Yodify Product Library
Instantly add the mA-Isolating Repeater Series 9164 and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
mA-Isolating Repeater Series 9164
Brand: R. STAHL AGThe 9164 series mA isolating repeater allows two 4 to 20 mA signal sources to be coupled. For example, it allows four-conductor transmitters to be connected to I/O cards designed to be operated with two conductors.
The use of this device therefore saves costs by eliminating the need for additional I/O cards or can be used as the only solution for I/O cards that only operate with two conductors.
Features- For installation in Zone 1 or Zone 2 hazardous areas (depending on the variant)
- inputs can be intrinsically safe (Ex i), feature increased safety (Ex e) or be non-Ex
- space-saving, 12-mm wide design
1 - 2 of 2 Part Numbers
224364
For installation in Zone 1 or Zone 2 hazardous areas (depending on the variant)
inputs can be intrinsically safe (Ex i), feature increased safety (Ex e) or be non-Ex
space-saving, 12-mm wide design
Ambient Conditions
- Ambient temperature - -40 °C ... +75 °C
- Ambient temperature max. - +75 °C
- Ambient temperature min. - -40 °C
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326 Use in industrial environment
- Relative humidity max. - ≤ 90%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - without
- Auxiliary power nom. voltage - 30 V
- Nominal current - 30.00 mA
- Polarity reversal protection - yes
- Power dissipation max. - 3.7 V x 20 mA + 20 mA x
- Power dissipation max. 2 - (supply voltage - RL x 20 mA)
Electrical Data
- communication signal - HART, 0.5 ... 5 kHz
- Isolating repeater mode - Yes
- Number of channels - 1
- Transmitter supply mode - No
Explosion Protection
- Application range (zones) - 1, 2, 22
- ATEX dust certificate - BVS 15 ATEX E 068 X
- ATEX gas certificate - BVS 15 ATEX E 068 X
- Certificate EAC - TS RU S-DE.MN04.V.00392
- Certificates - ATEX (BVS), Canada (FM), EAC (TehnoP), IECEx (BVS), Russia (Meteorological certificate), SIL (exida), USA (FM)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface in Division NEC 500 - (Class I, II, III) 1, 2
- Ex interface zone - 0, 1, 2, 20, 21, 22
- Gas explosion protection ATEX - II 2 (1) G Ex ib [ia Ga] IIC T4 Gb
- Gas explosion protection EAC - 1 Ex ib [ia Ga] IIC T4 Gb
- Gas explosion protection IECEx - Ex ib [ia Ga] IIC T4 Gb
- IECEX dust certificate - IECEx BVS 15.0062 X
- IECEX gas certificate - IECEx BVS 15.0062 X
- Installation in Division NEC 500 - (Class I, II, III) 2
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i to Ex i - 500 V AC
- Test voltage according to standard - IEC EN 60079-11
General
- Description - The mA isolating repeaters are used for the connection of 4-wire transmitters to active 2-wire inputs and for the galvanic separation. Input: sink, Ex i Output: sink, Ex i
- Functional Description - The 9164 series mA isolating repeater allows two 4 to 20 mA signal sources to be coupled. For example, it allows four-conductor transmitters to be connected to I/O cards designed to be operated with two conductors. The use of this device therefore saves costs by eliminating the need for additional I/O cards or can be used as the only solution for I/O cards that only operate with two conductors.
- Highlights - For installation in Zone 1 or Zone 2 hazardous areas (depending on the variant) inputs can be intrinsically safe (Ex i), feature increased safety (Ex e) or be non-Ex space-saving, 12-mm wide design
- Product Description - mA isolating repeater Ex i field circuit
- Product Type - 9164/13-20-08
- Product Variant - mA-Isolating repeater
- Title Product Variant Technical Data - 9164/13-20-08 Ex i input
- WebCode - 9164A
Input
- Active supply voltage range - 5 - 30 V
- Input - Ex i: 4 to 20 mA HART (sink)
- Input function - Isolation amplifier
- Input functional range - 3,6 - 25 mA
- Input resistance - > 10 kΩs
- input signal - 3,8 ... 20,5 mA with HART
- voltage drop - < 3,7 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Grid dimension - 12.00 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.090 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 1.5 mm²
- Conductor cross-section solid max. - 1.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - horizontal vertical
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Behaviour of the output - = input signal
- deviation - ≤ 0,1 %
- LFD relay - No
- linearity error - ≤ 0,05 %
- offset error - ≤ 0,05 %
- Output - Ex i: passive HART (sink)
- Output current at I e =0 - 0 mA
- output signal - 3.8 - 20.5 mA with HART
- Settling time 10 … 90 % - ≤ 1 ms
- Temperature influence error limits - ≤ 0,05 % / 10K
Safety Data
- Max. current I i - 150.0 mA
- Max. power P i - 1000.0 mW
- Max. voltage U i - 30.0 V
224365
For installation in Zone 1 or Zone 2 hazardous areas (depending on the variant)
inputs can be intrinsically safe (Ex i), feature increased safety (Ex e) or be non-Ex
space-saving, 12-mm wide design
Ambient Conditions
- Ambient temperature - -40 °C ... +75 °C
- Ambient temperature max. - +75 °C
- Ambient temperature min. - -40 °C
- Electromagnetic compatibility - Tested to the following standards and regulations: EN 61326-1 Use in industrial environment; NAMUR NE 21
- Relative humidity max. - ≤ 90%
- Storage temperature - -40 °C ... +80 °C
- Storage temperature max. - +80 °C
- Storage temperature min. - -40 °C
- Use at the height of - < 2000 m
Auxiliary power
- Auxiliary power - without
- Auxiliary power nom. voltage - 30 V
- Nominal current - 30.00 mA
- Polarity reversal protection - yes
- Power dissipation max. - 4 V x 20 mA + 20 mA x
- Power dissipation max. 2 - (supply voltage - RL x 20 mA)
Electrical Data
- communication signal - HART, 0.5 ... 5 kHz
- Isolating repeater mode - Yes
- Number of channels - 1
- Transmitter supply mode - No
Explosion Protection
- Application range (zones) - 1, 2
- ATEX dust certificate - BVS 15 ATEX E 068 X
- ATEX gas certificate - BVS 15 ATEX E 068 X
- Certificate EAC - TS RU S-DE.MN04.V.00392
- Certificates - ATEX (BVS), EAC (TehnoP), IECEx (BVS), Russia (Meteorological certificate), SIL (exida)
- Dust explosion protection ATEX - II (1) D [Ex ia Da] IIIC
- Dust explosion protection EAC - [Ex ia Da] IIIC
- Dust explosion protection IECEx - [Ex ia Da] IIIC
- Ex interface zone - 1, 2, 21, 22
- Gas explosion protection ATEX - II 2 (1) G Ex e mb [ia Ga] IIC T4 Gb
- Gas explosion protection EAC - 1 Ex e mb [ia Ga] IIC T4 Gb X
- Gas explosion protection IECEx - Ex e mb [ia Ga] IIC T4 Gb
- IECEX dust certificate - IECEx BVS 15.0062 X
- IECEX gas certificate - IECEx BVS 15.0062 X
- Ship approval - CCS, DNVGL
Galvanic isolation
- Galvanic isolation Ex i input to output - 1.5 kV AC
- Test voltage according to standard - IEC EN 60079-11
General
- Description - The mA isolating repeaters are used for the connection of 4-wire transmitters to active 2-wire inputs and for the galvanic separation. Input: sink, Ex e Output: sink, Ex i
- Functional Description - The 9164 series mA isolating repeater allows two 4 to 20 mA signal sources to be coupled. For example, it allows four-conductor transmitters to be connected to I/O cards designed to be operated with two conductors. The use of this device therefore saves costs by eliminating the need for additional I/O cards or can be used as the only solution for I/O cards that only operate with two conductors.
- Highlights - For installation in Zone 1 or Zone 2 hazardous areas (depending on the variant) inputs can be intrinsically safe (Ex i), feature increased safety (Ex e) or be non-Ex space-saving, 12-mm wide design
- Product Description - mA isolating repeater Ex e field circuit
- Product Type - 9164/13-20-06
- Product Variant - mA-Isolating repeater
- Title Product Variant Technical Data - 9164/13-20-06 Ex e input
- WebCode - 9164A
Input
- Active supply voltage range - 5 - 30 V
- Input - Ex e: 4 ... 20 mA HART (sink)
- Input function - Isolation amplifier
- Input functional range - 3,6 - 25 mA
- Input resistance - > 10 kΩs
- input signal - 3,8 ... 20,5 mA with HART
- voltage drop - < 4 V
Mechanical Data
- Connection cross-section - 0.2-2.5 mm² flexible 0.25-2.5 mm² flexible core end sleeve
- Degree of protection (IP) - IP30
- Enclosure material - Polyamide
- Grid dimension - 12.00 mm
- Terminal degree of protection (IP) - IP20
- Weight - 0.140 kg
Mounting / Installation
- Conduct cross-section flexible max. - 0.2 mm²
- Conduct cross-section flexible max. - 1.5 mm²
- Conductor cross-section solid max. - 1.5 mm²
- Conductor cross-section solid min. - 0.2 mm²
- Connection type - Screw terminal
- Mounting position - vertical horizontal
- Mounting type - NS35/15, NS35/7.5 DIN rail
Output
- Behaviour of the output - = input signal
- deviation - ≤ 0,1 %
- LFD relay - No
- linearity error - ≤ 0,05 %
- offset error - ≤ 0,05 %
- Output - Ex i: passive HART (sink)
- Output current at I e =0 - 0 mA
- output signal - 3.8 - 20.5 mA with HART
- Settling time 10 … 90 % - ≤ 1 ms
- Temperature influence error limits - ≤ 0,05 % / 10K
Safety Data
- Max. current I i - 150.0 mA
- Max. power P i - 1000.0 mW
- Max. voltage U i - 30.0 V
- Safety-related maximum voltage - 253 V AC