Yodify Product Library
Add the GD10PE IR Extended Point Gas Detector to your store or catalog
Book Your Demo and See How
or create your store
GD10PE IR Extended Point Gas Detector
Brand: Detcon IncThe GD10PE is designed for critical applications involving large volumes of air with high velocity.
In places where you need fast reliable detection of low gas concentrations.
GD10PE is in a class of its own. The versatile GD10PE is suitable for monitoring, among others, the HVAC air intakes of living quarters, temporary refuges and local equipment rooms.
In addition the ventilation air and combustion air intakes of gas turbines can be monitored along with the ventilation air extract duct, the only location where you can guarantee to detect a gas leak on a turbine package.
With a measuring range of 0 to 20% LEL the GD10PE is 5 times more sensitive than standard point detectors.
The GD10 range of infrared gas detectors differ from all other models, because they utilize silicon based solid-state infrared sources.
The complete optomechanical design and constructions is so stable that an ultra fast speed of response can be achieved while providing unparalleled service life and detector stability, thus saving on maintenance and service costs.
An industry standard HART interface is used for configuration of the levels as well as access to maintenance data.
Specifications
Brand
Accuracy
- ± 1 % LEL (0 to 10 % LEL of Reading)
- ± 1.4 % LEL (0 to 20 % LEL of Reading)
Approvals & Certifications
- ATEX: 07-ATEX-1438
- CSA: 1773527
- IECEx: NEM 07.006
- INMETRO: AEX-11698
- SIL 2
Cable Entry
- M20 EExe Cable Gland
Communication
- HART
Consumption
- 3.5 W - Approximately
Current
- 4-20 mA - Sink
Electrical Connectors
- 12 to 22 AWG
- 3-Wire (0.5 to 1.5 mm²)
Enclosure, Body Material
- 316 Stainless Steel - SIS2343
Environmental Protection
- IP66
- IP67
Humidity
- 100 % RH
Load Impedance
- Maximum
Measuring Range
- Ethylene 5,000 ppm
- Methane 0 to 20 % LEL
Media
- Gas - Hydrocarbons
Operating Temperature
- -40° to 65° C (-40° to 149° F)
Output
- 1 mA - Dirty Optics Dirt Accumulation
- 2 mA - Early Clean Optics Prewarning
- 4-20 mA - Standard
Response Time
- 0.6 to 6 seconds
Stability
- ± 1.4 LEL - Lifetime
Storage Temperature
- -40° to 70° C (-40° to 158° F)
Supply Voltage
- 18-32 Vdc
- 24 Vdc
Temperature Range
- 0° to 85° C (32° to 185° F) - Probe, Inside Duct