ACS880-907 Regenerative Rectifier Unit
Brand: ABB GroupThis supply unit is used in regenerative drive systems to convert three-phase AC voltage to DC voltage.
The unit consists of R8i and L filter modules.
During motoring the input current flows through diodes to the DC bus of the drive system and the supply unit works as a diode bridge.
In regeneration the current flows from the DC bus through the IGBTs to the supply network.
The IGBTs are switched to conduct only once during each network voltage cycle.
This reduces switching losses and enables high input and output powers of the unit.
Unlike with a thyristor bridge, the IGBTs can be switched off at any time which improves reliability.
Features- Power range 294 to 6131 kVA
- Modular design with high power output
- Compact inverter units provides small footprint for assembly
- Same R8i module hardware as with R8i inverter module, but with up to 50% higher current rating (690 V)
- Reliable also during network voltage fluctuations
- Customized product that fulfills your needs
1 - 12 of 6,048 Part Numbers
ACS880-907-0600A-3+E202+E205
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Disconnector*
- Safety Function - None (Not Required)
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains
ACS880-907-0600A-3+E202+E205+F250
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - None (Not Required)
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q951
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Category 0 with Opening the Main Contactor/Breaker, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q951+Q954
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Category 0 with Opening the Main Contactor/Breaker, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q952
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Category 1 with Opening the Main Contactor/Breaker, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q952+Q954
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Category 1 with Opening the Main Contactor/Breaker, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q954
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - None (Not Required)
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q963
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Category 0 with STO, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q963+Q954
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Category 0 with STO, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q964
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Category 1 with STO, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q964+Q954
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Category 1 with STO, with Safety Relay
- Earth Fault Protection - Earth Fault Monitoring, Unearthed Mains
ACS880-907-0600A-3+E202+E205+F250+Q979 +Q973/ +Q972
- Voltage - 400 V (Range 380-415 V)
- Current Rating - 600 A
- EMC Filter - 1st Environment, Restricted Distribution, C2, Grounded Network (TN)
- Output Filter - Du/dt Filters
- Incoming Unit Apparatus - Line Contactor*
- Safety Function - Emergency Stop, Configurable Category 0 or 1 with STO & Safety Functions Module (FSO-12/-21)
- Earth Fault Protection - Earth Fault Monitoring, Earthed Mains
1 - 12 of 6,048 Part Numbers
Specifications
Brand
Voltage & Power Range
- MAins: 294 to 6,131 kVA
- Motor: 3-Phase output Voltage 0 to UN3 /UN5 /UN7
- Mains: 3-Phase, UN7 525-690 V, +10 %/-10 %
- Mains: 3-Phase, UN3 380-415 V, +10 %/-10 %
Frequency
- Motor: 0 to ± 598 Hz
- Mains: 50/60 Hz ± 5 %
Motor Control
- Direct torque Control (DTC)
Storage / Transport Temperature
- -40° to 70° C
Operating Temperature
- 0° to 40° C, No Frost Allowed
- 40° to 50° C with Derating of 1 %/1° C
Certifications & Approvals
- TÜV
- EMC
- RCM, EAC
- cULus, CSA
- RoHS
- LVD
- ATEX
- CE
Environmental Protection
- IP54
- IP42
- IP22
Humidity
- 5 % to 95 % Relative Humidity, no condensation
Altitude
- 0 to 1,000 m, without derating
- 1,000 to 4,000 m, with derating of 1 %/100 m
Cooling Type
- Dry Clean Air Cooling
Documentation
Catalog
Certificate
Manual
- ACS880 multidrive cabinets and modules electrical planning instructions pdf 5.5 MB
- ACS880 regenerative rectifier control program firmware manual pdf 5.0 MB
- ACS880 regenerative rectifier control program firmware manual - Drive composer version pdf 5.0 MB
- ACS880-907 regenerative rectifier units hardware manual pdf 16.0 MB
- BAMU-12C auxiliary measurement unit hardware manual pdf 1.3 MB
- PSL2 data logger file Signals and data word description pdf 3.9 MB
- ACS880 multidrive cabinets and modules safety instructions pdf 1.8 MB