Yodify Product Library
Instantly add the LTU43 Ultrasonic Transmitter - Clamp Mounting and 50,000+ more product series to your store or catalog
Book Your Demo and See How
or create your store
LTU43 Ultrasonic Transmitter - Clamp Mounting
Brand: Intempco Controls, Inc
Features
- SS 316L face material c/w Hygienic Clamp (Tri-Clamp) Mtg. base
- Simple push-button calibration (accurate)
- Output 4-20 mA/20-4 mA (isolated on 4-wire model’s only)
- Built-in temperature compensation
- Optional RS232 or RS485 communications with calibration, diagnostics and data logging software
- PLC compatible
- Three and four wire operation
1 - 1 of 1 Part Numbers
LTU43
- Supply Voltage - 115 Vac (± 20%), 1.7 VA
- Output - 4-20 mA/20-4 mA
- Range - 0.8 to 30 feet (0.24 to 9.1 meters)
- Enclosure Type - PVC, 1/2" NPT x 2 Conduits
- Process Connection - 1-1/2" Hygienic Clamp (Maximum 16 feet Range)
- Communication - No Communication
- Options - Without Option
1 - 1 of 1 Part Numbers
Specifications
Brand
Accuracy
- ± 0.1 % of, Max.
- ± 0.25 % of, Max.
- Loop Powered Display: ± 0.5 % of Reading
Ambient Temperature Range
- -40° to 60° C (-40° to 140° F)
Calibration
- Push Button or Programmable Via Optional Communications Port
Communication
- RS-232
- RS-485
Conduit Connection
- 2 x 1/2” NPT Female
Current
- Loop Powered Display: 150 mA - Max.
Display
- Head Mounted LCD Display
- Loop Powered Display: 4-1/2-Digit LCD 1/2” High
Enclosure, Body Material
- PVC-94V0
Environmental Protection
- IP67
- NEMA 6
Humidity
- Loop Powered Display: 0 to 95 % Non-Condensing
Load Resistance
- Supply Voltage: 750 ohms, Max.
Output
- 20-4 mA
- 4-20 mA
Pressure Range
- bar: 1 to 5
- kPa: 100 to 500
- psi: 14.5 to 72.52
Range
- 0.4 to 30 feet (0.12 to 9.1 metres)
- Loop Powered Display: 3.5-22 mA [22 mA & above = LOE (Loss of Echo)]
Resolution
- Output: 0.006 mA
Sensor, Probe Material
- Sensor: 316L Stainless Steel
Supply Voltage
- 115 Vac (± 20 %), 1.7 VA
- 12-30 Vdc, 0.07 A, Max.
- 230 Vac (± 20 %), 1.7 VA
Temperature Range
- Sanitary Nozzle: -40° to 130° C (-40° to 266° F) for 1/2-Hour Steam Cleaning
- Sanitary Nozzle: -40° to 60° C (-40° to 140° F) for No Steam Cleaning (CIP)
Tri-Clamp Connection
- 1-1/2” Hygienic Tri-Clamp
- 2” Hygienic Tri-Clamp
Voltage Drop
- Loop Powered Display: 0.95 V at 20 mA
- Food & Beverage
- Pharmaceutical
- Water