isolating repeater for input signals can be used for the intrinsically safe operation of intrinsically safe power sources.
- Highlights - Conversion of Ex i voltage signals in 0/4 ... 20 mA signals Can be used for safety levels up to SIL 2 (IEC/EN 61508)
- Product Description - Transmitter supply unit Ex i field circuit
- Product Type - 9163/23-11-10k
- Title Product Variant Technical Data - 9163/23-11-10k HART mA-repeater in
- WebCode - 9163A
Input
- Input - 0/4 ... 20 mA with HART
- Input current max. mA sources - 50 mA
- Input function - Isolation amplifier
- Input functional range - 0 - 24 mA
- Input open circuit voltage U a - ≤ 15,50 V
- Input resistance - ≤ 150 ohms
- Input resistance (AC) HART - ca. 300 Ω
- input signal - 0/4 ... 20 mA with HART
- short-circuit current - ≤ 35 mA
Mechanical Data
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Fire resistance (UL 94) - V0
- Grid dimension - 17.60 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.177 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 2.5 mm²
- Conductor cross-section solid max. - 2.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Spring clamp terminal
- Mounting position - horizontal vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Behaviour of the output - = input signal
- deviation - ≤ 0,1 %
- LFD relay - No
- Load R L max. with resistor - 379 Ω
- Load resistance R L - 0 ... 600 Ω (terminal 1+/2- resp. 5+/6-) 0 ... 479 Ω (terminal 3+/2- resp. 4+/6-) (with internal 221 Ω resistor for HART)
- Load resistance R L max. - 600.00 Ω
- Load resistance R L max. HART - 379 ohms
- Load resistance R L max. note - With internal 221 ohm resistor
- Output - 0/4 ... 20 mA with HART
- Output functional range - 0.0 - 24.0 mA
- Output residual ripple - ≤ 40 µAeff
- output signal - 0/4 ... 20 mA with HART
- Settling time 10 … 90 % - ≤ 100 µs
- Temperature influence error limits - ≤ 0,05 % / 10K
Safety Data
- Internal capacitance C i - negligible
- Internal capacitance C i isolating repeater - negligible
- Internal inductance L i - negligible
- Internal inductance L i isolating repeater - negligible
- Max. current I i - 150.0 mA
- Max. power P i - 1000.0 mW
- Max. power P o note - negligible
- Max. voltage U i - 30.0 V
- Max. voltage U o isolation amplifier - Negligible
- Safety-related maximum voltage - 253 V
1 - 6 of 6 Part Numbers