Brand: Detcon IncThe GD10L provides an effective response to the detection of gas hazards in a wide range of industrial environments from boiler plant rooms to offshore petrochemical installations.
The GD10L safeguards life, environment and property through reliable gas detection over path lengths from 2 meters (6.5 feet) to 30 meters (100 feet).
The IR sources are more resistant to vibration/shock than competing technologies, hence replacement of the IR sources is not necessary during its long service life.
The unit combines a transmitter/ receiver into a single housing and utilizes a novel retro-reflector.
The whole system can be commissionable by a single person.
The retro-reflector is heated to minimize condensation and icing.
Specifications
Brand
Approvals & Certifications
- ATEX 2 II G EExde IIC T6
- IEC Ex: Ex de IIC T6
Consumption
- 120 W, Max.
- Approximately 5 W
Current
- 1 mA - Clean Optics
- 4-20 mA - Current Sink
Distance
- Detection Distance: 6.5 to 100 ft (2 to 30 metres)
Electrical Connectors
- 3-Wire M20 EExe Cable Gland
Enclosure, Body Material
- 316 Stainless Steel - SIS2343
Environmental Protection
- IP66
- IP67
- NEMA 4X
Frequency
- 50 Hz - Flash
Humidity
- 99 % RH, Non-Condensing
Load Impedance
- Maximum
Measuring Range
- 5 LEL.m Methane
Operating Temperature
- -20° to 60° C (-4° to 140° F)
Output
- 4-20 mA Standard
Range
- 100 ft (30 metres)
Repeatability
- Better than 0.1 LEL.m
Response Time
- T50 = 2.5 seconds
- T90 = 5 seconds
RFI/EMI Protection
- EN 500082-2
- EN 50081-1
- EN 50081-2
- EN 50082-1
Stability
- Better than 0.2 LEL.m - Long-term
Supply Voltage
- 18-32 Vdc
- 230 Vac - Retro-Reflector
- Chemical Plants
- Compressor Stations
- FPSOs
- Fuel Loading Facilities
- Offshore Drilling & Production Platforms
- Refineries